Plan Review Details - Permit 15010888
Plan Review Stops For Permit 15010888
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By shill Date 2015-02-17 Time 17:43 Rev Time 0.00
Received By shill Date 2015-02-17 Time 17:43 Sent To  
Notes
2015-02-17 17:43:58PROVISO - PROPOSED PLEXIGLASS AND PLYWOOD INSTALLATION
 IS TO BE UNDER A SEPARATE PERMIT
 THIS SCOPE REQUIRES A PERMIT; NOT "REGLAZING"

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-29 Cont ID  
Sent By shill Date 2015-01-29 Time 13:13 Rev Time 0.00
Received By shill Date 2015-01-29 Time 13:13 Sent To FIRE
Notes
2015-01-29 13:13:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A PLAN SHOWING LOCATION OF PROPOSED DOORS,
 FBC 107. INCLUDE A BASIC FLOOR PLAN WHICH SHOWS THE
 OCCUPANCY CLASSIFICATIONS SERVED, FBC CHAPTER 10.
  
 SEE FBC 1008, ARE PANIC DEVICES PROPOSED?
  
 CIRCLE ALL HARDWARE OPTIONS, INCLUDING THRESHOLD. IF
 THIS SERVES ASSEMBLY OCCUPANCY, IT APPEARS THAT PANIC
 DEVICES WILL LIKELY BE REQURED.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-11 Cont ID  
Sent By shill Date 2015-02-17 Time 17:44 Rev Time 0.00
Received By pleduc Date 2015-02-11 Time 12:21 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-30 Cont ID  
Sent By pleduc Date 2015-01-30 Time   Rev Time 0.00
Received By pleduc Date 2015-01-30 Time 08:42 Sent To PC
Notes
2015-01-30 08:45:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE PREVENTION REITERATES BUILDING COMMENTS.
  
 ADDITIONALLY, PLEASE INDICATE THE OCCUPANCY
 CLASSIFICATION AND OCCUPANCT LOADS
  
 LOCKS
  
 PLEASE PROVIDE THE DOOR LOCK INFORMATION COMPLIANT WITH
 THE BELOW REQUIRMENTS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 THUMB-TURN LOCK SHALL BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-17 Cont ID  
Sent By shill Date 2015-02-17 Time 17:44 Rev Time 0.00
Received By shill Date 2015-02-09 Time 08:08 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-30 Cont ID  
Sent By pleduc Date 2015-01-30 Time   Rev Time 0.00
Received By pleduc Date 2015-01-26 Time 15:45 Sent To  
Notes
2015-01-29 13:16:211/29 TO FIRE
  
2015-01-26 15:45:54ROUTED TO BUILDING LESS THAN $5K NSD