| Plan Review Stops For Permit 15010873 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-04-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-13 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-13 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-03-05 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-03-05 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2015-03-05 07:40:54 | 1ST REVIEW: FBC 2010 | | | | | | 1) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR | | | SUBMITTALS. | | | | | | 2) FCB 107.3.5.3 (13)- PROVIDE AN ENERGY SUBMITTAL. | | | | | | 3) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT,) THE VALUATION OF $20,000.00 | | | IS LOW. PLEASE AMMEND THE PRIMARY APPLICATION TO | | | INCLUDE THE VALUES INDICATED ON THE SUB PERMIT | | | APPLICATIONS. | | | | | | 4) FBC-EXISTING BUILDING CODE CHAPTER 4 - PROJECT DATA | | | ON SHEET A-2 SHOULD BE AMMENDED TO INDICATE THAT THE | | | SCOPE OF WORK IS ALSO AN ADDITION. THE BLOCK CONTAING | | | THE INFORMATION INDICATES IT IS AN "ALTERATION LEVEL | | | II." ALTHOUGH ADDITION IS MENTIONED IN THE INFORMATION, | | | IT SHOULD BE NOTED THAT THE SCOPE IS ALSO "ADDITION." | | | | | | 5) FBC-RESIDENTIAL BUILDING CODE CHAPTER 3 - | | | ENGINEERING CRITERIA ON SHEET A-2 SHOULD BE AMMENDED TO | | | INDICATE THAT THEAPPLICABLE CDOE IS: "FBC-RESIDENTIAL | | | BUILDING CODE" AND THE WIND DESIGN CRITERIA IS FOUND IN | | | CHAPTER 3. | | | | | | | | | IMPORTANT NOTICE EFFECTIVE MARCH 16, 2015, ALL PERMIT | | | APPLICATION PLAN REVIEWS WILL BE PERFORMED | | | ELECTRONICALLY | | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | | 1. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 2. INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | | NAMING CONVENTION FOR EACH DOCUMENT | | | 3. INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 4. ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS | | | SUBJECT TO ADMINISTRATIVE FEES TO DIGITIZE THE | | | DOCUMENTS | | | | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-04-09 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-04-09 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2015-04-09 11:39:56 | ROUTED TO S. KENNEDY'S DESK FOR BUILDING AND MECHANICAL | | | REVIEWS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-03-02 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-03-02 |
Time |
10:54 |
Sent To |
B |
|
| Notes |
| 2015-03-02 11:43:04 | 3/2/2015 | | | PROJECT: 321 VALENCIA RD. ADDITION | | | PERMIT#: 15010873 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION | | | | | | PROVIDE REVISED PLANS AND DOCUMENTATION ON SITE TO THE | | | INSPECTOR AT THE FIRST INSPECTION TO INCLUDE THE | | | FOLLOWING: | | | | | | 1) NEC 230.70 | | | INDICATE THE LOCATION OF THE ELECTRICAL PANEL TO BE IN | | | COMPLIANCE WITH THE NEC. 230.70 | | | | | | 2) 240.4, 240.24, 310.15(B)(6), 310.16 | | | A CODE COMPLIANT RISER DIAGRAM SHALL BE ON SITE FOR THE | | | INSPECTOR TO INDICATE COMPLIANCE WITH NEC 240.4, | | | 240.24, 310.15(B)(6), AND 310.16 | | | | | | 3) NEC215.5 | | | PROVIDE A REVISED LOAD CALCULATION TO INDICATE THE | | | ADDITION OF NEW LOADS. | | | | | | 4) NEC 408.4 | | | PROVIDE A NEW PANEL SCHEDULE TO INDICATE THE ADDITION | | | OF NEW LOADS. | | | | | | 5) NEC 250.94 | | | PROVIDE AN INTERSYSTEM BOND STRIP AT THE ELECTRICAL | | | SERVICE ON THE ELECTRICAL GROUNDING ELECTRODE. | | | | | | 6) NEC 210.12 | | | PROVIDE ARC FAULT CIRCUIT PROTECTION ON ALL NEW | | | CIRCUITS FOR THE NEW BEDROOM. | | | | | | 7) NEC 406.11 | | | RECEPTACLES SHALL BE TAMPER RESISTANT. | | | | | | 8) FBC-RESIDENTIAL 314 AND 315. | | | PROVIDE SMOKE DETECTORS AS REQUIRED BYTHE FBC. VERIFY | | | ALL SMOKE DETECTORS ARE INSTALLED AND INTERCONNECTED | | | THROUGHOUT THE EXISTING RESIDENCE. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-04-08 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-04-08 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-04-08 |
Time |
11:22 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-01-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-01-28 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-01-28 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-04-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-24 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-23 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2015-04-23 12:26:10 | TO SAK DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-04-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-13 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-03-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-03-30 12:21:12 | PER PHONE CONV W/ F MITTNER SHE WILL COME DOWN & GET | | | PERMIT PKG FOR HISTORIC APPROVAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-03-05 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-01-28 |
Time |
16:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2015-04-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-16 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-16 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-03-05 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-03-05 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2015-03-05 07:40:03 | 1ST REVIEW: FBC 2010 | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-04-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-13 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-13 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-03-05 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-02-25 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2015-03-05 07:39:02 | 1ST REVIEW: FBC 2010 | | | | | | NO MECHANICAL PLANS HAVE BEEN PROVIDED. PROVIDE PLANS | | | PER FBC 107. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-04-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-13 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-13 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-01-31 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-01-31 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-31 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2015-01-31 07:26:15 | A CODE COMPLIANT SANITARY RISER SHALL BE ONSITE FOR | | | INSPECTOR AT ROUGH PLUMBING INSPECTION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2015-04-24 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-24 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-24 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-04-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-13 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-13 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2015-04-13 11:18:27 | 2ND REVIEW: FBC 2010 | | | | | | FBC 107: THE PRODUCT APPROVALS SUBMITTED FOR THE ROOF | | | WERE FOR TILE ONLY WITH NO SECONDARY WATER RESISTANT | | | BARRIER. THE ROOF SECTION ONLY INDICATES A SINGLE 30# | | | UNDERLAYMENT. PLEASE SPECIFY THE THE ENTIRE ROOFING | | | SYSTEM PROPOSED. YOU MAY REVISE THE SECTION BY LETTER | | | AND SUBMIT AN ADDITIONAL PRODUCT APPROVAL IF | | | APPLICABLE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-03-05 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-03-05 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2015-03-05 07:44:45 | 1ST REVIEW: FBC 2010 | | | | | | SEE BUILDING PLAN REVIEW COMMENTS AS TO ROOFING PRODUCT | | | APPROVAL. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-01-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-01-28 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-01-28 |
Time |
09:52 |
Sent To |
B |
|
| Notes |
|
|