| 2015-01-30 14:50:25 | WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 1) INDICATE ON THE PLAN THE TYPE OF PIPE MATERIAL TO BE |
| | INSTALLED. |
| | 2) INDICATE ON THE PLAN THE SIZE OF THE PIPE TO BE |
| | INSTALLED. |
| | 3) THE PLANS STATE THE DISTANCE FROM POINT A TO B IS 40 |
| | FT. YET THE PIPE SECTIONS ADD UP TO 44 FT.WHICH MEANS |
| | THE 50 FT.ROW IS TO BE USED IN THE SIZING TABLE. SHOW |
| | THE CORRECT DEVELOPED LENGTH ON THE PLAN. |
| | 4) CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN TWO |
| | SETS. |
| | 5) PLANS IN PENCIL ARE NOT ACCEPTABLE. MAKE COPIES OF |
| | THE PLANS ONCE ALL CORRECTIONS ARE MADE. |
| | 6) THE PLANS SHOW THAT THIS IS A 1/2 PSI SYSTEM BUT THE |
| | SIZING TABLE REFERENCED ON THE PLAN IS FOR A 2 PSI. |
| | SYSTEM. CLARIFY. |
| | 7) INDICATE ON THE PLAN IF THE 3" VENT IS NEW OR |
| | EXISTING. IF IT IS NEW, COMPLY WITH 2010 FBCR SEC. G |
| | 2426 & G 2427 OF 2010 FBCR. IF NEW, SHOW THE VENT |
| | HEIGHT ABOVE THE ROOF, TYPE OF VENT, ETC. |
| | 8) INDICATE THE SIZE OF THE APPLIANCE VENT ON THE PLAN. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | GAS APPLIANCE. THE APPLIANCE SHALL BE LISTED AND |
| | LABELED PER THE FBCR SEC.G2404.3. |
| | 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER SEC. |
| | G2407 OF THE 2010 FBCR. |
| | 11) THE APPLIANCE SHALL BE PROTECTED FROM PHYSICAL |
| | DAMAGE SINCE IT IS IN A GARAGE. |
| | 12) THE REGULATOR SHALL BE VENTED TO THE EXTERIOR PER |
| | FBCR SEC.G2421.3. |
| | 13) INDICATE ON THE PLAN THE TYPE OF APPLIANCE.THE |
| | APPLICATION NOTES" REPLACE OWNER'S WATER." I ASSUME |
| | THIS MEANS A WATER HEATER.INDICATE SUCH ON THE PERMIT |
| | APPLICATION. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |