Plan Review Details - Permit 15011048
Plan Review Stops For Permit 15011048
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-18 Cont ID  
Sent By rmcdouga Date 2015-06-18 Time 17:03 Rev Time 0.00
Received By rmcdouga Date 2015-06-16 Time 18:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-28 Cont ID  
Sent By rmcdouga Date 2015-05-28 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2015-05-27 Time 15:57 Sent To  
Notes
2015-05-28 16:39:55PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2
 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 2 THE ELEVATIONS ON SHEETS A.09 INDICATES THAT THE
 DOORS AND WINDOWS IN THE ENTRY FOYER ARE 9'-0" IN
 HEIGHT AND THE FLOOR PLAN ON A.04 CALLS OUT 8'-0" TALL
 WINDOWS AND DOORS. PLEASE CLARIFY. FBC 107.2.1
  
 3) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN
 PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS
 WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN
 THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC
 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO
 BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH
 THE 8' TALL WINDOWS IN THE NEW ENTRY FOYER.
  
 4) THE CORRECTED RAS 117 CALCULATIONS FOR THE BUILT UP
 ROOFING ARE REQUIRED TO HAVE THE ENGINEER'S SEAL AND
 ORIGINAL HANDWRITTEN SIGNATURE. COPIES AND OTHER
 FACSIMILES ARE NOT ACCEPTABLE. FS 471
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By rmcdouga Date 2015-03-12 Time 13:27 Rev Time 0.00
Received By rmcdouga Date 2015-03-11 Time 18:56 Sent To  
Notes
2015-03-12 07:59:32PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET A.02 THE NOTES FOR THE BRICK BBQ HAVE BEEN
 PRINTED OVER AND ARE ILLEGIBLE. PLEASE CORRECT. FBC
 107.2.1
  
 2) ON SHEET A.12 THE STRUCTURAL CRITERIA CONTAINS
 MISTAKES. THE PROJECT IS LOCATED IN A WINDBORNE DEBRIS
 REGION AND THE RISK CATEGORY ( WIND IMPORTANCE FACTOR )
 SHOULD BE II. FBC 1609.2 & 1604.5
  
 3) THE WINDOW AND DOOR BUCK DETAILS ON SHEET A1.2 DO
 NOT SPECIFY THE ANCHOR SPACING FOR THE TAPCONS. FBC
 107.2.1
  
 4) ON SHEET 6 OF THE STRUCTURAL DRAWINGS THE EXPOSURE
 CATEGORY IS INCORRECTLY SPECIFIED AS "C". THE PROJECT
 IS LOCATED WITHIN 600 FEET OF THE INTERCOASTAL WATER
 WAY AND IS EXPOSURE "D". PLEASE CHECK TO SEE THAT ALL
 COMPONENT AND CLADDING PRESSURES ON THE PLANS ARE FOR
 EXPOSURE "D".
  
 5) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. FBC ENERGY CONSERVATION - SECT. 103.2.3.2
 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 6) ON SHEET 1 OF THE STRUCTURAL DRAWINGS SOME OF THE C4
 COLUMNS ARE NOT MARKED AT THE COVERED LOGGIA. FBC
 107.2.1
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE PRODUCT
 APPROVALS FOR THE ASPHALT SHINGLE OR METAL ROOFING,
 HORIZONTAL ROLLING WINDOWS AND THE STRUCTURAL MULLIONS.
  
 8) THERE ARE MULTIPLE GLASS TYPES WITH DIFFERENT DESIGN
 PRESSURES IN THE PRODUCT APPROVAL FOR THE FIXED GLASS
 WINDOWS ( NOA NO.12-1218.11). PLEASE MARK THE ITEMS IN
 THE APPROPRIATE TABLE THAT APPLY TO THIS JOB. FBC
 107.2.1 & FBC R301.2.1 NOTE: THERE DOES NOT APPEAR TO
 BE A SIZE LISTED IN THE TABLES THAT IS COMPATABILE WITH
 THE 8' TALL WINDOWS IN THE NEW FOYER.
  
 9) THE RAS 117 CALCULATIONS FOR THE BUILT UP ROOFING
 MATERIAL SPECIFY THE FASTENER SPACING FOR THE CORNER
 AREAS AS 3.4" O.C. RAS 117 SECTION 8.1 SPECIFIES THAT
 THE MINIMUM FASTENER SEPARATION SHALL NOT BE LESS THAN
 4 IN. O.C. PLEASE REVISE THE CALCULATIONS.
  
