| 2015-02-06 07:56:11 | BUILDING PLAN REVIEW |
| | PERMIT: 15010908 |
| | ADD: 1097 THE POINT DR./ AKA/ |
| | 1097 PARADISE COVE |
| | CONT: HOME STRETCHERS INC. |
| | TEL: (561) 588-1888 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. FEB. 06/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE DESIGNER OF RECORD HAS NOT DECLARED TO WHICH |
| | METHOD THEY ARE GOING TO COMPLY TO THE 2010 FL EXISTING |
| | BLDG CODE, 101.5. THE PERMIT APPLICATION INDICATES |
| | REMOVAL OF DRYWALL, THE FLOOR PLAN SUBMITTED INDICATES |
| | THE REMOVAL AND REPLACE DRYWALL THROUGH OUT THE ENTIRE |
| | UNIT, DOES THIS INCLUDE THE CEILINGS? WPB ADMIN CODE |
| | 107.2.1.3 ADDITIONAL INFORMAION IS REQUIRED. IS THIS |
| | FROM A FIRE & SMOKE DAMAGE? |
| | |
| | 2) WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | |
| | 2.1) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | |
| | |
| | 2.2) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS/ TENANT SEPARATION WALLS/ |
| | PLANS INDICATE 2 HR FIRE RATING, PROVIDE UL OR GYPSUM |
| | ASSOC ASSEMBLY NUMBER SEE FBC-B |
| | 709.3. |
| | |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | |
| | PROTECTION OF OPENINGS OF HORIZONTAL ASSEMBLIES/ FLOOR |
| | CEILING ASSOCIATION |
| | |
| | FLOOR/ CEILING ASSEMBLY, CONCRETE/ METAL DECK OR A |
| | FOOR/ CEILING ASSEMBLY, WOOD TRUSSES PROVIDE UL, OR |
| | GYPSUM ASSEMBLY TO WHAT WILL BE |
| | INSTALLED AND HOUR OF FIRE RATING. 2010 FBC-B 712.3 |
| | FIRE-RESISTANCE RATING. THE FIRE-RESISTANCE RATING OF |
| | FLOOR AND ROOF ASSEMBLIES SHALL NOT BE |
| | LESS THAN THAT REQUIRED BY THE BUILDING TYPE OF |
| | CONSTRUCTION. HORIZONTAL ASSEMBLIES SEPARATING DWELLING |
| | UNITS IN THE SAME BUILDING AND HORIZONTAL |
| | ASSEMBLIES SEPARATING SLEEPING UNITS IN THE SAME |
| | BUILDING SHALL BE A MINIMUM OF 1-HOUR |
| | FIRE-RESISTANCE-RATED CONSTRUCTION. |
| | DOES THE DUCT WORK GO UP INTO THE FLOOR TRUSSES? IF SO |
| | A 1 HR. BOXED CHASE WILL BE REQUIRED OR A RADIENT |
| | DAMPER. 2010 FBC-B 713.4.1.3 DUCTS |
| | AND AIR TRANSFER OPENINGS. PENETRATIONS OF HORIZONTAL |
| | ASSEMBLIES BY DUCTS AND AIR TRANSFER OPENINGS SHALL |
| | COMPLY WITH SECTION 716. |
| | |
| | 2.3 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| | FIRE SPRINKLERS NFPA 13 OR NFPA 13R. |
| | |
| | 3) NOTE THE EXISTING DINING ROOM IS BEING TRANSFORMED |
| | INTO A SLEEPING ROOM, PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-B 1029.2 EMERGENCY ESCAPE & RESCUE WINDOWS 5.7 |
| | FOR 2ND OR 3RD FLOOR UNITS, 5 SQ FT FOR 1ST FLOOR UNITS |
| | (VENT SIZE). PROVIDE THE OVER ALL WINDOW SIZE AND THE |
| | TYPE OF WINDOW. |
| | |
| | 4) THE DEN BEING A NEW SLEEPING ROOM PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2010 FBC-B [F] 907.2.9 GROUP R-2. |
| | FIRE ALARM SYSTEMS AND SMOKE ALARMS SHALL BE INSTALLED |
| | IN GROUP R-2 OCCUPANCIES AS REQUIRED IN SECTIONS |
| | 907.2.9.1 AND 907.2.9.2. |
| | |
| | 5) THE DESIGNER OF RECORD IT APPEARS TO BE THE |
| | CONTRACTOR, WILL NEED TO PRINT THEIR NAME, SIGN THEIR |
| | NAME AND PRINT THEIR LICENSE NUMBER ON THE PLANS THEY |
| | ARE DESIGNING. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | |