Plan Review Details - Permit 15020064
Plan Review Stops For Permit 15020064
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-31 Cont ID  
Sent By shill Date 2015-03-31 Time 17:53 Rev Time 0.00
Received By shill Date 2015-03-31 Time 17:53 Sent To FIRE
Notes
2015-03-31 17:56:18****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE FBC 1609.1, "DECREASES IN WIND LOADS SHALL NOT BE
 MADE FOR THE EFFECT OF SHIELDING BY OTHER STRUCTURES."
 PER ARCHITECT, THIS PROJECT COMPLIES WITH EXPOSURE C.
 SUBMIT A SIGNED, SEALED LETTER FROM ARCHITECT
 CONFIRMING THAT PROPOSED CONSTRUCTION MEETS EXPOSURE C
 DESIGN CRITERIA.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By shill Date 2015-03-03 Time 14:50 Rev Time 0.00
Received By shill Date 2015-03-03 Time 14:50 Sent To FIRE
Notes
2015-03-03 14:58:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE ASCE7-10 AND FBC 1609 REGARDING IMPORTANCE
 FACTOR. HOSPITALS HAVE A GREATER IMPORTANCE FACTOR THAN
 MOST BUILDINGS, YET "0.75" IS STATED AS THE IMPORTANCE
 FACTOR (A NUMBER WHICH TO MY KNOWLEDGE HAS NEVER BEEN
 USED). THAT IS NOT A CLASSIFICATION BUT IT APPEARS THAT
 ARCHITECT IS DESIGNING TO AN IMPORTANTCE FACTOR OF 1.
 IT IS NOTED THAT THIS REPAIR IS TO BE DONE IN A COVERED
 WALKWAY WHICH SERVES AS EMERGENCY EGRESS.
  
 FIRST, CLASSIFY THE STRUCTURES THIS WALKWAY SERVES
 (SITE PLAN, OCCUPANCY CLASSIFICATION OF EACH STRUCTURE
 AFFECTED). A "HOSPITAL" WOULD HAVE AN IMPORTANCE FACTOR
 OF III OR IV, SEE FBC 1604.5. IF BUILDINGS ARE
 CLASSIFIED AS A 1 OR II, BRIEFLY DESCRIBE USE TO
 JUSTIFY THE RISK FACTOR.
  
 IF A LESSER RISK FACTOR THAN THE HIGHEST OF THE TWO
 BUILDINGS IS USED FOR THIS DESIGN, PROVIDE A WRITTEN
 JUSTIFICATION FOR THE REDUCED IMPORTANCE FACTOR. IT
 WOULD APPEAR THAT THE ENTIRE EXIT PATH OF TRAVEL WOULD
 BE REQUIRED TO BE MAINTAINED FOR BOTH EXITING AND
 ACCESS BY EMERGENCY RESPONSE AND OTHERS.
  
 2. EXPOSURE CLASSIFICATION APPEARS INCORRECT, SEE
 DEFINITION OF EXPOSURE C, FBC 1609. PROVIDE A SITE PLAN
 SHOWING THE LOCATION OF THIS STRUCTURE RELATIVE TO THE
 SITE.
  
 3. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD
 ZONE. IF AVAILABLE, PLEASE PROVIDE AN ELEVATION
 CERTIFICATE FOR THE AFFECTED STRUCTURE (S). IF NOT
 AVAILABLE, A COMPLETE ANALYSIS WILL BE DONE TO
 DETERMINE IF THIS IS A SUBSTANTIAL IMPROVEMENT PER CITY
 OF WEST PALM BEACH MUNICIPAL CODE 9494-546(B), FBC 2010
 EXISTING BUILDING 601.3.
  
 4. IT IS NOT CLEAR WHAT "ASCE CATEGORY" IS; PLEASE
 PROVIDE ASCE TABLE REFERENCE. IF THIS IS THE RISK
 FACTOR, PLEASE SEE ITEM 1.
  
 5. PROVIDE A PRODUCT APPROVAL FOR THE ALUMINUM FASCIA
 IF AVAILABLE, FBC 1609, FAC9N-3.
  
 6. REVISE PLAN TO INCLUDE CLASSIFICATION OF WORK, FBC
 2010 EXISTING BUILDING 401.4.
  
 7. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-04-03 Time 10:21 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-04 Cont ID  
Sent By pleduc Date 2015-03-04 Time   Rev Time 0.00
Received By pleduc Date 2015-03-04 Time 13:44 Sent To PC
Notes
2015-03-04 13:54:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE REVIEW ALL OTHE DEPARTMENT COMMENTS AND
 RESUBMIT.
  
 ADDITIONALLY, AS THIS IS A REQUIRED EXIT PATH OF
 TRAVEL, PLEASE PROVIDE A STATEMENT OF INTENT FOR THIS
 ADDITION, INCLUDING IT'S EFFECT/AFFECT ON THE EXISTING
 MEANS OF EGRESS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-03-12 Time 10:55 Sent To  
Notes
2015-03-31 17:56:533/31 TO FIRE
  
  
2015-03-13 10:56:46TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-04 Cont ID  
Sent By pleduc Date 2015-03-04 Time   Rev Time 0.00
Received By pleduc Date 2015-02-03 Time 11:52 Sent To Z
Notes
2015-03-03 15:12:303/3 TO FIRE
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By sgraham Date 2015-03-13 Time 16:07 Rev Time 0.00
Received By sgraham Date 2015-03-13 Time 16:07 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-03-04 Time 13:54 Rev Time 0.00
Received By sgraham Date 2015-02-05 Time 13:55 Sent To B
Notes
2015-02-05 14:00:152/5/15 ZONING FAILED
  
 1. PROVIDE A SITE PLAN HIGHLIGHTING THE LOCATION OF THE
 ALUMINUM FASCIA