Plan Review Details - Permit 15020017
Plan Review Stops For Permit 15020017
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By cpuell Date 2015-10-09 Time 09:05 Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-17 Cont ID  
Sent By jwitmer Date 2015-03-17 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2015-03-17 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-13 Cont ID  
Sent By jwitmer Date 2015-02-13 Time 15:44 Rev Time 0.00
Received By jwitmer Date 2015-02-13 Time 13:39 Sent To  
Notes
2015-02-13 15:44:02BUILDING PLAN REVIEW
 PERMIT: 15020017
 ADD: 550 S. ROSEMARY AVE. # 236
 CONT:M. SCIGIANO CONSTRUCTION
 TEL: (561)719-2496
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: FRI. FEB. 13/ 2015
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD HAS NOT INDICATED ON THE
 COVERSHEET, 2.1 SCOPE OF WORK NOR 4.1 EGRESS PLAN
 COMPLIANCE WITH THE 2010 FBC-EXIST. BLDG. CODE 101.5
 COMPLIANCE METHODS.
  
 2) MISSING INFORMATION FOR MINIMUM PLAN REVIEW. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
  
 2.1) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 2.2) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 2.3) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2.4) SHEET 4.1 THE LIFE SAFETY SHEET IS MISSING:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS THE BACK OF HOUSE EXIT IS NOT SHOWN ON PAGE
 4.1 BY THE RESTROOMS NOR DOES IT SHOW BY THE ELEVATOR
 THE EXIT, AND DISCHARGE.
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 3) SHEET THE DEMOLITION PLAN 1.1 SHOWS AN EXISTING
 INDOOR/ OUTDOOR BAR. THE DOORS INTHIS AREA ARE BIFOLD
 DOORS ACORDIAN STYLE TO ONE SIDE ONLY, SHEET 2.1 SHOWS
 THE NORTH DOORS ACCORDIAN STYLE TO ONE SIDE WHERE THE
 EAST DOORS NOW SHOW ACCORDIAN STYLE DOORS ON BOTH SIDES
 OF THE OPENING/
 IS THIS A NEW DOOR CONFIGURATION THAT WILL REQUIRE
 PRODUCT APPROVALS FOR THE OPENING AND THE DESIGNER OF
 RECORD APPROVAL AS WELL.
  
 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS
 FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL
 ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH THIS CODE.
  
 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS
 FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL
 ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH THIS CODE. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR REVIEWING
 AND COORDINATING SUBMITTAL DOCUMENTS PREPARED BY
 OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL ITEMS,
 FOR COMPATIBILITY WITH THE DESIGN OF THE BUILDING.
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4A) SHEET 3.1 AND 4.1 BOTH SHOW THE ELEVATOR SHAFT AND
 AN AREA TO THE RIGHT OF THE ELEVATOR 12 X 14 FT. THIS
 AREA DOES NOT SHOW ANY TYPE OF USAGE, NOTE FROM THE
 FURRTHEST CORNER IN THIS AREA SEE FBC-B 1017.4.3 TABLE
 AND SEATING AISLE ACCESSWAY LENGTH. THE LENGTH OF
 TRAVEL ALONG THE AISLE ACCESSWAY SHALL NOT EXCEED 30
 FEET (9144 MM) FROM ANY SEAT TO THE POINT WHERE A
 PERSON HAS A CHOICE OF TWO OR MORE PATHS OF EGRESS
 TRAVEL TO SEPARATE EXITS.
  
 4B) THE 2ND AREA OF CONCERN IS THE OUTDOOR SEATING AREA
 EAST OF THE MAIN ENTRY, THE NEW PROPOSED BAR HAS A
 LARGER FOOTPRINT & OCCUPANT LOAD, THE ACTUAL OUTDOOR
 SEATING AREA EXIT DISCHARGES IS NOT SHOWN NOR THE
 OCCUPANT LOAD OR EXITING PAST THE NORTH SIDE OF THE
 BAR., COMPLIANCE WITH FBC-B 1017.4.3 APPEARS TO BE A
 PROBLEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-31 Cont ID  
Sent By dhayes Date 2015-03-31 Time 10:47 Rev Time 0.00
Received By dhayes Date 2015-03-31 Time 09:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-09 Cont ID  
Sent By dhayes Date 2015-02-09 Time 16:35 Rev Time 0.00
Received By dhayes Date 2015-02-09 Time 16:35 Sent To  
Notes
2015-02-09 16:44:172/9/2015
 PROJECT: LAFAYETTES MISIC ROOM
 PERMIT#: 15020017
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED.
  
 1) PROVIDE EXIT AND EMERGENCY LIGHTING AS REQUIRED. SEE
 NFPA 101 SECTION 7.10.1.5.1, NEC 700.16, NEC 700.12.
  
 2) PROVIDE PANEL SCHEDULES WITH CIRCUIT NUMBERS
 CORRESPONDING TO THE FLOOR PLAN. NEC 408.4
  
 3) PROVIDE LIGHTING CONTROL AS REQUIRED BY FBC 505.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-12 Cont ID  
Sent By pleduc Date 2015-03-12 Time   Rev Time 0.00
Received By pleduc Date 2015-03-12 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-02-05 Time   Rev Time 0.00
Received By pleduc Date 2015-02-05 Time 12:42 Sent To  
Notes
2015-02-05 14:12:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET 1.1 INDICATES THAT THE ENTRY DOOR TO BE CLOSED
 AND LOCKED.
  
