Plan Review Details - Permit 15010897
Plan Review Stops For Permit 15010897
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-08-24 Cont ID  
Sent By jwitmer Date 2015-08-24 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2015-08-24 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-08-11 Cont ID  
Sent By jwitmer Date 2015-08-11 Time 09:39 Rev Time 0.00
Received By jwitmer Date 2015-08-11 Time 08:45 Sent To  
Notes
2015-08-11 09:29:38BUILDING PLAN REVIEW
 PERMIT: 15010897
 ADD: 4720 BROADWAY
 CONT: ROBLING ARCHITECTURE
 TEL: (561)649-6705
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 4TH REVIEW
 DATE: TUES. AUG. 11/ 2015
  
 ACTION: BUILDING PROVISO/ DEFERRED SUBMITTAL
  
 ARCHITECT DAMON ROBLING SENT E-MAIL 08/10/15 04:04 PM
 ASKING IF THE PRODUCT APPROVALS CAN BE A PROVISO/
 DEFERRED SUBMITTAL.
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 1) ROOFING REPORT: FL 13464-RO ROOFING GAF MODIFIED FL
 13464- R0 THE ROOFING SUB-SYSTEMS TO BE APPLIED HAS NOT
 BEEN IDENTIFIED NOR THE ASSOCIATED PRESSURES. SEE
 APPENDIX SHEET 2 OF 13 NOTE 8 REQUIRES ENHANCED
 FASTENING BY A QUALIFIED DESIGN PROFESSIONAL.
 THE DESIGNER OF RECORD ON SHEET A1.0 HAS LISTED TABLE #
 1 ON PLANS WHICH ALLOWS THE FOLLOWING PRODUCTS (TABLE
 1) MAKE UP THE SUBJECT SYSTEMS. NOTE TABLES 2A, 2B & 2C
 ARE STEEL DECKS WITH INSULATION NONE OF THE SUB-SYSTEMS
 HAVE BEEN IDENTIFIED FOR INSTALLATION.
  
 2) FROM 3RD REVIEW: SHEET A7.0 FOR EXTERIOR FINISHES
 INDICATES THE USE OF REYNOBOND ACM PANELS FOR THE
 EXTERIOR FINISH OF THE BUILDING. NO PRODUCT APPROVALS
 WERE SUBMITTED FOR THIS PRODUCT. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: ACM PANELS/ AND OR MCM PANELS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-10 Cont ID  
Sent By jwitmer Date 2015-08-10 Time 07:37 Rev Time 0.00
Received By jwitmer Date 2015-08-10 Time 06:59 Sent To  
Notes
2015-08-10 07:36:592010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RDD REVIEW
 DATE: MON. AUG. 10/ 2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) PRODUCT APPROVALS.
  
 2A) 3RD REQUEST. GAF MODIFIED FL 13464- R0 THE ROOFING
 SUB-SYSTEMS TO BE APPLIED HAS NOT BEEN IDENTIFIED NOR
 THE ASSOCIATED PRESSURES. SEE APPENDIX SHEET 2 OF 13
 NOTE 8 REQUIRES ENHANCED FASTENING BY A QUALIFIED
 DESIGN PROFESSIONAL.
 THE DESIGNER OF RECORD ON SHEET A1.0 HAS LISTED TABLE #
 1 ON PLANS WHICH ALLOWS THE FOLOWING PRODUCTS (TABLE 1)
 MAKE UP THE SUBJECT SYSTEMS. NOTE TABLES 2A, 2B & 2C
 ARE STEEL DECKS WITH INSULATION NONE OF THE SUB-SYSTEMS
 HAVE BEEN IDENTIFIED FOR INSTALATION. THE DESIGNER OF
 RECORD HAS NOT INDICATED TO BE PICKED BY ROOFING
 CONTRACTOR AND REVIEWED BY THE DESIGNER OF RECORD
 BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. HAS NOT
 INDICATED THIS TO BE A DEFERRED SUBMITTAL.
  
 3-5) COMPLIED.
  
 6A) NEW COMMENT. SHEET A7.0 FOR EXTERIOR FINISHES
 INDICATES THE USE OF REYNOBOND ACM PANELS FOR THE
 EXTERIOR FINISH OF THE BUILDING. NO PRODUCT APPROVALS
 WERE SUBMITTED FOR THIS PRODUCT. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: ACM PANELS/ AND OR MCM PANELS
  
 6B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-30 Cont ID  
Sent By jwitmer Date 2015-06-30 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2015-06-30 Time 11:56 Sent To  
Notes
2015-06-30 13:56:37BUILDING PLAN REVIEW
 PERMIT: 15010897
 ADD: 4720 BROADWAY
 CONT: ROBLING ARCHITECTURE
 TEL: (561)649-6705
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 30/ 2015
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) PRODUCT APPROVALS.
  
