Plan Review Stops For Permit 15010851
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-02-06 Cont ID  
Sent By jwitmer Date 2015-02-06 Time 06:15 Rev Time  
Received By jwitmer Date 2015-02-05 Time   Sent To  
Notes
2015-02-05 17:58:31BUILDING PLAN REVIEW
 PERMIT: 15010851
 ADD: 1022 18TH ST.
 CONT: SYNERGY DESIGN DESIGN- BUILD
 TEL: (352)562-5054
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. FEB. 05/ 2015
 ACTION: RECOMMENDATION
  
 1) THE DESIGNER OF RECORD HAS NOT DECLAIRED TO WHAT
 LEVEL OF ALTERATION THE WORK UNDER THIS PERMIT IS TO BE
 COMPLETED. WITH THE LIMITED INFORMATION PROVIDED WE ARE
 REVIEWING THIS PERMIT AS A LEVEL 1 ALTERATION. 604.1
 GENERAL. MEANS OF EGRESS FOR BUILDINGS UNDERGOING
 ALTERATION SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 601.1 AND THE SCOPING PROVISIONS OF CHAPTER 1
 WHERE APPLICABLE.
  
 RECOMMENDATION ONLY, THE DOUBLE DOORS LABELED # 2 SWING
 AGAINST THE EGRESS PATH (2010 FBC-B 1008.1.2), WITH
 OCCUPANT LOADS GREATER THAN 50 THE DOORS SHALL SWING IN
 THE DIRECTION OF EGRESS TRAVEL. THE RECOMMENDATION IS
 TO REMOVE THE DOORS OR PUT THESE DOORS ON DOUBLE ACTING
 HINGES SO THEY WILL NOT IMPEDE ACCESS TO THE RESTROOMS.
  
 NOTE IT IS ASSUMED THE WINDOWS ARE GOING TO BE
 INSTALLED WITHIN THE SAME OPENING. IF THE SIZES CHANGE
 THEN THIS BECOMES A LEVEL 2 ALTERATION, AND
 SECTION 2010 EXISTING BUILDING CODE LEVEL II 701.3
 BECOMES ACTIVE. COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2010 EXISTING BUILDING CODE LEVEL 2. 705.2 EXCEPTION 2:
 MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA FIRE
 PREVENTION CODE UNDER WHICH THE BUILDING WAS
 CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF
 EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO LIFE. WE BELIEVE
 THIS IS A DISTINCT HAZARD TO LIFE.
  
 THIS BUILDING WAS BUILT IN 1948 AND WAS UNDER THE
 BUILDING CODE CITY OF WEST PALM BEACH 1947. SECTION
 603. EXIT FACILITIES.(I) DOORS & GATES. ALL EXIT AND
 ENTRANCE DOORS OR GATES SHALL SWING IN THE DIRECTION OF
 EXIT TRAVEL AND IF PROVIDED WITH LATCHES SUCH LATCHES
 SHALL BE OF SELF -RELEASING TYPE, SUCH AS PANIC BOLTS
 OR SIMILAR DEVICES, WHICH WILL PERMIT THE DOORS TO OPEN
 WHEN PRESSED AGAINST.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 BUILDING PROVISO:
 SHEET A1.0
 2010 FBC-B 1008.1.9.3 LOCKS AND LATCHES.
 APPROVED LOCKS AND LATCHES SHALL BE PERMITTED TO
 PREVENT OPERATION OF DOORS WHERE ANY OF THE FOLLOWING
 EXISTS:
  
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR
 (MAIN EXIT) OR DOORS ARE PERMITTED TO BE EQUIPPED WITH
 KEY-OPERATED LOCKING DEVICES FROM THE EGRESS SIDE
 PROVIDED:
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOCABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 NOTE: DOORS IDENTIFIED # 4 WILL NEED PANIC HARDWARE,
 NOT THE MAIN EXTERIOR ENTRY DOOR.
 2010 FBC-B
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 EXCEPTIONS: 1. A MAIN EXIT OF A GROUP A OCCUPANCY IN
 COMPLIANCE WITH SECTION 1008.1.9.3, ITEM 2.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-03 Cont ID  
Sent By sciard Date 2015-03-03 Time 13:22 Rev Time 0.00
Received By sciard Date 2015-03-03 Time 13:22 Sent To  
Notes
2015-03-03 13:23:47PROVIDE PANEL SCHEDULE AND LOAD CALCULATION FOR ROUGH
 OR FINAL FOR INSPECTOR AS PREVIOUSLY NOTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By sciard Date 2015-02-10 Time 14:03 Rev Time 0.00
Received By sciard Date 2015-02-10 Time 14:03 Sent To  
Notes
2015-02-10 14:09:451. FBC 107.3.5.3. PROVIDE SERVICE RISER DIAGRAM, TO
 INCLUDE RACEWAY SIZE, GROUNDING DETAIL, LOAD
 CALCULATIONS, PANEL SCHEDULE ETC.( AS NOTED ON WORK
 NARRATIVE #1)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-02-05 Time   Rev Time 0.00
Received By pleduc Date 2015-01-29 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-18 Cont ID  
Sent By skennedy Date 2015-03-18 Time 11:13 Rev Time 0.00
Received By skennedy Date 2015-01-23 Time 17:05 Sent To  
Notes
2015-01-27 17:07:57B02
  
2015-01-23 16:23:01PLANS ROUTED TO BUILDING, CONTRACTOR NOT REGISTERED IN
 SYSTEM. PERMIT APP PLACED UNDER TBD UNTIL REGISTRATION
 COMPLETED NSD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-03-18 Cont ID  
Sent By skennedy Date 2015-03-18 Time 11:13 Rev Time  
Received By skennedy Date   Time   Sent To  
Notes
2015-03-18 11:13:38SEPARATE PERMIT ISSUED.