Plan Review Details - Permit 15010861
Plan Review Stops For Permit 15010861
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-05-29 Cont ID  
Sent By jgomez Date 2015-05-29 Time 12:44 Rev Time 0.00
Received By jgomez Date 2015-05-29 Time 12:43 Sent To  
Notes
2015-05-29 12:45:45BUILDING REVIEW APPROVED WITH PROVISO:
  
 5/29/15 MET W/ RAFAEL RODRIGUEZ. ROOFING CONTRACTOR MAY
 SUBMIT FLAT ROOF PRODUCT APPROVAL AND RAS 117
 CALCULATIONS WHEN APPLYING FOR ROOFING SUB-PERMIT. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-05-21 Cont ID  
Sent By jgomez Date 2015-05-21 Time 08:09 Rev Time 0.00
Received By jgomez Date 2015-05-21 Time 07:53 Sent To  
Notes
2015-05-21 08:22:38BUILDING REVIEW COMMENTS TO INFORMATION SUBMITTED TO
 ADDRESS PREVIOUS PROVISO:
  
 THE ORIGINAL PROVISO COMMENT WAS:
  
 1- REVISE RAS 117 CALCULATIONS: ARCHITECTURAL PLANS AND
 NOA 12-0716.18 SUBMITTED CALL FOR INSULATED ROOF DECK.
 CALCULATIONS SUBMITTED ARE FOR A NON INSULATED
 ASSEMBLY. REVISE AS REQUIRED TO MATCH..
  
 NOTE: THE PROVISO WAS TO REVISE THE RAS 117
 CALCULATIONS BECAUSE THEY DIDN'T MATCH THE SELECTED
 ASSEMBLY TO BE INSTALLED. INFORMATION SUBMITTED WAS NOA
 12-0716.18 COVER PAGE AND PAGE 10 SHOWING THE INSULATED
 ASSEMBLY. THIS INFORMATION WAS ALREADY SUBMITTED AND
 APPROVED. WHAT WE NEED IS THE REVISED RAS 117
 CALCULATIONS TO MATCH THE SELECTED ASSEMBLY. REVISED
 CALCULATIONS WERE NOT SUBMITTED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-29 Cont ID  
Sent By jgomez Date 2015-04-29 Time 14:51 Rev Time 0.00
Received By jgomez Date 2015-04-29 Time 14:51 Sent To  
Notes
2015-05-15 09:48:135/15/15 TALKED TO RAFAEL (ARCH.) TO GO OVER PROVISO
 COMMENTS. JG.
  
  
2015-04-29 14:51:41BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE RAS 117 CALCULATIONS: ARCHITECTURAL PLANS AND
 NOA 12-0716.18 SUBMITTED CALL FOR INSULATED ROOF DECK.
 CALCULATIONS SUBMITTED ARE FOR A NON INSULATED
 ASSEMBLY. REVISE AS REQUIRED TO MATCH..

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jgomez Date 2015-03-05 Time 15:58 Rev Time 0.00
Received By jgomez Date 2015-03-05 Time 15:54 Sent To  
Notes
2015-03-05 16:02:03RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION WAS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. VALUATION BASED ON ALL SCOPE OF WORK
 SHOWN ON PLANS WAS UPDATED TO $120,000 MIN. THE PERMIT
 FEE BALANCE IS $2528.70.
  
 3- PROVIDE MANUFACTURER'S CUT SHEETS FOR 24EH SINGLE
 HUNG WINDOWS TO VERIFY COMPLIANCE WITH EGRESS
 REQUIREMENTS OF SEC. R310 OF 2010 FBC-RESIDENTIAL.
 (NOTE: ALSO SEE HISTORIC REVIEW COMMENTS REGARDING SIZE
 OF WINDOWS).
  
 4- DESIGN CRITERIA ON SHEET SP-1 AND SHEET S-000
 DOESN'T MATCH. EXPOSURE CATEGORY IS DIFFERENT. REVISE
 AS REQUIRED TO MATCH.
  
