Plan Review Details - Permit 15020047
Plan Review Stops For Permit 15020047
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2015-03-02 Cont ID  
Sent By tklarge Date 2015-03-02 Time 11:08 Rev Time 0.00
Received By tklarge Date 2015-03-02 Time 11:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-03-01 Cont ID  
Sent By tklarge Date 2015-03-01 Time 04:40 Rev Time 0.00
Received By tklarge Date 2015-03-01 Time 04:27 Sent To  
Notes
2015-03-01 04:35:581) SHOW THE LOCATION OF THE GAS DRYER ON THE PLAN.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 2) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES.WPB
 AMEND. TO 2010 FBC SEC.107.2.1. 2ND REQUEST.
 3) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 2010 FBCR SEC.G2404.3. 2ND REQUEST.
 4) SUBMIT 2 COPIES OF THE APPLICABLE PIPE SIZING TABLE
 FROM CHAPT.24 OF THE 2010 FBCR. 2ND REQUEST
 5) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM.2010 FBCR SEC,G2413.1.,
 2413.2.2ND REQUEST.
 6) SHOW THE DISTANCE FROM THE METER TO THE FURTHEST OUT
 PER 2010 FBCR SEC.G2413.4.1.2ND REQUEST.
 7) THE PERMIT APPLICATION WORK DESCRIPTION INCLUDES A
 GAS DRYER TO BE INSTALLED BUT IT IS NOT SHOWN ON THE
 GAS PLAN. CLARIFY.
 8) THE "SPECIFICATIONS" THAT WERE SUBMITTED ARE NOT
 ACCEPTABLE. THEY LACK THE REQUIRED INFORMATION
 NEEDED.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 9) A SEPARATE ELECTRICAL PERMIT WILL BE REQUIRED FOR
 THE TANKLESS WATER HEATER FOR THE AUTO IGNITER.
  
 I SUGGEST YOU CONTACT ME TO SET UP AN APPOINTMENT TO
 REVIEW THE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By tklarge Date 2015-02-05 Time 05:49 Rev Time 0.00
Received By tklarge Date 2015-02-05 Time 05:26 Sent To  
Notes
2015-02-05 05:48:481) PLANS DONE IN PENCIL ARE NOT ACCEPTED.
 2) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR ALL GAS APPLIANCES.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 3) ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 2010 FBCR SEC.G2404.3.
 4) SUBMIT 2 COPIES OF THE APPLICABLE PIPE SIZING TABLE
 FROM CHAPT.24 OF THE 2010 FBCR.
 5) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM.2010 FBCR SEC,G2413.1., 2413.2.
 6) SHOW THE DISTANCE FROM THE METER TO THE FURTHEST OUT
 PER 2010 FBCR SEC.G2413.4.1.
 7) INDICATE THE GAS DELIVERY PRESSURE ON THE PLANS.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2015-02-03 09:41:05ROUTED TO PLUMBING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-01 Cont ID  
Sent By tlarge Date 2015-03-01 Time 04:41 Rev Time 0.00
Received By tklarge Date 2015-02-25 Time 11:32 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-05 Cont ID  
Sent By tlarge Date 2015-02-05 Time 05:49 Rev Time 0.00
Received By tklarge Date 2015-02-03 Time 15:02 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-03-01 Cont ID  
Sent By tklarge Date 2015-03-01 Time 04:41 Rev Time 0.00
Received By tklarge Date 2015-03-01 Time 04:37 Sent To  
Notes
2015-03-01 04:40:041) SUBMIT A WATER RISER DIAGRAM FOR THE INSTALLATION OF
 THE TANKLESS WATER HEATER.WPB AMEND. TO 2010 FBC SEC.
 107.3.5.3.11.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  