 2A) 2ND REQUEST. GAF MODIFIED FL 13464- R0 THE ROOFING
 SUB-SYSTEMS TO BE APPLIED HAS NOT BEEN IDENTIFIED NOR
 THE ASSOCIATED PRESSURES. SEE APPENDIX SHEET 2 OF 13
 NOTE 8 REQUIRES ENHANCED FASTENING BY A QUALIFIED
 DESIGN PROFESSIONAL.
  
 3) SEMI-COMPLIED. SHEET S-4 FOR ROOF ZONES 2 & 3 THE
 NEGATIVE PRESSURES ARE LOW FOR A 10 SQ. FT. AREA TAKEN
 @ ELE. 20 FEET ABOVE GRADE. ROOF ZONE 2 INDICATES A
 -48.47 SHOULD BE APPROX. -67.8 (VASD) AND ROOF ZONE 3
 THE PLANS SHOW A -57.65 AND SHOULD BE -102 (VASD) .
  
 4) COMPLIED.
  
 5) 2ND REQUEST. SHEET A7.0 INDICATES WALL DETAIL A-G.
 SHEET A8.0 SECTIONS 2,3 & 4 ARE THESE SECTIONS SHOW A
 FRAMED OUT WALL SECTIONS. THERE IS NO ATTACHMENT,
 FRAMING OR MATERIALS FOR THE SURFACE FINISH? NO DETAILS
 FOR THIS BUILT OUT WALL IN THE STRUCTURAL SHEETS
 EITHER. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-25 Cont ID  
Sent By jwitmer Date 2015-02-25 Time 07:43 Rev Time  
Received By jwitmer Date 2015-02-20 Time   Sent To  
Notes
2015-02-25 07:09:51BUILDING PLAN REVIEW
 PERMIT: 15010897
 ADD: 4720 BROADWAY
 CONT: ROBLING ARCHITECTURE
 TEL: (561)649-6705
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: WED. FEB. 20-25
 ACTION: DENIED
  
 1) SHEET T1.0 BUILDING CODE CLASSIFICATION:
 1A) LIST (1) EXIT FOR 50 SEATS TOTAL PLEASE SEE THE
 2010 FBC-B TABLE 1015.1 ONE EXIT UNDER THE MERCANTILE
 OCCUPANCY IS MAXIMUM AT 49 OCCUPANTS.
 1B) PLEASE NOTE UNDER APPLICABLE CODES THIS PLAN IS TO
 BE BUILT IN THE VILLAGE OF NORTH PALM BEACH.
  
 2) THERE IS A COVERSHEET LISTING PRODUCT APPROVALS,
 THERE IS NO HEADER, TITLE BLOCK FROM A CONTRACTOR NOR
 THE DESIGNER, NO SHOP DRAWING STAMP OF APPROVAL, NOR
 SIGNATURE OF THE DESIGNER OF RECORD INDICATING THEY
 WERE REVIEWED AND CODE COMPLIANT. 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2A) KAWNEER OUTSWING STOREFRONT DOORS NOA 11-1013.03
 TECHNICAL SHEETS SUBMITTED 8 1/2 X 11 SIZED FOR 8 1/2 X
 14 CUT OFF 1/3 OF SHEET.
 2B) KAWNEER STOREFRONT NOA 11-0908.10 TECHNICAL SHEETS
 SUBMITTED 8 1/2 X 11 SIZED FOR 8 1/2 X 14 CUT OFF 1/3
 OF SHEET.
 2C) TIA BAR TC-5 SERIES ROOF CURBS NOA-0828.02
 TECHNICAL SHEETS SUBMITTED 8 1/2 X 11 SIZED FOR 8 1/2 X
 14 CUT OFF 1/3 OF SHEET.
 2D) MIAMI TECH ALUMINUM A/C STANDS 13-1017.09 TECHNICAL
 SHEETS SUBMITTED 8 1/2 X 11 SIZED FOR 8 1/2 X 14 CUT
 OFF 1/3 OF SHEET.
 FLEMING-BARON EXTERIOR DOOR FL 14237-R1 NO TECHNICAL
 SHEETS SUBMITTED.
 GAF MODIFIED FL 13464- R0 THE ROOFING SUB-SYSTEMSTO BE
 APPLIED NOT IDENTIFIED NOR THE ASSOCIATED PRESSURES.
  
 3) SHEET S-2 THE WIND DESIGN PRESSURES INDICATE A B
 EXPOSURE PLEASE REVIEW WHEN WITHIN 1400 FT OF THE
 INTERCOASTAL FOR THIS LOCATION TO BE CONSIDERED A B
 EXPOSURE THE JOBSITE LOCATION WOULD NEED TO BE A
 MINIMUM 2,600 FT AWAY FROM THE INTERCOASTAL. FBC-B
 1609.4.2 SURFACE ROUGHNESS CATEGORIES. BECAUSE THE
 EXPOSURE C CATEGORY HAS MULTIPLIERS WITH ITS HEIGHT THE
 PRESSURES PROVIDED ARE LOW. TABLE 1609.7(2).
  
 4A) SHEET S-2 DETAIL # 3 SHOWS A NEW CONCRETE DECK- THE
 PLANS DO NOT PROVIDE TYPE OR AMOUNT OF RE-INFORCING
 STEEL OR CONCRETE MIX? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4B) DETAIL #2 SHOWS A NEW ROOF DECK NOTE SEE PLANS
 AGAIN NO DETAIL FOR RE-INFORCING STEEL OR CONCRETE MIX,
 NEW ROOF PITCH W/ VERMICULITE?
  
 5) SHEET A8.0 SECTIONS 2,3 & 4 ARE THESE SECTIONS FOR
 THE SIGN OR BUILT OUT WALL SECTIONS? NO ATTACHMENT,
 FRAMING OR MATERIALS FOR THE SURFACE FINISH?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-08-17 Cont ID  
Sent By skennedy Date 2015-08-17 Time 14:32 Rev Time 0.00
Received By skennedy Date 2015-08-17 Time 14:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-07-21 Cont ID  
Sent By dhayes Date 2015-07-21 Time 08:21 Rev Time 0.00
Received By dhayes Date 2015-07-21 Time   Sent To  
Notes
2015-07-22 08:20:28NO NEW ELECTRICAL PLANS INCLUDED IN THE RESUBMITTAL
 PACKAGE. EMAILED AND CORRESPONDED WITH DAMON OF
 ROBLING. HE FORWARDED TO BRIAN ALLEN OF ROBLING, HE
 ASSURES ME THEY WILL INCLUDE THE ELECTRICAL SHEETS IN
 THE NEXT RESUBMITTAL COMING SOON...
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-28 Cont ID  
Sent By dhayes Date 2015-01-28 Time 14:59 Rev Time 0.00
Received By dhayes Date 2015-01-28 Time 13:41 Sent To  
Notes
2015-01-28 13:41:241/28/2015
 PROJECT: KFC
 PERMIT#: 15010897
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) SHEET T1.0
 CHANGE THE VERSION OF THE NATIONAL ELECTRICAL CODE IN
 EFFECT AT THE TIME OF THIS SUBMITTAL FROM 2011 TO THE
 2008 NEC.
  
 2) SHEET E2.0
 PROVIDE A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH
 NEC TABLE 250.66 FOR ELECTRICAL SYSTEM RISER.
 INDICATE THE CIRCUIT FEEDING PANEL LA.
 INDICATE THE FEEDER SIZE AND TYPE FEEDING PANEL LA.
 PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-07-07 Cont ID  
Sent By cranford Date 2015-07-07 Time 11:08 Rev Time 0.00
Received By cranford Date 2015-07-02 Time 14:51 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-02-12 Cont ID  
Sent By cranford Date 2015-02-12 Time 14:47 Rev Time 0.00
Received By cranford Date 2015-02-12 Time 13:53 Sent To  
Notes
2015-02-12 14:47:081. THE LOADING AREA CANNOT BE LOCATED WITHIN THE
 PROPOSED DUMPSTER ENCLOSURE. PLEASE SHOW THE LOADING
 AREA IN ANOTHER LOCATION.
  
 2. PLEASE LABEL TO GATE WIDTH AND INTERIOR OPENINGS FOR
 THE PROPOSED DUMPSTER ENCLOSURE. THE ENCLOSURE MUST
 MEET THE MINIMUM DIMENSIONS SHOWN IN SECTION 94-444,
 FIGURE XIV-3 OF THE CITY'S CODE OF ORDINANCES.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-12 Cont ID  
Sent By pleduc Date 2015-06-12 Time   Rev Time 0.00
Received By pleduc Date 2015-06-12 Time 09:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By pleduc Date 2015-02-10 Time   Rev Time 0.00
Received By pleduc Date 2015-02-10 Time 16:10 Sent To  
Notes
2015-02-10 17:28:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE REVISE THE EDITION OF THE FLORIDA LIFE SAFETY
 CODE TO 2012.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANY LOADS,
 EXIT PATHS, COMMON PATHS OF TRAVEL, EXIT PATH
 DIMENSION, EIXTS, EXIT DOORS, AND FIRE EXTINGUISHERS
 LOCATIONS.
  
 PROVIDE CONSTUCTION COMMENTS/NOTES ON THE PLAN
 INDICATING THE INSTALLATION OF A NFPA 96 COMPLIANT HOOD
 SYSTEM TO BE SUBMITTED THROUGH SEPARATE SHOP DRAWINGS.
  
 PROVIDE CONSTRUCTION COMMENTS/NOTE ON THE PLAN
 INDICATING THE INSTALLATION OF A NFPA COMPLIANT HOOD
 SUPPRESSION SYSTEM TO BE SUBMITTED THROUGH SEPARATE
 SHOP DRAWINGS.
  