 5- COMPONENTS AND CLADDING ON SHEET S-000: ACCORDING TO
 FOOTNOTE ON FIGURE R301.2(7) THE MIN. DIMENSION FOR
 ZONE #3 IS 4'-0". REVISE THE "A" DISTANCE ON NOTE #2 OF
 DETAIL A ON SHEET S-000.
  
 6- ENERGY CALCULATIONS: REVISE DOORS INFORMATION. THERE
 ARE NOT WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS
 SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA.
  
 B) ROOF TILE ADHESIVE. NOA 12-0228.18 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA.
  
 C) SIMPSON HGAM10 STRUCTURAL CONNECTOR. JAX APEX
 TECHNOLOGY REPORT SUBMITTED IS NOT AN APPROVED PRODUCT
 APPROVAL. MANUFACTURER MAY APPLY FOR LOCAL PRODUCT
 APPROVAL IF THERE IS NOT AN OFFICIAL PRODUCT APPROVAL.
  
 D) TAMKO MODIFIED BITUMEN ROOF SYSTEM NOA 12-0716.18
 WAS SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA.
  
 E) ENTRY DOOR AS SHOWN ON PLANS.
  
 8- DESIGNER OF RECORD TO APPROVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
 NOTE: PLEASE STAMP REVIEW STAMP ON FRONT OF PRODUCT
 APPROVAL PAGE NOT ON THE BACK. THIS IS REQUIRED FOR THE
 PROPER RECORDS RETENTION SCANNING PROCESS.
  
 9- CLAY TILE NOA 12-0529.12 SUBMITTED DOESN'T SHOW ANY
 FASTENING SYSTEM USING #10 SCREWS. ARCHITECT TO REVISE
 ALL DETAILS AND SPECIFICATIONS ON PLANS TO MATCH
 PRODUCT APPROVAL OR PROVIDE A DIFFERENT CLAY TILE NOA
 THAT ALLOWS NAILS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 10- TAMKO MODIFIED BITUMEN ROOF SYSTEM: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 OF TAMKO NOA SUBMITTED. CALCULATIONS
 REQUIRED TO MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301 OF 2010 FBC-RESIDENTIAL.
  
 **** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-28 Cont ID  
Sent By dhayes Date 2015-05-28 Time 13:44 Rev Time 0.00
Received By dhayes Date 2015-05-28 Time 13:25 Sent To  
Notes
2015-05-28 13:21:55 
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-04-29 Cont ID  
Sent By dhayes Date 2015-04-29 Time 13:41 Rev Time 0.00
Received By dhayes Date 2015-04-29 Time 13:06 Sent To  
Notes
2015-04-29 13:41:174/29/2015
 PROJECT: PARK PL RESIDENTIAL RENOVATION
 PERMIT#: 15010861
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL ON THE
 FLOOR PLAN. WPB AMENDMENTS OF THE FBC 107
  
 2) EVEN THOUGH THE FUEL SOURCE FOR THE WATER HEATER IS
 GAS THERE IS AN ELECTRICAL IGNIGHTER CIRCUIT THAT
 REQUIRES A DISCONNECT. PROVIDE THE LOCATION OF THE
 ELECTRICAL CIRCUIT AND DISCONNECT FOR THE ELECTRICAL
 WATER HEATER. NEC422.31
  
 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. VERIFY
 CIRCUITS IN THE DINING ROOM ARE 20AMP CIRCUITS. THERE
 ARE NO CIRCUITS IN THE PANEL CIRCUIT DIRECTORY
 INDICATED FOR THE DINING ROOM. WPB AMENDMENTS OF THE
 FBC 107
  
 4) INDICATE A SPECIFIC PURPOSE OR USE FOR EACH OF THE
 CIRCUITS IN THE PANEL CIRCUIT DIRECTORY. EVERY CIRCUIT
 AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS
 TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC
 408.4
  
 5) VERIFY RECEPTACLE WALL SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8
 M (6 FT) FROM A RECEPTACLE OUTLET. NEC 210.52
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 11:02 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 09:22 Sent To  
Notes
2015-03-06 09:38:363/6/2015
 PROJECT: PARK PL RESIDENTIAL RENNOVATION
 PERMIT#: 15010861
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND
 THE LOCATION OF THE ELECTRICAL PANEL ON THE FLOOR PLAN.
 WPB AMENDMENTS OF THE FBC 107
  
