Plan Review Details - Permit 15010983
Plan Review Stops For Permit 15010983
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-26 Cont ID  
Sent By jwitmer Date 2015-03-26 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2015-03-26 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By JWitmer Date 2015-02-27 Time 06:15 Rev Time 0.00
Received By jwitmer Date 2015-02-27 Time   Sent To  
Notes
2015-02-27 06:09:55BUILDING PLAN REVIEW
 PERMIT: 15010983
 ADD: 401 S. DIXIE HWY. SUITE # 3
 CONT: T. B. D.
 TEL: (561)389-3887
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 27/2015
 ACTION: DENIED
  
 NOTE!!!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1) 2ND REQUEST. BOTH THE COVER SHEET INDICATE THIS TO
 BE A BUSINESS OCCUPANCY, THE PLANS INDICATE A COFFEE
 SHOP. THIS SPACE APPEARS TO BE AN A-2 OCCUPANCY
 INTENDED FOR FOOD AND/OR DRINK CONSUMPTION, NOTE THE
 OCCUPANT LOAD WOULD NEED TO BE 50 OR MORE OCCUPANTS.
 FBC-B 303.1 ALSO SEE 309.1 MERCANTILE RESTAURANTS AND
 DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF LESS
 THAN 50 PERSONS.
  
 2)COMPLIED. THE LIFE SAFETY SHEET INDICATES THE SQUARE
 FOOTAGE FOR THE 1ST FLOOR, BUT NOT FOR THIS TENANT
 SPACE, PLEASE PROVIDE THE SQUARE FOOTAGE AND OCCUPANT
 LOAD PER FBC-B TABLE 1004.1.1 FOR THIS TENANT SPACE.
  
 3) 2ND REQUEST. RESPONCE THE DESIGNER OF RECORD QOUTED
 THE CODE SECTION FOR COMPLIANCE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART.
  
 THE LIFE SAFETY PLAN DOES NOT SHOW TABLES AND CHAIRS IN
 THE DINING AREA NOR COMPLIANCE WITH AISLE ACCESS WAY
 FOR TABLES & CHAIRS, 2010 FBC-B 1017.4 (1)-(3) NOR
 1028.9.1 AND 1028.9.1.1.
  
 4) PROVISO: WILL BE INSPECTED IN THE FIELD FOR CODE
 COMPLIANCE FOR THE FLORIDA ACCESSIBILITY CODE. ISHEET
 A-1.0 SHOWS 2 PIECES OF MILLWORK SUPPLIED BY OWNER, WE
 DO NOT KNOW THE USAGE AND IF THESE UNITS COMPLY WITH
 THE 2010 FBC- ACCESSIBILITY CODE 904.5.1 SELF-SERVICE
 SHELVES AND DISPENSING DEVICES.
  
 5) 2ND REQUEST. RESPONCE THE DESIGNER OF RECORD QOUTED
 THE CODE SECTION FOR COMPLIANCE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART.
  
 LIFE SAFETY NOR SHEET A-1.0 SHOW COMPLIANCE WITH 2010
 FL ACCESSIBILTY CODE 02.1 GENERAL. DINING SURFACES AND
 WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-03 Cont ID  
Sent By jwitmer Date 2015-02-03 Time 15:47 Rev Time 0.00
Received By jwitmer Date 2015-02-03 Time 14:06 Sent To  
Notes
2015-02-03 15:01:15BUILDING PLAN REVIEW
 PERMIT: 15010983
 ADD: 401 S. DIXIE HWY. SUITE # 3
 CONT: T. B. D.
 TEL: (561)389-3887
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 03/2015
 ACTION: DENIED
  
 1) BOTH THE COVER SHEET AND LIFE SAFETY SHEETS INDICATE
 THIS TO BE A BUSINESS OCCUPANCY, THE PLANS INDICATE A
 COFFEE SHOP. THIS SPACE APPEARS TO BE AN A-2 OCCUPANCY
 INTENDED FOR FOOD AND/OR DRINK CONSUMPTION, NOTE THE
 OCCUPANT LOAD WOULD NEED TO BE 50 OR MORE OCCUPANTS.
 FBC-B 303.1 ALSO SEE 309.1 MERCANTILE RESTAURANTS AND
 DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF LESS
 THAN 50 PERSONS.
  
