Plan Review Details - Permit 15010920
Plan Review Stops For Permit 15010920
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-09 Cont ID  
Sent By jgomez Date 2015-04-09 Time 11:32 Rev Time 0.00
Received By jgomez Date 2015-04-09 Time 11:32 Sent To  
Notes
2015-04-09 11:34:04REVISION APPROVED WITH PROVISO:
  
 1- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 IMPACT PROTECTION SYSTEM NOA 12-1004.02 SUBMITTED. NEED
 INSTALLATION SCHEDULE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301. 2.1.4 OF 2010 FBC.
 NOTE: YOU MAY USE THE CITY INSTALLATION SCHEDULE SAMPLE
 OR PROVIDE COMPLETE INFORMATION IN A DIFFERENT FORMAT
 AS LONG AS ALL THE REQUIRED INFORMATION IS PROVIDED.
  
 NOTE: FOR YOUR INFORMATION LANDINGS WILL BE REQUIRED
 FOR THE NEW EXTERIOR FRENCH DOORS. ACCORDING TO STAIR
 DETAIL ON SHEET 5 OF ENGINEER'S DRAWINGS SUBMITTED,
 THERE ARE THREE STEPS NOT TWO. THIS WILL BE VERIFIED IN
 THE FIELD.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By jgomez Date 2015-02-26 Time 07:22 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 07:21 Sent To  
Notes
2015-02-26 07:21:56RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE ENTRY DOOR AS SHOWN ON PLANS. SEE
 HISTORIC COMMENTS.
  
 2- ENGINEER TO REVISE FRONT ELEVATION ON SHEET #2. THE
 ARCHED ENTRY DOOR IS NOT EXISTING. ALSO, SEE HISTORIC
 COMMENTS FOR WINDOW FRAMES COLOR. NOTE: IF PROPOSED
 DOOR DOESN'T HAVE IMPACT GLASS AND SHUTTERS ARE
 PROPOSED, THEN TAKE INTO CONSIDERATION THAT EGRESS
 CAN'T BE BLOCKED. SEC. R311 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-28 Cont ID  
Sent By dhayes Date 2015-03-28 Time 12:57 Rev Time 0.00
Received By dhayes Date 2015-03-28 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-28 Cont ID  
Sent By dhayes Date 2015-01-28 Time 11:39 Rev Time 0.00
Received By dhayes Date 2015-01-28 Time 10:51 Sent To  
Notes
2015-01-28 11:39:261/28/2015
 PROJECT: 535 36TH ST
 PERMIT#: 14070394, REVISION TRACKING # 15010920
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 MAKE CORRECTIONS TO THE ELECTRICAL PLAN REVIEW
 DEFICIENCIES LISTED BELOW:
  
 1) NEC 210.63 SEE 210.8(A)(3), ONE 125VOLT,
 SINGLE-PHASE, 15 OR 20AMP GFI RECEPTACLE OUTLET SHALL
 BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT.
  
 2) NEC 440.14. DISCONNECTING MEANS SHALL BE LOCATED
 WITHIN SIGHT FROM AND READILY ACCESSIBLE FROM THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE
 DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED
 ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING
 EQUIPMENT.
  
 3) FBC-RESIDENTIAL 314 AND 315.WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
 4) NEC 210.52(D) AT LEAST ONE RECEPTACLE OUTLET SHALL
 BE INSTALLED IN BATHROOMS WITHIN (3 FT) OF THE OUTSIDE
 EDGE OF EACH BASIN. THE RECEPTACLE OUTLET SHALL BE
 LOCATED ON A WALL OR PARTITION THAT IS ADJACENT TO THE
 BASIN OR BASIN COUNTERTOP, OR INSTALLED ON THE SIDE OR
 FACE OF THE BASIN CABINET NOT MORE THAN (12 IN.) BELOW
 THE COUNTERTOP. SEE ALSO: 210.52(C)(3)
  
 5) NEC 250.94.AN INTERSYSTEM BONDING TERMINATION FOR
 CONNECTING INTERSYSTEM BONDING AND GROUNDING CONDUCTORS
 REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL
 TO ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-03-31 Cont ID  
Sent By fmittner Date 2015-03-31 Time 16:04 Rev Time 0.00
Received By fmittner Date 2015-03-31 Time 16:04 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By fmittner Date 2015-02-04 Time 11:32 Rev Time 0.00
Received By fmittner Date 2015-02-04 Time 11:32 Sent To  
Notes
2015-02-04 11:33:36PLANS DO NOT CLARIFY/DEPICT COMMENTS FROM MASTER PERMIT
 14070394. SEE BELOW:
  
 SPOKE TO APPLICANT AND CLARRIFIED THAT FRONT DOOR WILL
 HAVE ARCHED TOP. PRODUCT SUBMITTALS NOT SUBMITTED FOR
 THIS YET. WINDOWS WILL BE WHITE FRAMES, CLEAR GLASS,
 EXACT OPENINGS AS EXISTING (NO SIZE CHANGES EXCEPT FOR
 FRENCH DOOR LOCATION). QUESTIONS CONTACT FRIEDERIKE
 MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-09 Cont ID  
Sent By jgomez Date 2015-04-09 Time 11:32 Rev Time 0.00
Received By jgomez Date 2015-03-17 Time 10:49 Sent To  
Notes
2015-03-23 14:21:313/23/15 SACHA SUBMITTED ENTRY DOOR PRODUCT APPROVAL.
 JG.
2015-03-18 10:41:27R10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-26 Cont ID  
Sent By jgomez Date 2015-02-26 Time 08:29 Rev Time 0.00
Received By jgomez Date 2015-01-28 Time 11:42 Sent To  
Notes
2015-01-28 11:43:06R09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-02-26 Cont ID  
Sent By hmoser Date 2015-02-26 Time 08:29 Rev Time 0.00
Received By jgomez Date 2015-02-26 Time 08:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-28 Cont ID  
Sent By tklarge Date 2015-03-28 Time 13:28 Rev Time 0.00
Received By tklarge Date 2015-03-28 Time 13:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-31 Cont ID  
Sent By tklarge Date 2015-01-31 Time 07:10 Rev Time 0.00
Received By tklarge Date 2015-01-31 Time 07:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By fmitner Date 2015-02-04 Time 11:37 Rev Time 0.00
Received By fmittner Date 2015-02-04 Time 11:37 Sent To  
Notes
***NONE***