Plan Review Details - Permit 15011018
Plan Review Stops For Permit 15011018
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-26 Cont ID  
Sent By jwitmer Date 2015-04-26 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2015-04-26 Time 12:01 Sent To  
Notes
2015-04-26 13:13:20BUILDING PLAN REVIEW
 PERMIT: 15011018
 ADD: 2020 PALM BEACH LAKES
 CONT: TBD
 TEL: (770)799-2273
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN. APRIL 26/ 2015
 ACTION: BUILDING PROVISO
  
 1) SUBMITTED GAF ROOFING REPORT FL 16730-R4 GAF
 EVERGUARD EXTREME TPO SINGLE PLY ROOFING SYSTEM WAS
 SUBMITTED WITH THE 68-PAGE APPENDIX. THE 68 PAGE
 APPENDIX LIST ALL SUB-SYSTEMS, ATTACHMENTS AS WELL AS
 MAXIMUM DESIGN PRESSURES AND LIMITATIONS SEE APPENDIX
 SHEET #2. THE APPENDIX 68 PAGES OF SUB-SYSTEMS WERE
 REVIEWED, NO SUB-SYSTEM WAS IDENTIFIED.
  
 THE ROOFING CONTRACTOR UNDER THE SUB-PERMIT WILL BE
 REQUIRED TO SUBMIT THE PRODUCT APPROVAL APPROVED BY THE
 DESIGNER OF RECORD WITH SHOP DRAWING STAMP OF APPROVAL
 AND THE SUB-SYSTEM IDENTIFIED WITH ASSOCIATED
 PRESSURES, DEPENDING ON THE TYPE OF FASTENING SYSTEM
 ELECTED, MAY OR MAY NO REQUIRE ENHANCED FASTENING SEE
 APPENDIX SHEET # 2 FOR NOTES AND LIMITATIONS OF THE
 PRODUCT.
  
 PLAN REVIEW FEES WILL BE ASSOCIATED THE SUB-ROOFING
 PERMIT FOR REVIEW OF SUB-SYSTEM IDENTIFICATION.
  
 2) 107. 3.4.2 DEFERRED SUBMITTALS :
 1) PREMADE RAIN SCREEN SYSTEMS
 2) FUTURE CANOPY
 THESE DEFERRED SUBMITTALS WILL NEED TO MEET THE WIND
 DESIGN REQUIREMENTS AND BE REVIEWED BY THE DESIGNER OF
 RECORD BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
 .
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-08 Cont ID  
Sent By jwitmer Date 2015-04-08 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2015-04-08 Time 07:46 Sent To  
Notes
2015-04-08 10:58:34BUILDING PLAN REVIEW
 PERMIT: 15011018
 ADD: 2020 PALM BEACH LAKES
 CONT: TBD
 TEL: (770)799-2273
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 08/ 2015
 ACTION: DENIED
  
 1) THE COVER SHEET DOES LIST THE DOOR AND ROOF PRODUCT
 APPROVALS. THE DOOR APPROVAL FL 15493.1 SUBMITTED HAS
 NO COVER SHEET & THE WRONG TECHNICAL SHEETS ATTACHED.
  
 2) THE FL 16730-R4 GAF SINGLE PLY ROOFING SYSTEMS
 SUBMITTED SHEETS 1-4 AND NOT THE 68-PAGE APPENDIX. THE
 68 PAGE APPENDIX LIST ALL SUB-SYSTEMS, ATTACHMENTS AS
 WELL AS MAXIMUM DESIGN PRESSURES AND LIMITATIONS.
  
 THESE DOCUMENTS CAN BE DEFERRED SUBMITTALS UPON WRITTEN
 REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND
 FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE
 BUILDING. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By tklarge Date 2015-02-05 Time 09:32 Rev Time  
Received By jwitmer Date 2015-02-05 Time 06:32 Sent To  
Notes
2015-02-05 08:41:38BUILDING PLAN REVIEW
 PERMIT: 15011018
 ADD: 2020 PALM BEACH LAKES
 CONT: TBD
 TEL: (770)799-2273
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 05/ 2015
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 SHEET A110 SHOWS A FLOOR PLAN WITH FURNATURE LAYOUT, NO
 LIFE SAFETY PLAN WAS SUBMITTED SHOWING EXITS AND
 OCCUPANT LOADS THAT WILL BE TRAVELING THROUGH THE EXIT
 DOORS.
  
 2) S101 THE WIND DESIN CRITERIA SHOWS THIS LOCATION AS
 A "B" EXPOSURE. PLEASE REVIEW THE 2010 FBC-B 1609.4.2
 SURFACE ROUGHNESS C.
 HIS SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND
 DIRECTION. NOTE PALM BEACH LAKES LIES FROM NORTHEAST TO
 SOUTHWEST, THE AREAS TO THE NORTH AND WEST MEET THE
 CURFACE ROUGHNESS FOR EXPOSURE C.
  
 3) S101 WITH THE EXPOSURE C THE PRESSURES WILL BE
 HIGHER WITH A HEIGHT ADJUSTMENT AND EXPOSURE OF C, OF
 1.29. FBC-B TABLE 1609.7(2).
  
 4) SHEET D1 INDICATES THE REAR EXTERIOR KITCHEN DOOR TO
 BE REPLACED, SHEET A100 INDICATES DOOR TO BE IDENTIFIED
 AS # 105.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 ( D) ROOFING PRODUCTS AND ASSEMBLIES NEW ROOF OVER
 CANOPY.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) SHEET G002 THE ACCESSIBILITY SHEET SHOWS THE GRAB
 RAIL HEIGHTS TAKEN AT THE CENTERLINE OF THE RAIL. 2010
 FL ACCESS. CODE 609.4, TOP OF GRIPPING SURFACE,
  
 7) SHEET D100 INDICATES IN THE RESTROOM WALLS REPLACE
 OR REPAIR SUBSTRATE MATERIALS. SHEET A150 SHOWS TILE
 WALL SURFACES NO INFORMATION AS TO THE REPLACED
 SUBSTRATE. SHOW COMPLIANCE WITH:
 FBC-B 1210.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2509.1 WET AREAS.
 SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO
 SECTIONS 1210.2 AND 1210.3.
  
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 8) SHEET A200 THE FRONT ELEVATION SHOWS A RAIN SCREEN
 BY OTHERS, THIS SYSTEM WILL NEED TO SHOW COMPLIANCE
 WITH COMPONENTS AND CLADDING FOR 170 MPH VULT, HOW THIS
 SYSTEM WILL BE FASTENED TO THE SUB-SHEATHING AND
 REVIEWED BY THE DESIGNER OF RECORD.FL 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 NOTE: SHEET A300 DETAIL 35 INDICATES THE BLOCKING
 REQUIRED FOR THE RAIN SCREEN SYSTEM TO BE COORDINATED
 WITH G. C. PLEASE ALSO HAVE THE STRUCTURAL ENGINEEER
 VERIFY THE BLOCKING SPECIES OF WOOD, AND TYPE OF
 ANCHORS TO LOCK IN THE BLOCKING AS WELL AS THE TYPE OF
 WALL BRACKETS LOCKING THE RAIN SCREEN SYSTEM TO THE
 STRUCTURE.
  
 9) SHEET A200 & A230 BOTH SHOW A METAL HORIZONTAL
 EYEBROW TYPE CANOPY, THE DESIGNER OF RECORD ELECTS THIS
 SUBMITTAL TO BE A DEFERRED SUBMITTAL.
 THIS SYSTEM WILL NEED TO SHOW COMPLIANCE WITH
 COMPONENTS AND CLADDING FOR 170 MPH VULT, HOW THIS
 SYSTEM WILL BE FASTENED TO THE SUB-SHEATHING AND
 REVIEWED BY THE DESIGNER OF RECORD.FL 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 10) S101 DETAIL # 2 INDICATES THE SIZE OF THE RAFTERS,
 AND RIDGE BUT THE PLANS FAIL TO PROVIDE THE SPECIES AND
 GRADE FBC-B TABLE 2308.10.2 & TABLE 2308.10.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By rlecky Date 2015-02-12 Time 10:32 Rev Time 0.00
Received By rlecky Date 2015-02-12 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-16 Cont ID  
Sent By scaldero Date 2015-03-16 Time 16:05 Rev Time 0.00
Received By scaldero Date 2015-03-16 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By scaldero Date 2015-02-10 Time 16:20 Rev Time 0.00
Received By scaldero Date 2015-02-10 Time 15:39 Sent To  
Notes
2015-02-10 16:20:37PERMIT # 15011018
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED:
 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) IS THERE AN ACTIVE FIRE ALARM SYSTEM AT THIS
 LOCATION? IF SO, PLEASE PROVIDE DETAILS REGARDING
 LOCATION OF FACP.
  
 5) FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF
 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA
 BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE
 MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-26 Cont ID  
Sent By jwitmer Date 2015-04-26 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2015-04-24 Time   Sent To  
Notes
2015-04-25 09:38:44SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-22 Cont ID  
Sent By skennedy Date 2015-04-22 Time 08:47 Rev Time 0.00
Received By skennedy Date 2015-03-13 Time 11:55 Sent To  
Notes
2015-03-13 11:56:21C33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-24 Cont ID  
Sent By hmoser Date 2015-02-24 Time 15:40 Rev Time 0.00
Received By hmoser Date 2015-01-28 Time 14:06 Sent To  
Notes
2015-01-29 14:07:43C24
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-02-05 Cont ID  
Sent By jwitmer Date 2015-02-05 Time 09:32 Rev Time 0.00
Received By jwitmer Date 2015-02-05 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-02-24 Cont ID  
Sent By hmoser Date 2015-02-24 Time 15:40 Rev Time 0.00
Received By hmoser Date 2015-02-24 Time 15:23 Sent To  
Notes
2015-02-24 15:40:11NO MECHANICAL SUBMITTED. HAVE AIR CONDITIONING
 CONTRACTOR PROVIDE
 SEPARATE APPLICATION AND PLANS FOR PERMIT BE FOR WORK
 BEGINS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-07 Cont ID  
Sent By tklarge Date 2015-04-07 Time 11:32 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 12:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-31 Cont ID  
Sent By tklarge Date 2015-01-31 Time 06:12 Rev Time 0.00
Received By tklarge Date 2015-01-30 Time 13:22 Sent To  
Notes
2015-01-31 06:14:20!) PROVIDE A WATER AND SANITARY RISER ON THE PLANS PER
 WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 2) PROVIDE ROOF DRAINAGE DETAILS / CALCULATIONS,
 SCUPPER DETAILS, ETC. COMPLY WITH 2010 FBC SEC.1503.4
 AND CHAPTER 11 OF THE 2010 FL. PLBG. CODE AND WPB
 AMEND. TO 2010 FBC SEC. 107.2.1, FBC 1503.4 THRU
 1503.4.2.1.
 3) ONE HALF OF THE AREA OF THE MODIFIED PARAPET WALL
 SHALL BE ADDED TO THE ROOF DRAINAGE CALCULATIONS PER
 2010 FPC SEC.1106.4.
 4) SHT. A 210 REFERS TO A NEW SCUPPER. PROVIDE A
 SCUPPER DETAIL SHOWING L X W . SCUPPER SHALL COMPLY W/
 2010 FPC TABLE 1106.7.
 5) SECONDARY DRAINAGE IS REQUIRED FOR THE ROOF SYSTEM
 PER SEC.1107.1 OF THE 2010 FPC AND 1503.4.1 OF THE 2010
 FBC. SUPPLY DETAILS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-22 Cont ID  
Sent By sgraham Date 2015-04-22 Time 08:19 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By sgraham Date 2015-02-04 Time 11:38 Rev Time 0.00
Received By sgraham Date 2015-02-04 Time 11:38 Sent To  
Notes
2015-02-02 15:32:202/2/15