 2) PROVIDE THE LOCATION OF THE ELECTRICAL CIRCUIT AND
 DISCONNECT FOR THE ELECTRICAL WATER HEATER. NEC422.31
  
 3) REVISE THE WATER HEATER CIRCUIT TO INCLUDE THE
 CORECT OCPD AND WIRE SIZE. IF THE PROPOSED WATER HEATER
 IS 6KW THE CIRCUIT NEEDS TO BE UPDATED TO BE APPROVED A
 CONTINUOUS DUTY CIRCUIT RATED AT 125% OVER THE
 CONNECTED LOAD. NEC 422.13
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By tklarge Date 2015-02-04 Time 04:49 Rev Time 0.00
Received By tklarge Date 2015-02-04 Time 04:42 Sent To  
Notes
2015-02-04 04:50:29MANUF. SPECS & INSTALLATION MANUALS FOR ALL GAS
 EQUIPMENT SHALL BE ONSITE FOR INSPECTOR @ ROUGH GAS
 INSPECTION.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-05-26 Cont ID  
Sent By fmittner Date 2015-05-26 Time 11:21 Rev Time 0.00
Received By fmittner Date 2015-05-26 Time 11:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By fmittner Date 2015-02-04 Time 11:27 Rev Time 0.00
Received By fmittner Date 2015-02-04 Time 11:26 Sent To  
Notes
2015-02-04 11:51:23WINDOW SIZES/PROPORTIONS ON THE FRONT SECOND FLOOR
 CANNOT CHANGE FROM ORIGINAL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-04 Cont ID  
Sent By jgomez Date 2015-06-04 Time 09:41 Rev Time 0.00
Received By jgomez Date 2015-06-03 Time 15:42 Sent To  
Notes
2015-06-03 15:44:44SENT JG DESK FOR FINAL REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-28 Cont ID  
Sent By dhayes Date 2015-05-28 Time 13:44 Rev Time 0.00
Received By dhayes Date 2015-05-20 Time 19:57 Sent To  
Notes
2015-05-20 19:58:42SUBMITTAL FOR ELECTRICAL AND BUILDING WITHOUT FINISHING
 ZONING AND HISTORIC REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2015-04-06 Time 15:03 Sent To  
Notes
2015-04-06 15:03:28RE-SUBMITTAL SENT TO R21 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 11:02 Rev Time 0.00
Received By dhayes Date 2015-01-26 Time 11:53 Sent To  
Notes
2015-01-28 11:50:53SENT TO R15 BIN FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-06-03 Cont ID  
Sent By ccole Date 2015-06-04 Time 15:43 Rev Time 0.00
Received By jgomez Date 2015-06-03 Time 15:42 Sent To  
Notes
2015-06-04 09:41:31$236.59 PAID. MU-2015-013027. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-04-29 Cont ID  
Sent By jgomez Date 2015-04-29 Time 15:33 Rev Time 0.00
Received By jgomez Date 2015-04-29 Time 15:33 Sent To  
Notes
2015-04-29 15:33:261- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jgomez Date 2015-03-05 Time 16:02 Rev Time 0.00
Received By jgomez Date 2015-03-05 Time 16:02 Sent To  
Notes
2015-03-05 16:02:311- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-30 Cont ID  
Sent By jgomez Date 2015-04-29 Time 18:40 Rev Time 0.00
Received By jgomez Date 2015-04-29 Time 18:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-06 Cont ID  
Sent By jgomez Date 2015-03-06 Time 08:39 Rev Time 0.00
Received By jgomez Date 2015-03-06 Time 08:37 Sent To E
Notes
2015-03-06 09:01:43RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND COMPLETE INFORMATION OF THE
 DESIGN PROFESSIONAL WHO SIGNED AND SEALED THE M.1 SHEET
 AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- SHEET M.1: MASTER BEDROOM NEEDS TO COMPLY WITH THE
 BALANCED RETURN AIR SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. NOTE: TAKE INTO CONSIDERATION THAT ALL
 SUPPLY AIR INTO THE MASTER SUITE NEEDS TO BE CONSIDERED
 TO COMPLY WITH THE BALANCED RETURN AIR. THERE IS A
 TRANSFER GRILL LOCATED IN THE AHU #2 CLOSET. IF THIS
 GRILL IS FOR THE MASTER BEDROOM BALANCED RETURN AIR
 REQUIREMENTS, THEN IT DOESN'T COMPLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By tklarge Date 2015-02-04 Time 04:42 Rev Time 0.00
Received By tklarge Date 2015-02-03 Time 11:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-06-04 Cont ID  
Sent By jgomez Date 2015-05-29 Time 12:46 Rev Time 0.00
Received By jgomez Date 2015-05-29 Time 12:46 Sent To  
Notes
2015-05-29 12:46:401- CLAY TILE NOA 12-0529.12.
 2- ROOF TILE ADHESIVE NOA 12-0228.18.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 5/29/15 MET W/ RAFAEL RODRIGUEZ. ROOFING CONTRACTOR MAY
 SUBMIT FLAT ROOF PRODUCT APPROVAL AND RAS 117
 CALCULATIONS WHEN APPLYING FOR ROOFING SUB-PERMIT. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-04-29 Cont ID  
Sent By jgomez Date 2015-04-29 Time 18:34 Rev Time 0.00
Received By jgomez Date 2015-04-29 Time 18:34 Sent To  
Notes
2015-04-29 18:34:521- CLAY TILE NOA 12-0529.12.
 2- ROOF TILE ADHESIVE NOA 12-0228.18.
 3- TAMKO MODIFIED BITUMEN ROOF SYSTEM NOA 12-0716.18.
 4- REVISE RAS 117 CALCULATIONS. SEE BUILDING PROVISO
 BELOW:
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE RAS 117 CALCULATIONS: ARCHITECTURAL PLANS AND
 NOA 12-0716.18 SUBMITTED CALL FOR INSULATED ROOF DECK.
 CALCULATIONS SUBMITTED ARE FOR A NON INSULATED
 ASSEMBLY. REVISE AS REQUIRED TO MATCH..
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-03-06 Cont ID  
Sent By jgomez Date 2015-03-06 Time 08:35 Rev Time 0.00
Received By jgomez Date 2015-03-06 Time 08:15 Sent To  
Notes
2015-03-06 08:37:341- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF TILE ADHESIVE. NOA 12-0228.18 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA.
  
 B) TAMKO MODIFIED BITUMEN ROOF SYSTEM NOA 12-0716.18
 WAS SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA.
  
 2- DESIGNER OF RECORD TO APPROVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
 NOTE: PLEASE STAMP REVIEW STAMP ON FRONT OF PRODUCT
 APPROVAL PAGE NOT ON THE BACK. THIS IS REQUIRED FOR THE
 PROPER RECORDS RETENTION SCANNING PROCESS.
  
 3- CLAY TILE NOA 12-0529.12 SUBMITTED DOESN'T SHOW ANY
 FASTENING SYSTEM USING #10 SCREWS. ARCHITECT TO REVISE
 ALL DETAILS AND SPECIFICATIONS ON PLANS TO MATCH
 PRODUCT APPROVAL OR PROVIDE A DIFFERENT CLAY TILE NOA
 THAT ALLOWS NAILS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
 AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 4- TAMKO MODIFIED BITUMEN ROOF SYSTEM: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 OF TAMKO NOA SUBMITTED. CALCULATIONS
 REQUIRED TO MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301 OF 2010 FBC-RESIDENTIAL.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-26 Cont ID  
Sent By fmittner Date 2015-05-26 Time 11:21 Rev Time 0.00
Received By fmittner Date 2015-05-26 Time 11:21 Sent To  
Notes
2015-04-29 14:50:10NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By fmittner Date 2015-02-04 Time 11:26 Rev Time 0.00
Received By fmittner Date 2015-02-04 Time 11:26 Sent To  
Notes
2015-02-02 16:14:032/2/15


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved