Plan Review Details - Permit 15010859
Plan Review Stops For Permit 15010859
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-28 Cont ID  
Sent By tklarge Date 2015-02-28 Time 03:50 Rev Time 0.00
Received By tklarge Date 2015-02-27 Time 14:50 Sent To  
Notes
2015-02-27 14:50:51SENT TO T LARGE

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-28 Cont ID  
Sent By tklarge Date 2015-02-28 Time 03:50 Rev Time 0.00
Received By tklarge Date 2015-02-28 Time 03:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-27 Cont ID  
Sent By tklarge Date 2015-01-27 Time 08:55 Rev Time 0.00
Received By tklarge Date 2015-01-27 Time 05:04 Sent To  
Notes
2015-01-27 05:28:321) SUBMIT COPY OF THE MAINTENANCE AGREEMENT FOR THE
 EMPTYING OF THE HOLDING TANKS TO ENSURE THE TANKS WILL
 BE MAINTAINED IN A SANITARY CONDITION.2010 FPC SEC.311,
 WPB AMEND. TO 2010 FBC SEC.107.2.1.
 2) INDICATE THE CAPACITY (IN GALLONS) OF BOTH TANKS ON
 THE PLANS. A PERMIT MAY BE REQUIRED FROM THE PALM BEACH
 COUNTY HEALTH DEPT. FOR THE TANKS.
 3) SUBMIT MANUF. SPEC. SHEETS FOR THE BACKFLOW
 PREVENTION DEVICE. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 4) ALL HOSE BIBBS SHALL BE SEPARATELY VALVED PER 2010
 FPC SEC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
2015-01-26 10:52:34ROUTED TO PLUMBING LESS THAN $5K