| Plan Review Stops For Permit 15011048 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-06-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-06-18 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-16 |
Time |
18:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-28 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-27 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2015-05-28 16:39:55 | PLAN REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION | | | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2 | | | CODE COMPLIANCE CERTIFICATION. | | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | 2 THE ELEVATIONS ON SHEETS A.09 INDICATES THAT THE | | | DOORS AND WINDOWS IN THE ENTRY FOYER ARE 9'-0" IN | | | HEIGHT AND THE FLOOR PLAN ON A.04 CALLS OUT 8'-0" TALL | | | WINDOWS AND DOORS. PLEASE CLARIFY. FBC 107.2.1 | | | | | | 3) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN | | | PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS | | | WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN | | | THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC | | | 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO | | | BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH | | | THE 8' TALL WINDOWS IN THE NEW ENTRY FOYER. | | | | | | 4) THE CORRECTED RAS 117 CALCULATIONS FOR THE BUILT UP | | | ROOFING ARE REQUIRED TO HAVE THE ENGINEER'S SEAL AND | | | ORIGINAL HANDWRITTEN SIGNATURE. COPIES AND OTHER | | | FACSIMILES ARE NOT ACCEPTABLE. FS 471 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-12 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-11 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2015-03-12 07:59:32 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) ON SHEET A.02 THE NOTES FOR THE BRICK BBQ HAVE BEEN | | | PRINTED OVER AND ARE ILLEGIBLE. PLEASE CORRECT. FBC | | | 107.2.1 | | | | | | 2) ON SHEET A.12 THE STRUCTURAL CRITERIA CONTAINS | | | MISTAKES. THE PROJECT IS LOCATED IN A WINDBORNE DEBRIS | | | REGION AND THE RISK CATEGORY ( WIND IMPORTANCE FACTOR ) | | | SHOULD BE II. FBC 1609.2 & 1604.5 | | | | | | 3) THE WINDOW AND DOOR BUCK DETAILS ON SHEET A1.2 DO | | | NOT SPECIFY THE ANCHOR SPACING FOR THE TAPCONS. FBC | | | 107.2.1 | | | | | | 4) ON SHEET 6 OF THE STRUCTURAL DRAWINGS THE EXPOSURE | | | CATEGORY IS INCORRECTLY SPECIFIED AS "C". THE PROJECT | | | IS LOCATED WITHIN 600 FEET OF THE INTERCOASTAL WATER | | | WAY AND IS EXPOSURE "D". PLEASE CHECK TO SEE THAT ALL | | | COMPONENT AND CLADDING PRESSURES ON THE PLANS ARE FOR | | | EXPOSURE "D". | | | | | | 5) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION | | | SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER | | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | | 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2 | | | CODE COMPLIANCE CERTIFICATION. | | | THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | | RENOVATION. | | | | | | 6) ON SHEET 1 OF THE STRUCTURAL DRAWINGS SOME OF THE C4 | | | COLUMNS ARE NOT MARKED AT THE COVERED LOGGIA. FBC | | | 107.2.1 | | | | | | 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT | | | APPROVALS FOR THE ASPHALT SHINGLE OR METAL ROOFING, | | | HORIZONTAL ROLLING WINDOWS AND THE STRUCTURAL MULLIONS. | | | | | | 8) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN | | | PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS | | | WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN | | | THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC | | | 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO | | | BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH | | | THE 8' TALL WINDOWS IN THE NEW FOYER. | | | | | | 9) THE RAS 117 CALCULATIONS FOR THE BUILT UP ROOFING | | | MATERIAL SPECIFY THE FASTENER SPACING FOR THE CORNER | | | AREAS AS 3.4" O.C. RAS 117 SECTION 8.1 SPECIFIES THAT | | | THE MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN | | | 4 IN. O.C. PLEASE REVISE THE CALCULATIONS. | | | | | | 10) ASPHALT SHINGLES ARE SPECIFIED TO BE INSTALLED ON | | | THE GARAGE ON SHEET A.01 AND THE ELEVATIONS SHOW A NEW | | | METAL ROOF. CLARIFY. FBC 107.2.1 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-06-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-06-17 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-16 |
Time |
18:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-28 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-27 |
Time |
19:07 |
Sent To |
|
|
| Notes |
| 2015-05-28 08:07:01 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. NEW COMMENT | | | : SPECIFY THE OVERCURRENT PROTECTION AND WIRE SIZES FOR | | | EACH CIRCUIT IN THE PANEL SCHEDULE. | | | | | | 2) AS SHOWN ON THE RISER DIAGRAM, THE #1CU FEEDER WIRES | | | TO THE 150 AMP PANEL ARE UNDERSIZED. WHEN THERE IS MORE | | | THAN ONE PANEL FEEDERS ARE REQUIRED TO BE SIZED IN | | | ACCORDANCE WITH NEC TABLE 310.16. THE SMALLEST SIZE | | | FEEDERS FOR A 150 AMP PANEL IN THIS DESIGN ARE 1/0 CU. | | | | | | 3) THE PANEL SCHEDULE ON SHEET A.11 FOR PANEL 'A' IS | | | INCORRECTLY LABELED AS 100 AMP. IT SHOULD BE 150 AMP | | | ACCORDING TO THE RISER DIAGRAM. FBC 107.2.1 | | | | | | 4) SERVICE DISCONNECT IS REQUIRED FOR NEW A/C | | | CONDENSING UNIT AT GYM. NEC 440.11 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-12 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-12 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2015-03-12 15:19:50 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. | | | | | | 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. | | | | | | 3) NEC 240.24(A) & (B) PANELS SHALL BE READILY | | | ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. | | | SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL | | | FLOOR PLAN. | | | | | | 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. THE | | | RECEPTICALS FOR THE GARAGE DOOR OPENERS SHALL BE GFCI | | | PROTECTED. | | | | | | 5) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL | | | BE PROVIDED. | | | | | | 6) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE | | | BONDED. | | | | | | 7) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLETS. | | | | | | 8) LUMINAIRES IN CLOTHES CLOSETS SHALL OF THE TYPE | | | PERMITTED AND LOCATED AS REQUIRED BY NEC 410.16 (A) - | | | (C) . | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-12 |
Time |
05:17 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-06-12 |
Time |
05:16 |
Sent To |
|
|
| Notes |
| 2015-06-12 05:17:33 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE | | | ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-06-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-06-18 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-08 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-05-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-28 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-01 |
Time |
17:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-04-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-03-19 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2015-04-07 15:38:16 | NEW CONTRACTOR STEVE CURRY REQUESTED THAT PLANS BE | | | REMOVED FROM REVIEW UNTIL HE RESUBMITS WITH NEW | | | DOCUMENTS. RM | | 2015-03-20 06:54:07 | R19 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-12 |
Time |
16:18 |
Rev Time |
|
| Received By |
rmcdouga |
Date |
2015-01-29 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-27 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-27 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2015-05-27 15:57:15 | MU-2015-6347 NO IMPACT FEES WERE DUE. | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-03-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-11 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-11 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2015-03-11 19:00:44 | THE PLANS SHOW THAT THE OPEN BREEZEWAY IS TO BE | | | ENCLOSED TO CREATE AN ENTRY FOYER. BEFORE A PERMIT TO | | | CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF PLANS | | | SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY | | | FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE | | | STAMP AND A COPY OF THE PAID RECEIPT MUST BE RETURNED | | | TO THE CITY BUILDING DEPARTMENT BEFORE THE BUILDING | | | PERMIT CAN BE ISSUED. FOR INFORMATION CALL PALM BEACH | | | COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2015-05-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-05-27 |
Time |
18:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-05-27 |
Time |
18:47 |
Sent To |
|
|
| Notes |
| 2015-05-27 18:49:25 | SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR | | | MEECHANICAL. THE VALUE OF THE MECHANICAL WORK IS TO BE | | | REMOVED FROM THE PRIME PERMIT AND DECLARED ON THE | | | SEPARATE MECHANICAL PERMIT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-03-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-12 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-03-12 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2015-03-12 13:44:05 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | 2) FBC - 107.3.5.3 PROVIDE MECHANICAL PLANS. FBC | | | -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA: | | | SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN | | | EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | | | 3) PLEASE CLARIFY THE LOCATION OF THE AIR HANDLER THAT | | | IS LOCATED IN THE ATTIC. THE PLANS INDICATE THAT THE | | | EXISTING PITCHED ROOF OF THE HOUSE IS TO BE REPLACED | | | WITH NEW LOW SLOPE ROOF TRUSSES. WILL THERE BE ENOUGH | | | ROOM FOR THE AIR HANDLER? ALSO IT APPEARS THAT ALL OF | | | THE DUCT WORK IN THE ATTIC WILL NEED TO BE REMOVED AND | | | REPLACED. | | | | | | 4) THE DEMO PLANS SPECIFY THAT THE TWO MINI-SPLITS AT | | | THE GARAGE WILL REMAIN AND SHEET A.05 SHOWS ONE NEW AC | | | UNIT. PLEASE CLARIFY. FBC 107.2.1 | | | | | | 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | | | 6) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. | | | | | | 7) FBC-R - M1305.1.3 APPLIANCES IN ATTICS. | | | ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN | | | OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE | | | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT | | | NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES | | | (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG | | | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM | | | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE | | | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 | | | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE | | | SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES | | | (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE | | | APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS | | | OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY | | | 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW | | | REMOVAL OF THE LARGEST APPLIANCE. | | | | | | 8) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS. | | | A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE | | | REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN | | | ACCORDANCE WITH CHAPTER 34. | | | | | | 9) FBC-R - M1305.1.3.2 AIR-HANDLING UNITS. | | | AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE | | | FOLLOWING CONDITIONS ARE MET: | | | 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN | | | 6 FEET (1829 MM) OF AN ATTIC ACCESS. | | | 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE | | | UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING | | | PROPERLY. | | | 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO | | | REPLACE THE AIR HANDLER. | | | 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL | | | INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS | | | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL | | | CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST | | | PARAGRAPH IN BOLD: | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-12 |
Time |
05:13 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-06-12 |
Time |
04:36 |
Sent To |
|
|
| Notes |
| 2015-06-12 05:15:47 | PROVISO: S & S SANITARY & WATER RISERS THAT CORRELATE | | | W/ FLOOR PLAN TO BE ONSITE @ ROUGH PLBG. INSPECTION. | | | MANUF. SPECS & INSTALLATION MANUALS FOR GAS EQUIPMENT | | | TO BE ONSITE FOR ROUGH GAS INSP. | | | SEPARATE PERMIT REQD. FOR GAS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-05-16 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-05-16 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-05-16 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2015-05-16 10:17:08 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM THAT | | | CORRELATES WITH THE FLOOR PLANS,WPB AMEND. TO 2010 FBC | | | SSEC.107.2.1. | | | 2) IDENTIFY THE ROOMS ON BOTH OF THE RISERS. AS NOW | | | DRAWN, IT IS EXTREMELY DIFFICULT TO REVIEW. | | | 3) IDENTIFY THE GYM BATH ON THE SANITARY RISER. ,WPB | | | AMEND. TO 2010 FBC SSEC.107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-02-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-02-05 |
Time |
05:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-02-05 |
Time |
04:15 |
Sent To |
|
|
| Notes |
| 2015-02-05 05:20:21 | 1) THE PLANS SHALL BE SIGNED AND SEALED BY THE | | | ARCHITECT PER THE FL. ADMIN. CODE RULE 61G1-16.001. | | | 2) SUBMIT MANUF. SPECS/INSTALLATION MANUAL FOR ALL GAS | | | APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER | | | THE FBCR SEC. G2404.3. | | | 3) IDENTIFY ALL THE BATHS ON THE FLOOR PLAN SHT.A.04. | | | THE NAMES OF THE BATHS ON THE FLOOR PLAN DO NOT MATCH | | | THE NAMES ON THE PLBG. RISER. CLARIFY. WPB AMEND. TO | | | 2010 FBC SEC. 107.2.1. | | | 4)THE PREP SINK IN THE KITCHEN IS NOT SHOWN ON THE | | | KITCHEN SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1. | | | 5) CLEANOUTS ARE REQUIRED IN ALL STACKS PER 2010 FBCR | | | SEC.P3005.2.6. | | | 6) SUBMIT A WATER RISER DIAGRAM FOR NEW BATHS.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 7) IDENTIFY THE PIECE OF EQUIPMENT MARKED "WP" IN THE | | | UTILITY ROOM.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-06-12 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-12 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2015-05-08 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-05-08 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-05-08 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2015-05-08 15:06:50 | 3RD CHECKLIST 5/8/15 ZONING FAILED | | | | | | 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-03-20 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-03-20 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-03-20 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2015-03-20 12:55:08 | 3/20/15 ZONING FAILED | | | | | | 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-02-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-02-04 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-02-04 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2015-02-04 11:41:30 | 2/4/15 ZONING FAILED. | | | | | | 1. PROVIDE TWO UP TO DATE SURVERYS OF THE PROPERTY. |
|
|