| 2015-02-27 08:15:26 | BUILDING PLAN REVIEW |
| | PERMIT: 15020073 |
| | ADD: 513 N. SAPODILLA AVE. |
| | CONT: MISO CONSTRUCTION |
| | TEL: ( 561)246-0411 |
| | E-MAIL:[email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 27/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS, |
| | (E) SHUTTERS/ IF WINDOWS ARE NOT IMPACT RESISTANT |
| | TESTED |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) THE COVERSHEET INDICATE THIS IS A LEVEL LL |
| | ALTERATION AND DRYWALL IS TO BE PATCHED, THE PLANS DOES |
| | NOT PROVIDE AS TO HOW MUCH IN AREA THIS DRYWALL PATCH |
| | WORK WILL BE, SECTION 703.4.1 OF THE EXST. BLDG. CODE |
| | MAY APPLY. 703.4.1 SUPPLEMENTAL INTERIOR FINISH |
| | REQUIREMENTS. |
| | WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF |
| | THE FLOOR AREA, SECTION 703.4 SHALL ALSO APPLY TO THE |
| | INTERIOR FINISH IN EXITS AND CORRIDORS SERVING THE WORK |
| | AREA THROUGHOUT THE FLOOR. |
| | |
| | 4) THE PLANS DO NOT INDICATE WHERE THE WORK AREA IS |
| | CLEARLY, DOES THE GUARDRAILS COMPLY WITH EXST. BLDG. |
| | CODE 703.5. |
| | |
| | 5) SHEET A-2 LIST THIS PROJECT AS A R-3 OCCUPANCY, SEE |
| | WIND DESIGN, PLEASE REVISE 2010 FBC-B 310.1 R-2. |
| | APARTMENT HOUSES. |
| | |
| | 6) SHEET A-1 1ST FLOOR VERSES SHEET A-3 THE 2ND FLOOR, |
| | THE 1ST FLOOR SHOWS DROPPED CEILINGS TO RUN THE A/C |
| | DUCT, THE 2ND FLOOR PLANS DO NOT SHOW A HATCHED AREA |
| | BUT IT APPEARS ON THE 2ND FLOOR MECHANICAL SOME OF THE |
| | A/C DROPS WILL BE SIDE WALL WHERE OTHERS WILL BE |
| | CEILING GRILLES. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED, MAY BE A DISSCREPANCY IN THE PLANS. |
| | |
| | 7) SHEET A-3 NOTES TENANT SEPARATION WALL INDICATES IN |
| | NOTE # 1 SOUND INSULATION IS REQUIRED FOR THE TENANT |
| | SEPARATION WALL. PLEASE PROVIDE COMPLIANCE WITH 2010 |
| | FBC-B 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN |
| | CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; |
| | RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| | VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED, |
| | INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED |
| | RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING |
| | UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 8) THE PLANS WILL ALSO NEED ON THE 2ND FLOOR, FLOOR |
| | SYSTEM TO SHOW COMPLIANCE WITH 2010 FBC-B 1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 9) A-3 FLOOR FINISHES SHOW CARPET FOR ALL FLOORS, WILL |
| | THERE BE CARPET IN THE BATHROOMS AND KITCHEN AREAS AS |
| | WELL? THE PLANS ARE NOT CLEAR IF DRYWALL IS BEING |
| | REPLACED IN THE SHOWER COMPARTMENTS AS WELL? 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 10) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1209.2 ATTIC |
| | SPACES. |
| | AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| | BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| | CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| | MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |