Plan Review Details - Permit 15010836
Plan Review Stops For Permit 15010836
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-24 Cont ID  
Sent By jwitmer Date 2015-07-24 Time 11:10 Rev Time 0.00
Received By jwitmer Date 2015-07-24 Time   Sent To  
Notes
2015-06-19 14:42:34B28

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-07 Cont ID  
Sent By jwitmer Date 2015-02-07 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2015-02-06 Time 05:42 Sent To  
Notes
2015-02-07 08:34:06BUILDING PLAN REVIEW
 PERMIT: 15010836
 ADD: 5300 GEORGIA AVE.
 CONT: H. CANO INC.
 TEL: (561)586-2212
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. FEB. 07/ 2015
 ACTION: DENIED
  
 1) THE CONTRACTOR HAS MIS-REPRESENTED THE SCOPE OF WORK
 UNDER THIS PROJECT. THERE ARE CURRENTLY 4 CODE CASES
 GOING ANGAINST THIS PROPERTY. SOFT HOLDS FLAG THIS
 PREOPERTY, THE PHOTOGRAPHS FROM THE SITE VISIT FROM THE
 CODE, FIRE AND BUILDING INSPECTORS SHOW VARIOUS
 VIOLATIONS FOR THE INTERIOR AS WELL AS ON THE EXTERIOR
 OF THE PROPERTY.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
 INSUFFIENT INFORMATION PROVIDED FOR A MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS:
  
 107.3.5.1 COMMERCIAL BUILDINGS: THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA
 107.3.5.1.1 BUILDING 1.1) FLOOR PLAN FOR THE TOTAL AREA
 INSIDE THE BUILDING, DESIGNATE AREAS OF WORK AND AREAS
 WHERE CHANGE OF OCCUPANCY HAS OCURRED, ( COOKING AREAS
 & NEW BUSINESS OCCUPANCIES)
  
 1.2) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED. AMOUNTS OF BOTTLED GASSES STORED
 ON THE INTERIOR AND OR EXTERIOR
 OF THE BUILDING.
  
 1.3) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 1.4) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
  
 1.5) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
 SPECIAL OCCUPANCY REQUIREMENTS
  
 1.6) INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 2) THE DESIGNER OF RECORD HAS NOT DECLARED TO WHICH
 METHOD THEY HAVE DESIGNED UNDER THE 2010 FBC-EISTING
 BUILDING CODE:
  
 EXST. BLDG. CODE101.4.2 BUILDINGS PREVIOUSLY OCCUPIED.
 THE LEGAL OCCUPANCY OF ANY BUILDING EXISTING ON THE
 DATE OF ADOPTION OF THIS CODE SHALL BE PERMITTED TO
 CONTINUE WITHOUT CHANGE, EXCEPT AS IS SPECIFICALLY
 COVERED IN THIS CODE, THE FLORIDA FIRE PREVENTION CODE,
 OR AS IS DEEMED NECESSARY BY THE CODE OFFICIAL FOR THE
 GENERAL SAFETY AND WELFARE OF THE OCCUPANTS AND THE
 PUBLIC.
  
 EXST. BLDG. CODE 101.5 COMPLIANCE METHODS. THE REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE
 METHODS LISTED IN SECTIONS 101.5.1 THROUGH 101.5.3 AS
 SELECTED BY THE APPLICANT.
  
 3) FOR THE TRUE AMOUNT OF WORK TO MAKE THIS BUILDING
 CODE COMPLIANT, AND WORK COMPLETED WITH OUT A PERMIT,
 AND THE CHANGE OF OCCUPANCIES THAT HAS OCCURRED, THE
 VALUE OF WORK IS TO LOW;
  
 3A) PERMIT FEES TO BE UPGRADED TO REFLECT THE AMOUNT OF
 WORK TO BE COMPLETED TO RESOLVE THE CODE CASES : W P B
 ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON
 BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND
 PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A
 FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3B) THE VALUE OF WORK WILL ACCEDE $25,000.00 DOLLORS
 THAT WILL MAKE IT NECCESSARY FOR A DESIGN PROFESSIONAL
 TO DESIGN THE PLANS AND NOT A CONTRACTOR. FL. S.
 481.229(C).
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-29 Cont ID  
Sent By albarran Date 2015-07-29 Time 16:40 Rev Time 0.00
Received By albarran Date 2015-07-29 Time 16:15 Sent To  
Notes
2015-07-29 16:37:56MR. MOLINA CALLED TO INQUIRE ON HIS PERMIT'S ELECTRICAL
 COMMENTS. HE TOLD ME THAT THERE IS NO ELECTRICAL WORK
 BEING DONE, AND THAT THE LIGHT REQUESTED BY THE FIRE
 MARSHAL IS ALREADY THERE JUST NOT SHOWN ON THE PLANS. I
 WILL THEN APPROVE THE PERMIT WITH A "NO ELECTRIC THIS
 PERMIT PROVISO".

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-29 Cont ID  
Sent By albarran Date 2015-06-29 Time 17:16 Rev Time 0.00
Received By albarran Date 2015-06-29 Time 17:11 Sent To B
Notes
2015-06-29 17:18:20IN ADDITION TO THE PREVIOUSLY REQUESTED ELECTRICAL
 INFORMATION, YOU SHALL CLEARLY DEFINE YOUR SCOPE OF
 WORK TO INCLUDE ANY AND ALL ELECTRICAL WORK BEING DONE,
 IN ADDITION TO THE REQUIRED EMERGENCY LIGHT IN THE
 FREEZER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-12 Cont ID  
Sent By rlecky Date 2015-02-12 Time 14:26 Rev Time 0.00
Received By rlecky Date 2015-02-12 Time 14:17 Sent To  
Notes
2015-02-12 14:28:3015010836
 5300 GEORGIA AVE.
 INTERIOR RENOVATIONS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL PLAN FOR THE RENOVATIONS
 PROPOSED. NEC 110.2, 110.26, 215.5
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-22 Cont ID  
Sent By Lindow Date 2015-06-22 Time   Rev Time 0.00
Received By   Date 2015-06-22 Time   Sent To E
Notes
2015-06-22 14:45:14ADD EMERGENCY LIGHTING AS NOTED ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-02-05 Time   Rev Time 0.00
Received By pleduc Date 2015-01-29 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-29 Cont ID  
Sent By albarran Date 2015-07-29 Time 18:04 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-07-29 18:07:327/29/15 - AFTER A CONVERSATION W/MR. MOLINA THIS PERMIT
 WAS APPROVED W/O ANY ELECTRIC AS NOTED ON PLANS.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN
 "C". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-29 Cont ID  
Sent By llouie Date 2015-07-29 Time 14:35 Rev Time 0.00
Received By llouie Date 2015-06-19 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-21 Cont ID  
Sent By hmoser Date 2015-03-21 Time 09:33 Rev Time  
Received By hmoser Date 2015-01-23 Time   Sent To  
Notes
2015-01-24 09:57:54SENT TO B-12.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-01-27 Cont ID  
Sent By   Date 2015-01-27 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2015-01-27 Time 08:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-03-21 Cont ID  
Sent By hmoser Date 2015-03-21 Time 09:32 Rev Time 0.00
Received By hmoser Date 2015-03-21 Time 09:32 Sent To  
Notes
2015-03-21 09:33:21NO MECHANICAL AT THIS TIME. HM

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-07-25 Cont ID  
Sent By tklarge Date 2015-07-25 Time 10:32 Rev Time 0.00
Received By tklarge Date 2015-07-25 Time 10:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-02-09 Cont ID  
Sent By tklarge Date 2015-02-09 Time 08:56 Rev Time 0.00
Received By tklarge Date 2015-02-09 Time 08:30 Sent To  
Notes
2015-02-09 08:56:471) SUBMIT A COMPLETE SET OF PLANS FOR REVIEW. INDICATE
 ON THE PLANS IF ANY CHANGES OR ALTERATIONS ARE GOING TO
 BE MADE TO THE PLUMBING SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-29 Cont ID  
Sent By llouie Date 2015-07-29 Time   Rev Time 0.00
Received By llouie Date 2015-07-29 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By llouie Date 2015-02-10 Time   Rev Time 0.00
Received By llouie Date 2015-02-09 Time 08:44 Sent To  
Notes
2015-02-10 08:45:30** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE CONTRACTOR HAS MIS-REPRESENTED THE SCOPE OF
 WORK UNDER THIS PROJECT. EXISTING CODE CASES CITE
 INTERIOR AND EXTERIOR VIOLATIONS ON THE PROPERTY.
 FURTHER INSPECTIONS AND/OR MODIFIED SCOPE OF WORK AND
 ADDITIONAL MATERIAL NEEDED TO ADDRESS THE ISSUES.
  
 2.) REVIEW OF SUBMITTED PLANS FOUND INSUFFICIENT. NEED
 COMPLETE SET OF PLANS TO DETERMINE COMPLETE SCOPE OF
 WORK IN THE INTERIOR OF THE BUILDING: FLOOR PLANS
 SHOULD DEPICT TOTAL BUILDING AREA AND DESIGNATED AREA
 OF WORK AND WHERE CHANGE OF OCCUPANCY HAS OCCURRED.
  
 3.) SITE PLAN OF THE PROPERTY IS REQUIRED TO ASSESS
 PLACEMENT AND SCREENING OF OUTDOOR STORAGE, PARKING AND
 ACCESSIBILITY ON THE PROPERTY.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
  
  
  
  
  