 PROVIDE INDICATION THE THE BUILDING ADDRESS WILL BE
 VISIBLE FROM THE STREET. NUMBERS SHALL BE ATTACHED TO
 THE BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081, STRUCTURES WITH LIGHT FRAME
 FLOOR/ROOF TRUSS CONSTRUCTION SHALL BE IDENTIFIED WITH
 A SIGN AFFIXED TO THE BUILDING. PROVIDE INDICATIONS
 THAT A MALTESE CROSS 8-INCHES WIDE AND 8-INCHES TALL
 AND BE OF A BRIGHT RED REFLECTIVE COLOR AND BEAR THE
 APPROPRIATE LETTER R/F/RF DESIGNATION SHALL BE
 INSTALLED WITHIN 24" OF THE FRONT DOOR.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION NFPA 101, 7.2.1.5.9, THE LOCK/LATCH
 RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR
 WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-07-11 Cont ID  
Sent By tklarge Date 2015-07-11 Time 07:21 Rev Time 0.00
Received By tklarge Date 2015-07-11 Time 07:15 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-01-30 Cont ID  
Sent By tklarge Date 2015-01-30 Time 11:34 Rev Time 0.00
Received By tklarge Date 2015-01-30 Time 11:27 Sent To  
Notes
2015-01-30 11:34:41GAS
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER 2010 FL. GAS CODE SEC. 301.3.
 2) REFER TO THE APPLICABLE PIPE SIZING TABLE ON SHT.P-2
 FROM THE 2010 FGC THAT WAS USED TO SIZE THE GAS
 PIPING.FGC SEC.402.3.
 3) SHOW THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING
 FROM THE POINT OF DELIVERY. 402.4.1.
 4) INDICATE THE TYPE OF PIPE BEING USED FOR THE GAS
 SYSTEM. WPB AMEND.TO 2010 FBC SEC.107.2.1.
 5) INDICATE THE PIPE SIZE OF THE DROPS TO THE
 EQUIPMENT. WPB AMEND.TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-24 Cont ID  
Sent By jwitmer Date 2015-08-24 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2015-08-19 Time 14:41 Sent To  
Notes
2015-08-19 14:41:36RESUB ROUTED TO DKITTREDGE VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-18 Cont ID  
Sent By dkittred Date 2015-08-18 Time 14:45 Rev Time 0.00
Received By dkittred Date 2015-07-31 Time 09:06 Sent To  
Notes
2015-07-31 09:13:32C30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-22 Cont ID  
Sent By dhayes Date 2015-07-22 Time 08:21 Rev Time 0.00
Received By dhayes Date 2015-06-11 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-02 Cont ID  
Sent By hmoser Date 2015-03-02 Time 15:51 Rev Time 0.00
Received By hmoser Date 2015-01-27 Time 12:29 Sent To  
Notes
2015-01-28 12:30:27C26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-02-25 Cont ID  
Sent By jwitmer Date 2015-02-25 Time 07:44 Rev Time 0.00
Received By jwitmer Date 2015-02-25 Time 07:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-29 Cont ID  
Sent By hmoser Date 2015-06-29 Time 11:16 Rev Time 0.00
Received By hmoser Date 2015-06-29 Time 10:58 Sent To  
Notes
2015-06-29 11:06:34PASS PROVISO
  
 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE RTU CURB
 TO
 ROOF TIEDOWN AND RTU TO CURB TIEDOWN. PROVIDE THE
 TYPE AND SIZE ANCHOR USED ON THE DETAIL. PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 3) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL
 2010 FBC (M)
 4) HOODS AND COOLERS REQUIRE SEPARATE APPLICATION
 PLANS AND PERMIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-02 Cont ID  
Sent By hmoser Date 2015-03-02 Time 15:51 Rev Time 0.00
Received By hmoser Date 2015-03-02 Time 15:07 Sent To  
Notes
2015-03-02 15:51:02PLAN DENIED
 1) RETURN AIR REQUIRED FOR OFFICE PER SECTION
 601.4 BALANCED RETURN AIR 2010 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON
 CURB TO ROOF TIE DOWN AND RTU TO CURB
 TIE DOWN .PROVIDE TYPE SIZE AND SPACING
 OF ANCHOR. PER SECTION 301.12 WIND RESISTANCE
 FBC (M) 2010
 3) SEPARATE APPLICATION PLAN AND PERMIT REQUIRED
 FOR HOODS AND COOLERS .

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-11 Cont ID  
Sent By tklarge Date 2015-07-11 Time 07:15 Rev Time 0.00
Received By tklarge Date 2015-07-11 Time 06:40 Sent To  
Notes
2015-07-11 07:05:42 
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-30 Cont ID  
Sent By tklarge Date 2015-01-30 Time 11:26 Rev Time 0.00
Received By tklarge Date 2015-01-30 Time 06:43 Sent To  
Notes
2015-01-30 11:26:381) SHT.A1.0 - TOILET ROOMS ARE SHOWN AS 6 '- 8 3/4" IN
 WIDTH.THE ROOMS ARE NOT WIDE ENOUGH TO COMPLY WITH FAC
 604.3.1 AND THE FPC SEC. 405.3.1. THE MINIMUM WIDTH IS
 85" IF BUILT PERFECT OR 86" FOR CONSTRUCTION
 TOLERANCES.
 2) SUBMIT AN EQUIPMENT SCHEDULE FOR THE FOOD OPERATION.
 WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) SHT.A4.0 - THE REQUIRED CLEAR FLOOR SPACEDIMENSIONS
 FOR THE PLUMBING FIXTURES DOES NOT CORRELATE WITH THE
 WRITTEN DIMENSIONS; WATER CLOSET NEEDS 60 INCHES IN
 WIDTH, 30 INCHES FOR THE LAVATORY EQUALS 90 INCHES
 MINIMUM. THE PLAN SHOWS 80 3/4 ". CLARIFY.
 4) SHT. A.6 - SHOW THE MOUNTING HEIGHT FOR ALL TOILET
 ROOM ACCESSORIES. ALL ACCESSORIES SHALL COMPLY WITH THE
 2010 FL. ACCESS. CODE.
 5) SHT. A6.0 - SHOW THE HEIGHT DIMENSIONS OF ALL
 FIXTURES FROM THE FINISH FLOOR.COMPLY W/2010 FAC
 CHAPTER 306 FOR KNEE & TOE CLEARANCES AND CHAPTER 6 FOR
 PLUMBING ELEMENTS.
 6) SHT. P.1 - SIZE ALL SECTIONS OF THE WASTE STACKS &
 VENT STACKS, WPB AMEND.TO 2010 FBC SEC.107.2.1.
 7) SHT. P-1 - CLEANOUTS ARE REQD. IN THE BASE OF THE
 STACKS PER 2010 FPC SEC.708.3.4.
 8) SHT.P-1 - RISER DIAGRAM SHOWS A DRY VENT ON FIXTURE
 FD-2 AT DRIVE-THRU. DRY VENTS TO CONNECT ABOVE
 CENTERLINE OF DRAIN PIPE. FPC SEC.905.3.
 9) FLOOR DRAINS NOT RECEIVING THE DISCHARGE FROM
 INDIRECT WASTES SHALL BE PROVIDED WITH TRAP PRIMERS PER
 FPC SEC.1002.4.
 10) SHT. P-2 - HOSE BIBBS SHALL BE EQUIPPED WITH
 SHUTOFF VALVES PER FPC SEC.606.2.
 11) ALL BEVERAGE LINWS SHALL BE EQUIPPED W/BACKFLOW
 PREVENTERS COMPLYING WITH FPC SEC.608.16.1, ASSE 1022.
 NON-CARBONATED AND COFFEE BEVERAGE DISPENSERS SHALL
 COMPLY WITH FPC SEC.608.16.10, ASSE 1022.
 12) APPROVAL OF THE PLANS IS REQUIRED BY THE DEPT. OF
 BUSINESS & PROFESSIONAL REGULATION, DIVISION OF HOTEL &
 RESTAURANTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2015-08-20 Cont ID  
Sent By dkittred Date 2015-08-20 Time 10:11 Rev Time 0.00
Received By dkittred Date 2015-08-20 Time 09:47 Sent To  
Notes
2015-08-20 10:11:29PLANNING AND ZONING COMMENTS:
  
 8/20/15
  
 1. APPROVAL OF ZBA 3322 ALLOWS FOR 92'-7" SETBACK FOR
 DRIVE-THROUGH WINDOW EXPANSION FROM A RESIDENTIAL
 ZONING DISTRICT.
  
 2. SHEET SP1 REDLINED TO INCLUDE CORRECT REFERENCES TO
 MINIMUM PARKING, LOT, AND SETBACK REQUIREMENTS. PROVISO
 ADDED FOR ADDITIONAL STOP SIGN AND STOP BAR.
  
 3. SHEET FRP.1 REDLINED TO INCLUDE CORRECT/CLARIFIED
 PARKING SPACE LINE COLORING SCHEME.
  
 4. LANDSCAPE PERMIT IS REQUIRED TO BE SUBMITTED UNDER A
 SEPARATE APPLICATION FOR REVIEW AND A HOLD HAS BEEN
 PLACED ON THE FINAL C.O.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2015-08-18 Cont ID  
Sent By dkittred Date 2015-08-18 Time 14:44 Rev Time 0.00
Received By dkittred Date 2015-08-18 Time 09:10 Sent To  
Notes
2015-08-18 14:44:49PLANNING AND ZONING COMMENTS: ***FAILED**
  
 8/18/15
  
 ITEMS TO BE REVISED:
  
 1. APPLICANT TO SUBMIT REVISED DRAWNING SHOWING 3 FOOT
 WIDE WINDOW ON THE NORTH SIDE OF THE BROADWAY ENTRY
 DOOR.
  
 GENERAL COMMENT:
  
 2. APPLICANT WILL SUBMIT SEPARATE LANDSCAPE PERMIT IN
 ACCORDANCE WITH 6/23/15 ZONING COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By dkittred Date 2015-06-23 Time 11:37 Rev Time 0.00
Received By dkittred Date 2015-06-17 Time 10:04 Sent To  
Notes
2015-06-23 11:37:04PLANNING AND ZONING COMMENTS: ***FAILED***
  
 6/23/15
  
 1. A GENERAL CALCULATION SHOWS THAT THE WINDOW COVERAGE
 ALONG THE LENGTH OF THE BUILDING FACADE ALONG BROADWAY
 HAD DECREASED FROM 36% TO 22%. (EXISTING CODE
 REQUIREMENT IS 70%). DUE TO THE NATURE OF THE
 RENOVATION THE FULL 70% WILL NOT NEED TO BE ACHIEVED,
 HOWEVER, A MINIMUM OF 36% WINDOW COVERAGE WILL BE
 REQUIRED TO BE MAINTAINED. PLEASE DEMONSTRATE
 COMPLIANCE. ANY DECREASE BELOW WHAT IS EXISTING WILL
 REQUIRE A VARIANCE.
  
 2. PROVIDE A MINIMUM 5 FOOT SETBACK FOR THE DUMPSTER
 ENCLOSURE.
  
 3. PHOTOMETRIC PLAN WILL NEED TO INCLUDE THE LIGHT
 SPILLAGE AT THE PROPERTY LINE. IN ACCORDANCE WITH ZLDR
 SEC. 94-310(D), ILLUMINATION SHALL NOT BE GREATER THAN
 0.5 FC AT THE BOUNDARY TO A RESIDENTIAL ZONING
 DISTRICT. THE SUBJECT PROPERTY ABUTS A RESIDENTIAL
 ZONING DISTRICT TO THE EAST. PLEASE DEMONSTRATE
 COMPLIANCE.
  
 4. RESPONSE COMMENTS INDICATE THAT SURVEY WAS PROVIDED,
 HOWEVER, THERE WAS NO SURVEY INCLUDED IN THE SUBMITTAL
 PACKET.
  
 5. ZONING APPROVAL OF THE DRIVE-THRU WINDOW EXPANSION
 ON THE BACK IS PENDING SUBMITTAL AND APPROVAL OF A
 CLASS B SPECIAL USE PERMIT APPLICATION FOR A WAIVER TO
 THE BUILDING DISTANCE FROM A RESIDENTIAL ZONING
 DISTRICT.
  
 6. PROVIDE STOP SIGN AND STOP BAR AT THE POINT WHERE
 CUSTOMER PARKING DRIVE LANE INTERSECTS DRIVE-THRU EXIT
 LANES.
  
  
 GENERAL COMMENTS:
  
 7. THE CHART FOR PROPERTY DEVELOPMENT REGULATIONS
 INCORRECTLY LISTS MINIMUM LOT SIZE AND SETBACK
 REQUIREMENTS. PLANS HAVE BEEN RED LINED TO INDICATE THE
 CORRECTIONS. ANY REVISIONS TO SHEET SP 1 WILL NEED TO
 INCORPORATE THESE CHANGES.
  
 8. PLANS WERE RED LINED TO MAKE CORRECTIONS TO THE
 PARKING CALCULATIONS WHICH REQUIRE 3 PARKING SPACES PER
 1,000 SQUARE FEET OF BUILDING AREA AND ONE HANDICAP
 PARKING SPACES FOR UP TO 25 REGULAR PARKING SPACES
 PROVIDED. ANY REVISIONS TO SHEET SP 1 WILL NEED TO
 INCORPORATE THESE CHANGES.
  
 9. DIMENSIONED PARKING SPACES ON THE SITE PLAN SHOW 9',
 HOWEVER, THE STANDARD DETAIL SHOWS PARKING SPACES AT
 9.5'. YOU MAY WISH TO HAVE THESE CONSISTENT TO AVOID
 CONFUSION WHEN THE PARKING LOT IS STRIPED.
  
 10 SEPARATE PERMIT IS REQUIRED FOR LANDSCAPING. PLEASE
 ADDRESS THE FOLLOWING:
 A. DEMONSTRATE COMPLIANCE WITH ZLDR SEC.
 94-442(B)(2)(B) AND SEC. 94-443.
 B. SHOW ANY UTILITIES AND UTILITY EASEMENTS ON THE
 LANDSCAPE PLAN.
 C. PROVIDE LANDSCAPE ISLANDS/BUFFERS THAT ARE A MINIMUM
 OF 5 FEET IN WIDTH AS MEASURED FROM THE INSIDE OF THE
 CURBING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By dkittrid Date 2015-02-10 Time 12:17 Rev Time 0.00
Received By dkittred Date 2015-02-03 Time 08:17 Sent To  
Notes
2015-02-10 12:14:37PLANNING AND ZONING REVIEW ***FAILED***
  
 2/10/15
  
 BUILDING COMMENTS:
  
 1. ZLDR SEC. 94-221(D)(5) REQUIRES STOREFRONTS ALONG
 FRONTAGE LINES...EACH STOREFRONT MUST HAVE CLEAR GLAZED
 AREAS, ALONG A MINIMUM OF 70 PERCENT OF ITS FACADE
 LENGTH, BETWEEN TWO AND EIGHT FEET FROM THE GROUND.
 WHILE ADDITIONAL WINDOWS WITH CLEAR GLAZING IS
 PREFERRED TO MEET THE MINIMUM GLAZING REQUIREMENT WITH
 THE FACADE RENOVATION, IT IS UNDERSTOOD THAT THERE ARE
 EXISTING INTERNAL FUNCTIONS OF THE EXISTING BUILDING
 WHICH DO NOT MAKE THIS OPTIONS PRACTICAL. HOWEVER,
 ADDITIONAL DESIGN ELEMENTS SUCH AS FAUX WINDOW,
 TRELLIS, LANDSCAPING, AWNINGS, ARCHITECTURAL ELEMENTS,
 ETC. WILL NEED TO BE PROPOSED ALONG THE 'BLANK' PORTION
 OF THE FACADE ALONG BROADWAY TO MEET THE INTENT OF THE
 BMUD ZONING DISTRICT TO PROVIDE FOR AN URBAN,
 PEDESTRIAN-ORIENTED DISTRICT.
  
 2. PLEASE DEMONSTRATE COMPLIANCE WITH THE FOLLOWING
 CODE REQUIREMENTS FOR PROPOSED WINDOWS:
 A. ZLDR SEC. 94-221(D)(6)(C) - 'WINDOWS SHALL BE
 RECESSED A MINIMUM OF TWO INCHES FROM THE EXTERIOR FACE
 OF THE FACADE.'
 B. ZLDR SEC. 94-221(D)(6)(D) - 'MULTIPLE WINDOWS IN THE
 SAME ROUGH OPENING SHALL BE SEPARATED BY A FOUR-INCH
 WIDE POST AND SIT ON ONE CONTINUOUS SILL.'
  
 SITE PLAN COMMENTS:
  
 3. INCLUDE PROPERTY SURVEY.
  
 4. DIMENSION BUILDING SETBACK INCLUDING THE
 ADDITION(S).
  
 5. DRIVE-THRU RESTAURANTS IN THE BMUD TYPE II ZONING
 DISTRICT ARE SUBJECT TO EXTRA REQUIREMENTS. ALL
 PRINCIPAL AND ACCESSORY STRUCTURES SHALL BE 100 FEET
 FROM ANY RESIDENTIAL ZONING DISTRICT (ZLDR SEC.
 94-273(D)(66)). A RESIDENTIAL ZONING DISTRICT ABUTS THE
 SUBJECT PROPERTY TO THE EAST. PLEASE DIMENSION PLANS TO
 SHOW COMPLIANCE. ANY NEW ADDITIONS WITHIN THIS 100 FOOT
 SETBACK ARE NOT PERMITTED WITHOUT A WAVIER THROUGH THE
 CLASS B SPECIAL USE PERMIT PROCESS.
  
 6. DIMENSION DRIVE AISLES TO DEMONSTRATE COMPLIANCE
 WITH MINIMUM WIDTH REQUIREMENTS (ZLDR SEC. 94-485).
  
 7. HOW WILL SOMEONE IN THE PARKING LOT ACCESS THE
 BUILDING ENTRANCE? PLEASE INDICATE THE ROUTE OF SAFE
 PEDESTRIAN ACCESS.
  
 8. 'NEW CONCRETE WALK' ALONG THE SOUTH SIDE OF THE
 BUILDING IS NOT A FUNCTIONAL WALKWAY BECAUSE OF THE
 MENU BOARD AND PROPOSED ADDITION. IF THIS IS INTENDED
 TO BE A FUNCTIONAL WALKWAY OR PROVIDE A CONNECTION
 PLEASE REVISE TO DEMONSTRATE FEASIBILITY AS A WALKWAY.
 OTHERWISE, PROVIDE LANDSCAPING WITHIN THIS AREA RATHER
 THAN CONCRETE.
  
 9. PLEASE PROVIDE AND INDICATE THE LOCATION OF TRAFFIC
 CONTROL SIGNAGE (I.E. DO NOT ENTER, ONE-WAY, STOP).
  
 10. HOW DOES SOMEONE EXIT THE HANDICAP PARKING SPACE?
 IT APPEARS THEY WOULD NEED TO BACK-UP IN TO THE
 ENTRANCE DRIVE TO BE ABOUT TO PROCEED IN THE ONE-WAY
 DIRECTION AROUND THE BUILDING. THIS IS VERY UNSAFE FOR
 ANY PARKING SPACE TO BE LOCATED IN FRONT OF THE
 BUILDING WITH THE PROPOSED CONFIGURATION. PLEASE
 REVISE.
  
 11. PLEASE REVISE PARKING CALCULATIONS IN ACCORDANCE
 WITH ZLDR SEC. 94-221(F)(1). THE SITE WILL LIKELY
 EXCEED THE MAXIMUM PARKING PERMITTED, HOWEVER, THE SITE
 IMPROVEMENTS ARE BRINGING THE SITE CLOSER TO COMPLIANCE
 WITH THE MAXIMUM PARKING REGULATIONS SO THE CAP WILL
 NOT APPLY AS LONG AS YOU ARE REDUCING THE PARKING AND
 NOT INCREASING IT.
  
 12. PLEASE PROVIDE BICYCLE PARKING IN ACCORDANCE WITH
 ZLDR SEC. 94-111(I). INDICATE LOCATION OF BICYCLE
 PARKING ON SITE PLAN AND PROVIDE DETAIL SHOWING THE
 BICYCLE RACK AND MINIMUM SPACING DIMENSIONS. (NOTE:
 BICYCLE RACK SHOULD BE AN INVERTED U, A, POST AND LOOP,
 OR SIMILAR STYLE. WAVE STYLE RACKS ARE NOT PERMITTED.)
  
 13. NEW LIGHTING IS PROPOSED FOR THE BUILDING. PLEASE
 PROVIDE PHOTOMETRIC PLAN DEMONSTRATING COMPLIANCE WITH
 ZLDR SEC. 94-309(A) AND 94-310(D).
  
 14 PARKING STRIPING DETAIL WAS NOT PROVIDED. PLEASE
 PROVIDE DOUBLE LINE STRIPING DETAIL IN ACCORDANCE WITH
 ZLDR SEC. 94-485.
  
 15. ALL PARKING SPACES NEED TO BE DIMENSIONED.
  
 16. PROVIDE SIGNAGE AND STRIPING DETAILS FOR THE
 HANDICAP PARKING SPACE.
  
 17. BASED ON 1) EXTERIOR IMPROVEMENTS EXCEEDING $10,000
 (ZLDR SEC. 94-219(D)(9)(A)) AND/OR 2) THE VALUE OF
 CONSTRUCTION ($200,000) EXCEEDING 50% OF THE
 STRUCTURE'S VALUE ($44,334) ACCORDING TO THE PBC
 PROPERTY APPRAISER (ZLDR SEC. 94-441(C)(2)), THE
 LANDSCAPING ON THE SITE SHALL BE BROUGHT IN TO
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDRS. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 18. THE CONCRETE ISLAND IN REAR OF PROPERTY BEING
 PROPOSED WITH THE NEW PARKING LOT CONFIGURATION SHOULD
 BE LANDSCAPED.
  
 19. PLEASE NOTE THAT ANY MECHANICAL SYSTEMS, BACKFLOW
 PREVENTERS, AND SIMILAR DEVICES SHALL BE SCREENED FROM
 VIEW ON ALL SIDE BY THE FULL HEIGHT OF THE STRUCTURE BY
 LANDSCAPING OR BUILT ELEMENTS DESIGNED AS AN INTEGRAL
 PART OF THE BUILDING ARCHITECTURE.
  
 20. WILL SITE IMPROVEMENTS REQUIRE THE REMOVAL OF ANY
 TREES? IF YES, PLEASE SUBMIT A TREE ALTERATION PERMIT
 APPLICATION THROUGH THE PLANNING DIVISION: HTTP://WPB.O
 RG/PLANNING/WP-CONTENT/UPLOADS/SITES/37/2013/04/TREEALT
 ERATIONPERMITREVISED03-12-09.PDF
  
 21. A NEW DOUBLE DRIVE-THRU CONFIGURATION IS BEING
 PROPOSED FOR THE SITE TO FACILITATE A MORE EFFICIENT
 MOVEMENT OF PEOPLE THROUGH THE DRIVE-THRU. THERE IS
 SOME CONCERN WITH EXCESSIVE STACKING TO SPILL OUT ON TO
 BROADWAY. WILL THERE BE A PLAN IN PLACE TO PREVENT
 EXCESSIVE STACKING AND BACK-UP ONTO BROADWAY?
  
 GENERAL COMMENTS:
  
 22. SEPARATE PERMITS ARE REQUIRED FOR LANDSCAPING AND
 PARKING LOT STRIPING.
  
 23. SEPARATE PERMIT IS REQUIRED FOR SIGNAGE AND ZONING
 WILL CONDUCT THEIR REVIEW OF THE SIGNAGE AT THAT TIME.
  
 24. ALL REFERENCES TO THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS) CAN BE FOUND AT THE
 FOLLOWING LINK: HTTPS://WWW.MUNICODE.COM/LIBRARY/FL/WES
 T_PALM_BEACH/CODE_OF_ORDINANCES/TOC
  
 25. PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS WHEN
 RESUBMITTING.
  
  
 PLEASE FEEL FREE TO CONTACT ME PRIOR TO RESUBMITING TO
 DISCUSS PROPOSED REVISIONS.
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  
2015-02-02 15:26:582/2/15