 10) ASPHALT SHINGLES ARE SPECIFIED TO BE INSTALLED ON
 THE GARAGE ON SHEET A.01 AND THE ELEVATIONS SHOW A NEW
 METAL ROOF. CLARIFY. FBC 107.2.1
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-17 Cont ID  
Sent By rmcdouga Date 2015-06-17 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2015-06-16 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-28 Cont ID  
Sent By rmcdouga Date 2015-05-28 Time 08:53 Rev Time 0.00
Received By rmcdouga Date 2015-05-27 Time 19:07 Sent To  
Notes
2015-05-28 08:07:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. NEW COMMENT
 : SPECIFY THE OVERCURRENT PROTECTION AND WIRE SIZES FOR
 EACH CIRCUIT IN THE PANEL SCHEDULE.
  
 2) AS SHOWN ON THE RISER DIAGRAM, THE #1CU FEEDER WIRES
 TO THE 150 AMP PANEL ARE UNDERSIZED. WHEN THERE IS MORE
 THAN ONE PANEL FEEDERS ARE REQUIRED TO BE SIZED IN
 ACCORDANCE WITH NEC TABLE 310.16. THE SMALLEST SIZE
 FEEDERS FOR A 150 AMP PANEL IN THIS DESIGN ARE 1/0 CU.
  
 3) THE PANEL SCHEDULE ON SHEET A.11 FOR PANEL 'A' IS
 INCORRECTLY LABELED AS 100 AMP. IT SHOULD BE 150 AMP
 ACCORDING TO THE RISER DIAGRAM. FBC 107.2.1
  
 4) SERVICE DISCONNECT IS REQUIRED FOR NEW A/C
 CONDENSING UNIT AT GYM. NEC 440.11
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By rmcdouga Date 2015-03-12 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2015-03-12 Time 15:16 Sent To  
Notes
2015-03-12 15:19:50PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 2) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE.
  
 3) NEC 240.24(A) & (B) PANELS SHALL BE READILY
 ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS.
 SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL
 FLOOR PLAN.
  
 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED. THE
 RECEPTICALS FOR THE GARAGE DOOR OPENERS SHALL BE GFCI
 PROTECTED.
  
 5) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 6) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 7) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 8) LUMINAIRES IN CLOTHES CLOSETS SHALL OF THE TYPE
 PERMITTED AND LOCATED AS REQUIRED BY NEC 410.16 (A) -
 (C) .
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 05:17 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 05:16 Sent To  
Notes
2015-06-12 05:17:33GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-18 Cont ID  
Sent By rmcdouga Date 2015-06-18 Time 17:03 Rev Time 0.00
Received By rmcdouga Date 2015-06-08 Time 16:24 Sent To  
Notes
2015-06-09 16:29:03R22
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-28 Cont ID  
Sent By rmcdouga Date 2015-05-28 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2015-05-01 Time 17:35 Sent To  
Notes
2015-05-01 17:35:15R22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2015-04-07 Time   Rev Time 0.00
Received By shill Date 2015-03-19 Time 06:49 Sent To  
Notes
2015-04-07 15:38:16NEW CONTRACTOR STEVE CURRY REQUESTED THAT PLANS BE
 REMOVED FROM REVIEW UNTIL HE RESUBMITS WITH NEW
 DOCUMENTS. RM
2015-03-20 06:54:07R19
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-12 Cont ID  
Sent By rmcdouga Date 2015-03-12 Time 16:18 Rev Time  
Received By rmcdouga Date 2015-01-29 Time   Sent To  
Notes
2015-01-31 08:20:00R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-05-27 Cont ID  
Sent By rmcdouga Date 2015-05-27 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2015-05-27 Time 15:44 Sent To  
Notes
2015-05-27 15:57:15MU-2015-6347 NO IMPACT FEES WERE DUE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-11 Cont ID  
Sent By rmcdouga Date 2015-03-11 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2015-03-11 Time 19:00 Sent To  
Notes
2015-03-11 19:00:44THE PLANS SHOW THAT THE OPEN BREEZEWAY IS TO BE
 ENCLOSED TO CREATE AN ENTRY FOYER. BEFORE A PERMIT TO
 CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF PLANS
 SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY
 FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE
 STAMP AND A COPY OF THE PAID RECEIPT MUST BE RETURNED
 TO THE CITY BUILDING DEPARTMENT BEFORE THE BUILDING
 PERMIT CAN BE ISSUED. FOR INFORMATION CALL PALM BEACH
 COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By rmcdouga Date 2015-05-27 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2015-05-27 Time 18:47 Sent To  
Notes
2015-05-27 18:49:25SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR
 MEECHANICAL. THE VALUE OF THE MECHANICAL WORK IS TO BE
 REMOVED FROM THE PRIME PERMIT AND DECLARED ON THE
 SEPARATE MECHANICAL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By rmcdouga Date 2015-03-12 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2015-03-12 Time 13:29 Sent To  
Notes
2015-03-12 13:44:05PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC - 107.3.5.3 PROVIDE MECHANICAL PLANS. FBC
 -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA:
 SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN
 EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 3) PLEASE CLARIFY THE LOCATION OF THE AIR HANDLER THAT
 IS LOCATED IN THE ATTIC. THE PLANS INDICATE THAT THE
 EXISTING PITCHED ROOF OF THE HOUSE IS TO BE REPLACED
 WITH NEW LOW SLOPE ROOF TRUSSES. WILL THERE BE ENOUGH
 ROOM FOR THE AIR HANDLER? ALSO IT APPEARS THAT ALL OF
 THE DUCT WORK IN THE ATTIC WILL NEED TO BE REMOVED AND
 REPLACED.
  
 4) THE DEMO PLANS SPECIFY THAT THE TWO MINI-SPLITS AT
 THE GARAGE WILL REMAIN AND SHEET A.05 SHOWS ONE NEW AC
 UNIT. PLEASE CLARIFY. FBC 107.2.1
  
 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
  
 6) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 7) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 8) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 9) FBC-R - M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-12 Cont ID  
Sent By tklarge Date 2015-06-12 Time 05:13 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 04:36 Sent To  
Notes
2015-06-12 05:15:47PROVISO: S & S SANITARY & WATER RISERS THAT CORRELATE
 W/ FLOOR PLAN TO BE ONSITE @ ROUGH PLBG. INSPECTION.
 MANUF. SPECS & INSTALLATION MANUALS FOR GAS EQUIPMENT
 TO BE ONSITE FOR ROUGH GAS INSP.
 SEPARATE PERMIT REQD. FOR GAS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-16 Cont ID  
Sent By tklarge Date 2015-05-16 Time 11:25 Rev Time 0.00
Received By tklarge Date 2015-05-16 Time 09:33 Sent To  
Notes
2015-05-16 10:17:081) SUBMIT A SANITARY AND WATER RISER DIAGRAM THAT
 CORRELATES WITH THE FLOOR PLANS,WPB AMEND. TO 2010 FBC
 SSEC.107.2.1.
 2) IDENTIFY THE ROOMS ON BOTH OF THE RISERS. AS NOW
 DRAWN, IT IS EXTREMELY DIFFICULT TO REVIEW.
 3) IDENTIFY THE GYM BATH ON THE SANITARY RISER. ,WPB
 AMEND. TO 2010 FBC SSEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By tklarge Date 2015-02-05 Time 05:20 Rev Time 0.00
Received By tklarge Date 2015-02-05 Time 04:15 Sent To  
Notes
2015-02-05 05:20:211) THE PLANS SHALL BE SIGNED AND SEALED BY THE
 ARCHITECT PER THE FL. ADMIN. CODE RULE 61G1-16.001.
 2) SUBMIT MANUF. SPECS/INSTALLATION MANUAL FOR ALL GAS
 APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED PER
 THE FBCR SEC. G2404.3.
 3) IDENTIFY ALL THE BATHS ON THE FLOOR PLAN SHT.A.04.
 THE NAMES OF THE BATHS ON THE FLOOR PLAN DO NOT MATCH
 THE NAMES ON THE PLBG. RISER. CLARIFY. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 4)THE PREP SINK IN THE KITCHEN IS NOT SHOWN ON THE
 KITCHEN SANITARY RISER. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) CLEANOUTS ARE REQUIRED IN ALL STACKS PER 2010 FBCR
 SEC.P3005.2.6.
 6) SUBMIT A WATER RISER DIAGRAM FOR NEW BATHS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 7) IDENTIFY THE PIECE OF EQUIPMENT MARKED "WP" IN THE
 UTILITY ROOM.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2015-06-12 Cont ID  
Sent By sgraham Date 2015-06-12 Time 10:11 Rev Time 0.00
Received By sgraham Date 2015-06-12 Time 10:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-05-08 Cont ID  
Sent By sgraham Date 2015-05-08 Time 14:58 Rev Time 0.00
Received By sgraham Date 2015-05-08 Time 14:58 Sent To  
Notes
2015-05-08 15:06:503RD CHECKLIST 5/8/15 ZONING FAILED
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-03-20 Cont ID  
Sent By sgraham Date 2015-03-20 Time 12:54 Rev Time 0.00
Received By sgraham Date 2015-03-20 Time 12:54 Sent To  
Notes
2015-03-20 12:55:083/20/15 ZONING FAILED
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By sgraham Date 2015-02-04 Time 11:29 Rev Time 0.00
Received By sgraham Date 2015-02-04 Time 11:29 Sent To  
Notes
2015-02-04 11:41:302/4/15 ZONING FAILED.
  
 1. PROVIDE TWO UP TO DATE SURVERYS OF THE PROPERTY.