 SHEET 4.1 INDICATES A EXIT PATH PLAN. NO OCCUPANCY
 LOADS OR CALCULATIONS ARE PROVIDED. COMMON PATH OF
 TRAVEL DIMENSIONS ARE NOT PROVIDED. AN EXIT PATH ON THE
 BOTTON LEFT OF THE PAGE DOES NOT SHOW THE EXIT. EXIT
 CORRIDOR AND EXIT DOOR WIDTHS ARE NOT PROVIDED. THE
 DOOR EXIT DOORS OPENING TO THE PATIO CAN NOT BE COUNTED
 AS TWO SEPARATE EXITS. THE PROVIDED EXITS DO NOT MEET
 THE REQUIREMENTS OF SECTION NFPA 101, 7.5.1.3.3, IN
 BUILDINGS PROTECTED THROUGHOUT BY A SPRINKLER SYSTEM,
 THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS OR
 EXIT ACCESS DOORS SHALL BE NOT LESS THAN ONE-THIRD THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA BEING SERVED.
  
 THE ENTRY DOOR NOTED ABOVE SHALL REMAIN OPEN AND
 FUNCTION AS AN EXIT.
  
 RESUBMIT PLANS SHOWING CORRECTIONS NOTED ABOVE OR
 SUBMIT JUSTIFICATION FOR THE ELIMINATION OF THE ENTRY
 DOOR WITHIN THE REQUIREMENTS OF THE FIRE CODE.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-09 Cont ID  
Sent By jwitmer Date 2015-10-09 Time 09:05 Rev Time 0.00
Received By cpuell Date 2015-04-29 Time 16:59 Sent To B
Notes
2015-04-29 16:59:58ROUTE TO J. WITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-15 Cont ID  
Sent By eschneid Date 2015-04-15 Time 10:07 Rev Time 0.00
Received By eschneid Date 2015-04-09 Time 12:57 Sent To  
Notes
2015-04-09 12:57:24****EXPEDITED****
 TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-09 Cont ID  
Sent By shill Date 2015-04-03 Time 12:58 Rev Time 0.00
Received By shill Date 2015-03-09 Time   Sent To  
Notes
2015-03-09 17:35:08SENT TO C16.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-09 Cont ID  
Sent By   Date 2015-03-09 Time   Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 14:29 Sent To  
Notes
2015-02-03 14:33:50SENT TO C11 BIN FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-02-13 Cont ID  
Sent By   Date 2015-02-13 Time   Rev Time  
Received By   Date 2015-02-13 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-02-17 Cont ID  
Sent By skennedy Date 2015-02-17 Time 17:32 Rev Time 0.00
Received By skennedy Date 2015-02-17 Time 17:32 Sent To  
Notes
2015-02-17 17:33:21NO MECHANICAL SHOWN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By tklarge Date 2015-02-04 Time 14:37 Rev Time 0.00
Received By tklarge Date 2015-02-04 Time 13:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2015-04-15 Cont ID  
Sent By eschneid Date 2015-04-15 Time 10:05 Rev Time 0.50
Received By eschneid Date 2015-04-15 Time 10:05 Sent To  
Notes
2015-04-15 10:07:25SIGNS AND AWNINGS REQUIRE SEPARATE PERMITS WITH PLANS.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-04-03 Cont ID  
Sent By eschneid Date 2015-04-03 Time 11:33 Rev Time 0.25
Received By eschneid Date 2015-04-03 Time 11:33 Sent To  
Notes
2015-04-03 11:33:49FAILED
  
 1) REPEAT COMMENT: PROVIDE A SHEET WITH A SITE PLAN
 THAT SHOWS THE FEATURES (PLANTERS AND OTHER FIXED
 OBJECTS) IN THE PLAZA NORTH AND WEST OF THE NEW BAR AND
 SEATING. THE PLAN SHALL BE TO SCALE AND INCLUDE
 DIMENSION LINES TO VERIFY THAT THERE IS ADEQUATE ROOM
 FOR PEDESTRIAN MOBILITY THROUGH THIS AREA.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-24 Cont ID  
Sent By eschneid Date 2015-02-24 Time 10:19 Rev Time 0.50
Received By eschneid Date 2015-02-24 Time 08:53 Sent To  
Notes
2015-02-24 10:25:46FAILED
  
 1) PROVIDE A SHEET WITH A SITE PLAN THAT SHOWS THE
 FEATURES (PLANTERS AND OTHER FIXED OBJECTS) IN THE
 PLAZA NORTH AND WEST OF THE NEW BAR AND SEATING. THE
 PLAN SHALL BE TO SCALE AND INCLUDE DIMENSION LINES TO
 VERIFY THAT THERE IS ADEQUATE ROOM FOR PEDESTRIAN
 MOBILITY THROUGH THIS AREA.
  
 2) PROVIDE ELEVATION DRAWINGS OF THE NEW BAR AREA.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2015-02-10 10:34:112-10-15