 2) THE LIFE SAFETY SHEET INDICATES THE SQUARE FOOTAGE
 FOR THE 1ST FLOOR, BUT NOT FOR THIS TENANT SPACE,
 PLEASE PROVIDE THE SQUARE FOOTAGE AND OCCUPANT LOAD PER
 FBC-B TABLE 1004.1.1 FOR THIS TENANT SPACE.
  
 3) THE LIFE SAFETY PLAN DOES NOT SHOW TABLES AND CHAIRS
 IN THE DINING AREA NOR COMPLIANCE WITH AISLE ACCESS WAY
 FOR TABLES & CHAIRS, 2010 FBC-B 1017.4 (1)-(3) NOR
 1028.9.1 AND 1028.9.1.1.
  
 4) SHEET A-1.0 SHOWS 2 PIECES OF MILLWORK SUPPLIED BY
 OWNER, WE DO NOT KNOW THE USAGE AND IF THESE UNITS
 COMPLY WITH THE 2010 FBC- ACCESSIBILITY CODE 904.5.1
 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
  
 5) LIFE SAFETY NOR SHEET A-1.0 SHOW COMPLIANCE WITH
 2010 FL ACCESSIBILTY CODE 02.1 GENERAL. DINING SURFACES
 AND WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-09 Cont ID  
Sent By D Hayes Date 2015-03-09 Time 15:45 Rev Time 0.00
Received By dhayes Date 2015-03-09 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-12 Cont ID  
Sent By dhayes Date 2015-02-12 Time 10:59 Rev Time 0.00
Received By dhayes Date 2015-02-12 Time 09:41 Sent To  
Notes
2015-02-12 10:59:092/13/2015
 PROJECT:401 S. DIXIE HWY STE 3
 PERMIT#: 15010983
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE CORRECTIONS TO THE ELECTRICAL PLANS TO COMPLY
 WITH REVIEW COMMENTS BELOW:
  
 1) CLARIFY RISER DIAGRAM WHERE PANEL AC1 IS ALSO
 INDICATED AS "NEW PANEL "D" DISC." THE NOTES UNDER THE
 RISER DIAGRAM STATES "NO WORK PROPOSED ON RISER; SHOWN
 FOR INFORMATIONAL PURPOSES ONLY." IF THERE IS A NEW
 PANEL "D" INDICATE FEEDER AND PANEL AS NEW WORK,
 PROVIDE LOCATION OF NEW PANEL, A COMPLETE PANEL
 SCHEDULE AND LOAD CALCULATION FOR MDP.
  
 2) NEC 110.16 ARC FLASH PROTECTION.
 VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR THE
 PANEL BOARDS AND MAIN DISCONNECTING MEANS.
  
 3) NEC 110.9
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED.
  
 4) WPB AMENDMENTS TO FBC 107.2.1
 PROVIDE A SYMBOL ON THE SYMBOLS LEGEND ON SHEET E-1 FOR
 A GFI OUTLET OR ADD A GFI DESIGNATION TO THE OUTLETS
 DESIGNATED AS A SQUARE SYMBOL WITH TWO HORIZONTAL LINES
 IN THE KITCHEN COUNTER TOPS AND SINKS WHERE REQUIRED.
  
 5) FBC-E 505.2
 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
  
 6) FBC ENERGY CONSERVATION 505.3
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS.
  
 7) PROVIDE A LIGHTING FIXTURE DETAIL WITH MANUFACTURER
 SUBMITTALS ON OWNER PROVIDED LED ROPE LIGHT.
  
 8) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATORS. HOOD EXHAUST, FIRE ALARM,
 ACCESS CONTROL SYSTEM, SECURITY, CCTV, AUDIO/VIDEO,
 NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-25 Cont ID  
Sent By pleduc Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-24 Time 16:19 Sent To  
Notes
2015-03-20 17:56:15NEW DRAWING SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-30 Cont ID  
Sent By pleduc Date 2015-01-30 Time   Rev Time 0.00
Received By pleduc Date 2015-01-30 Time 11:01 Sent To  
Notes
2015-01-30 12:04:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS OF THE BUILDING, THE FIRE ALARM
 AND/OR FIRE SPRINKLER, SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 COOKING OR WARMING IN THE KITCHEN SHALL NOT PRODICE ANY
 GREASE LADEN VAPORS OR A NFPA 96 COMPLIANT HOOD,
 EXHAUST AND FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMIT..
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-30 Cont ID  
Sent By tklarge Date 2015-03-30 Time 12:07 Rev Time 0.00
Received By tklarge Date 2015-03-20 Time 17:51 Sent To  
Notes
2015-03-20 17:54:13RE-SUBMITTAL (SUBMITTED IN THE MIDDLE OF SECOND REVIEW)
 SENT TO B6 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-30 Cont ID  
Sent By tklarge Date 2015-03-30 Time 12:06 Rev Time 0.00
Received By tklarge Date 2015-02-24 Time   Sent To  
Notes
2015-02-24 17:40:38B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-14 Cont ID  
Sent By hmoser Date 2015-02-14 Time 09:00 Rev Time 0.00
Received By hmoser Date 2015-01-28 Time 09:10 Sent To  
Notes
2015-01-29 09:20:04B11
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2015-03-26 Cont ID  
Sent By   Date 2015-03-26 Time   Rev Time 0.00
Received By   Date 2015-03-26 Time   Sent To  
Notes
2015-03-26 07:29:093/16/15 PLANS STAMPED FROM P. B. C. IMPACT FEE OFFICE
 NO FEES DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-02-27 Cont ID  
Sent By jwitmer Date 2015-02-27 Time 06:11 Rev Time 0.00
Received By jwitmer Date 2015-02-27 Time 06:10 Sent To  
Notes
2015-02-27 06:11:47BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-02-27 Cont ID  
Sent By jwitmer Date 2015-02-27 Time 06:10 Rev Time 0.00
Received By jwitmer Date 2015-02-27 Time 06:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-03-26 Cont ID  
Sent By H moser Date 2015-03-26 Time 11:00 Rev Time 0.00
Received By hmoser Date 2015-03-26 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-02-14 Cont ID  
Sent By hmoser Date 2015-02-14 Time 08:59 Rev Time 0.00
Received By hmoser Date 2015-02-14 Time 08:30 Sent To  
Notes
2015-02-14 08:59:39PLAN DENIED
 1) SHOW ON THE PLAN WHERE THE OUT DOOR AIR TERMINATES.
 PER SECTION 401.4 INTAKE AIR OPENING LOCATION.
 2010 FBC (M)
 2) DUCT OFF OAF-1 SHOWS 12" RETURN AIR PROVIDE MORE
 INFORMATION. PER SECTION 107 FBC
 3) CLASS TWO HOOD REQUIRES SEPARATE APPLICATION, PLAN
 AND PERMIT.
  
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-03-30 Cont ID  
Sent By tklarge Date 2015-03-30 Time 12:00 Rev Time 0.00
Received By tklarge Date 2015-03-30 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-02-28 Cont ID  
Sent By T Large Date 2015-02-28 Time 10:51 Rev Time 0.00
Received By tklarge Date 2015-02-28 Time 10:05 Sent To  
Notes
2015-02-28 10:51:281) SHT.CS-1 & LS-1 BOTH INDICATE THIS OCCUPANCY AS A
 BUSINESS OCCUPANCY BUT THE PLAN CLEARLY STATES THIS AS
 A RETAIL SPACE AND HAS A DINING AREA. DEPENDING ON THE
 OCCUPANT LOAD, IT COULD BE ASSEMBLY, OR MERCANTILE PER
 SEC.303. CLARIFY.2ND REQUEST.
 2) SUBMIT THE SQUARE FOOTAGE OF THIS SPACE.WPB
 AMENDMENTS TO 2010 FBC SEC.107.2.1. 2ND REQUEST.
 3) SUBMIT THE OCCUPANT LOAD OF THIS SPACE..WPB
 AMENDMENTS TO 2010 FBC SEC.107.2.1.2ND REQUEST.
 4) INDICATE ON THE PLANS THE TYPE OF FOODS THAT WILL BE
 PREPARED AND SOLD. WPB AMENDMENTS TO 2010 FBC
 SEC.107.2.1.2ND REQUEST.
 5) SUBMIT THE SIZING CALCULATIONS THAT WERE USED TO
 SIZE THE SCHIER GREASE INTERCEPTOR.2010 FPC SEC.1003.2.
 6) THE GREASE INTERCEPTOR SHALL BE VENTED IN ACCORDANCE
 THE 2010 FPC SEC.1003.3.4.2.
 7) THE REVISED SHEETS SHALL BE INSERTED INTO THE MASTER
 SET BY THE APPLICANT.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By tklarge Date 2015-02-04 Time 04:37 Rev Time 0.00
Received By tklarge Date 2015-01-31 Time 07:27 Sent To  
Notes
2015-01-31 08:27:201) SHT.CS-1 & LS-1 BOTH INDICATE THIS OCCUPANCY AS A
 BUSINESS OCCUPANCY BUT THE PLAN CLEARLY STATES THIS AS
 A RETAIL SPACE AND HAS A DINING AREA. DEPENDING ON THE
 OCCUPANT LOAD, IT COULD BE ASSEMBLY, OR MERCANTILE PER
 SEC.303. CLARIFY.
 2) SUBMIT THE SQUARE FOOTAGE OF THIS SPACE.WPB
 AMENDMENTS TO 2010 FBC SEC.107.2.1.
 3) SUBMIT THE OCCUPANT LOAD OF THIS SPACE..WPB
 AMENDMENTS TO 2010 FBC SEC.107.2.1.
 4) INDICATE ON THE PLANS THE TYPE OF FOODS THAT WILL BE
 PREPARED AND SOLD. WPB AMENDMENTS TO 2010 FBC
 SEC.107.2.1.
 5) THE PLUMBING PLANS INDICATE A SCHIER GREASE
 INTERCEPTOR. THE GREASE INTERCEPTOR SHALL BE
 DESIGNED/SIZED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS. SUBMIT SIZING CALCULATIONS THAT HAVE BEEN
 DONE BY SCHIER TO ENSURE THE CORRECT SIZE IS BEING
 INSTALLED.2010 FPC SEC.1003.2.
 6) SHT. P-2 SHOWS A DRY VENT ON THE SANITARY RISER
 DOWNSTREAM OF THE FLOOR DRAIN NEAR THE INLET OF THE
 GREASE INTERCEPTOR. COMPLY W/2010 FPC SEC.905.3.
 7) SUBMIT MANUF. SPECIFICATIONS FOR THE SCHIER GREASE
 INTERCEPTOR.WPB AMENDMENTS TO 2010 FBC SEC.107.2.1.
 8) SHT. P-2 - SIZE ALL VENTS ON THE SANITARY RISER.WPB
 AMENDMENTS TO 2010 FBC SEC.107.2.1.
 9) SHT. P-2 SHOWS AN ITEM MARKED AS "D/W." IS THIS A
 DISHWASHER? IF SO, IT SHALL DRAIN THROUGH THE
 INTERCEPTOR. 2010 FPC SEC.1003.3.1.SHOW THE DRAIN ON
 THE SANITARY RISER.
 10) FLOOR SINKS NOT RECEIVING INDIRECT WASTE DISCHARGE
 SHALL HAVE TRAP PRIMERS PER 2010 FPC SEC.1002.4.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-02 Cont ID  
Sent By ajones Date 2015-02-02 Time 16:16 Rev Time 0.00
Received By ajones Date 2015-02-02 Time 16:16 Sent To  
Notes
***NONE***