| Plan Review Stops For Permit 15011051 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-02-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-02-03 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-02-03 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-01-31 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-01-31 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2015-01-31 09:30:53 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | FBC 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, | | | THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE | | | AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, | | | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND | | | RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. | | | PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE | | | COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE | | | SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR | | | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH | | | THE CONSTRUCTION DOCUMENTS. | | | | | | 1) SPECIFY THE ROOF SLOPE AND MEAN ROOF HEIGHT. | | | | | | 2) SPECIFY TYPE AND NUMBER OF MECHANICAL FASTENERS THAT | | | WILL BE USED TO ATTACH THE FLAT CONCRETE TILES. |
|
|
|