Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-05-06 Cont ID  
Sent By jwitmer Date 2015-05-06 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2015-05-06 Time 08:30 Sent To  
Notes
2015-05-06 11:01:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15010789
 ADD: 2600 BROADWAY
 CONT: MVP CONTRACTORS
 TEL: (954)214-0226
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. MAY 06/2015
 ACTION: DENIED
  
 NOTE: CONTRACTOR BROUGHT IN A 2ND SET OF PLANS TODAY
 05/06/2015.
  
 1) 3RD REQUEST SEMI-COMPLIED.
 1A) THE SUBMITTED PRODUCT APPROVALS HAVE NOT IDENTIFIED
 (CIRCLE) THE SIZE OF THE WINDOWS AND MULLIONS, TYPE OF
 GLAZING, TYPE OF ANCHORS AND ASSOCIATED PRESSURES.
 SHEET 5 OF63 SHOWS NEW WINDOW OPENINGS AND PARAPET IN
 THE ELEVATION VIEWS. ON THE LOWER LEFT CORNER OF THE
 SHEET WINDOW TYPE 1-3 ARE IDENTIFIED. WINDOWS 1 & 2 ARE
 SHOWN ON THE PLANS AS FIXED GLASS.
  
 1B) IN THE PRODUCT APPROVAL THERE ARE 8 TYPES OF
 GLAZING FOUND ON 7 TABLES PLEASE IDENTIFY THE TYPE OF
 GLAZING TO BE INSTALLED WITH THE APPROPRIATE PRESSURES.
  
 1C) WINDOW # 3 IS INDICATED TO BE A SINGLE HUNG WINDOW,
 NOT IDENTIFIED ON THE ELEVATION VIEW. THERE WAS A
 PRODUCT APPROVAL SUBMITTED FOR A SINGLE HUNG TYPE
 WINDOW.
  
 1D) COMPLIED. SUBMITTED PRODUCT APPROVALS HAVE BEEN
 REVIEWED BY THE DESIGNER OF RECORD.
  
 2) COMPLIED.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) COMPLIED.
 4-7) COMPLIED
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-03 Cont ID  
Sent By jwitmer Date 2015-04-03 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2015-04-03 Time 07:18 Sent To  
Notes
2015-04-03 08:09:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15010789
 ADD: 2600 BROADWAY
 CONT: MVP CONTRACTORS
 TEL: (954)214-0226
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. APRIL 03/2015
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1)2ND REQUEST SEMI-COMPLIED. THE SUBMITTED PRODUCT
 APPROVALS HAVE NOT IDENTIFIED THE SIZE OF THE WINDOWS
 AND MULLIONS, TYPE OF GLAZING, TYPE OF ANCHORS AND
 ASSOCIATED PRESSURES. SHEET 1 OF 3 SHOWS NEW WINDOW
 OPENINGS AND PARAPET IN THE ELEVATION VIEWS. PLEASE
 SHOW COMPLIANCE WITH 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS/ MULLIONS
  
 2) COMPLIED.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3A) 2ND REQUEST.
 THE PLANS DO NOT PROVIDE THE EXPOSURE CLASSIFICATION,
 THE ENGINEERING CALCS ARE FOR A B EXPOSURE. THE OTHER
 ISSUE WITH THE PROVIDED WIND DESIGN IS FOR THE MAIN
 WIND FORCE RESISSTING SYSTEM TAKEN FROM ASCE 7-10
 CHAPTER 27. COMPONENTS AND CLADDING ARE TAKEN FROM
 CHAPTER 30. SEE SECTIONS 26.7.4.2 IS FOR THE MAIN WIND
 FORCE RESISTING SYSTEM& 26.7.4.4. IS FOR COMPONENTS AND
 CLADDING.
 THERE ARE NO PRESSURES FOR THE WALL ZONES 4 & 5, ONLY
 THE PARAPET.
  
 WIND DESIGN CRITERIA IS PARTIALLY PROVIDED :
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10 THE 170 MPH VULT
 IS PROVIDED.
  
 3.2) NOT PROVIDED, AN IMPORTANCE FACTOR, FIGURE 1609
 A-C, ASCE 7-10.
  
 3.3) NOT PROVIDED. AN EXPOSURE CATEGORY SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) NOT PROVIDED. A HEIGHT AND EXPOSURE ADJUSTMENT
 COEFFICIENT, * SHALL BE DETERMINED FROM TABLE 1609.7.2.
 ASCE 7-10.
  
 3.5) NOT PROVIDED. COMPONENTS & CLADDING PRESSURES
 POSITIVE & NEGATIVE TABLE 1609.2(2) .
  
 3B) THE PRODUCT APPROVALS PRESSURES ARE SHOWN AS VASD,
 PLEASE PROVIDE PRESSURES IN VASD TO COINCIDE WITH THE
 PRODUCT APPROVALS. FOR ZONES 1-5. 2010 FBC-B 1609.1
 WIND SPEED CONVERSION.
 1609.1.5 TESTING TO ALLOWABLE OR NOMINAL LOADS. WHERE
 TESTING FOR WIND LOAD RESISTANCE IS BASED ON ALLOWABLE
 OR NOMINAL WIND LOADS, THE DESIGN WIND LOADS DETERMINED
 IN ACCORDANCE WITH ASCE 7 OR SECTION 1609 ARE PERMITTED
 TO BE MULTIPLIED BY 0.6 FOR THE PURPOSES OF THE WIND
 LOAD RESISTANCE TESTING.
  
 4-7) COMPLIED
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-09 Cont ID  
Sent By jwitmer Date 2015-03-09 Time   Rev Time  
Received By jwitmer Date 2015-03-09 Time 07:01 Sent To  
Notes
2015-03-09 07:35:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15010789
 ADD: 2600 BROADWAY
 CONT: MVP CONTRACTORS
 TEL: (954)214-0226
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. 09/2015
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1) SHEET 1 OF 3 SHOWS NEW WINDOW OPENINGS AND PARAPET
 IN THE ELEVATION VIEWS. PLEASE SHOW COMPLIANCE WITH
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS/ MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, LINTELS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS IF NON-IMPACT TESTED WINDOWS ARE INSTALLED
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3A) WIND DESIGN CRITERIA IS PARTIALLY PROVIDED :
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10 THE 170 MPH VULT
 IS PROVIDED.
  
 3.2) NOT PROVIDED, AN IMPORTANCE FACTOR, FIGURE 1609
 A-C, ASCE 7-10.
  
 3.3) NOT PROVIDED. AN EXPOSURE CATEGORY SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) NOT PROVIDED. A HEIGHT AND EXPOSURE ADJUSTMENT
 COEFFICIENT, * SHALL BE DETERMINED FROM TABLE 1609.7.2.
 ASCE 7-10.
  
 3.5) NOT PROVIDED. COMPONENTS & CLADDING PRESSURES
 POSITIVE & NEGATIVE TABLE 1609.2(2) .
  
 3B) THE PRODUCT APPROVALS PRESSURES ARE SHOWN AS VASD,
 PLEASE PROVIDE PRESSURES IN VASD TO COINCIDE WITH THE
 PRODUCT APPROVALS. FOR ZONES 1-5. 2010 FBC-B 1609.1
 WIND SPEED CONVERSION.
 1609.1.5 TESTING TO ALLOWABLE OR NOMINAL LOADS. WHERE
 TESTING FOR WIND LOAD RESISTANCE IS BASED ON ALLOWABLE
 OR NOMINAL WIND LOADS, THE DESIGN WIND LOADS DETERMINED
 IN ACCORDANCE WITH ASCE 7 OR SECTION 1609 ARE PERMITTED
 TO BE MULTIPLIED BY 0.6 FOR THE PURPOSES OF THE WIND
 LOAD RESISTANCE TESTING.
  
 4) SHEET 3 OF 3 DOES NOT SHOW IN DETAIL CUT SECTION OF
 PARAPET THE FASTENING SCHEDULE FOR EITHER THE ROCK
 BOARD, THE 5/8 INCH PLYWOOD, NOR THE METAL STUD TO THE
 EXISTING PIERS.
 THE PLANS ALSO INDICATE THE USE OF WIRE LATH OVER THE
 ROCK BOARD BUT NO MENTION OF THE TYPE OF WIRE LATH NOR
 THE GAUGE OF THE WIRE LATH NOR THE FASTENING SCHEDULE,
 SPACING OR TYPE OF FASTENER TO BE USED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 ADDITIONAL
 INFORMATION IS REQUIRED. CONSTRUCTION DOCUMENTS SHALL
 BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 5) THE PLANS DO NOT INDICATE THE TRANSITION FROM THE
 ROOF DECK TO PARAPET PLEASE PROVIDE COMPLIANCE WITH :
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 6) SHEET 3 DETAIL A/3 SHOWS THE NEW VERTICAL # 5 REBAR,
 THERE IS NO INFORMATION HOW THE NEW REBAR IS TO BE
 ATTACHED TO THE BEAM ABOVE OR THE FOUNDATION BELOW TO
 BECOME PART OF THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM).
  
 7) SHEET 2 DETAIL A/3 ALSO DOES NOT PROVIDE THE LOADING
 ON THE LINTEL/ FT, IF THERE IS ADDITIONAL REQUIREMENTS
 OF THE LINTEL.
 2104.1.5 LINTELS. THE DESIGN FOR LINTELS SHALL BE IN
 ACCORDANCE WITH THE MASONRY DESIGN PROVISIONS OF EITHER
 SECTION 2107 OR 2108.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-06-11 Cont ID  
Sent By dhayes Date 2015-06-11 Time 15:30 Rev Time 0.00
Received By dhayes Date 2015-06-11 Time 15:29 Sent To  
Notes
2015-06-11 15:31:08APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 422.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-19 Cont ID  
Sent By rlecky Date 2015-05-19 Time 12:48 Rev Time 0.00
Received By rlecky Date 2015-05-19 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-05 Cont ID  
Sent By rlecky Date 2015-05-05 Time 11:59 Rev Time 0.00
Received By rlecky Date 2015-05-05 Time 11:35 Sent To  
Notes
2015-05-05 12:00:03ONLY ONE NEW SET OF PLANS IN THE SUBMITTAL. RL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By rlecky Date 2015-04-28 Time 12:37 Rev Time 0.00
Received By rlecky Date 2015-04-28 Time 12:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-05-19 Cont ID  
Sent By pleduc Date 2015-05-19 Time   Rev Time 0.00
Received By pleduc Date 2015-05-19 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-04 Cont ID  
Sent By pleduc Date 2015-05-04 Time   Rev Time 0.00
Received By pleduc Date 2015-05-04 Time 16:01 Sent To  
Notes
2015-05-04 16:12:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ONLY ONE SET OF PLANS WAS RESUBMITTED AND IT WAS
 STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-27 Cont ID  
Sent By pleduc Date 2015-03-27 Time   Rev Time 0.00
Received By pleduc Date 2015-03-27 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-11 Cont ID  
Sent By dhayes Date 2015-06-11 Time 15:34 Rev Time 0.00
Received By dhayes Date 2015-06-08 Time 16:23 Sent To  
Notes
2015-06-09 16:10:36TO TL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-30 Cont ID  
Sent By   Date 2015-05-30 Time   Rev Time 0.00
Received By dhayes Date 2015-04-29 Time 07:28 Sent To  
Notes
2015-04-30 07:28:46B15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-28 Cont ID  
Sent By rlecky Date 2015-04-28 Time 12:37 Rev Time 0.00
Received By rlecky Date 2015-03-24 Time 08:56 Sent To  
Notes
2015-03-25 08:56:56RE-SUBMITTAL SENT TO B5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-09 Cont ID  
Sent By   Date 2015-03-09 Time   Rev Time 0.00
Received By rmcdouga Date 2015-01-22 Time 13:51 Sent To  
Notes
2015-01-23 13:51:51SENT TO ZONING

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-06-10 Cont ID  
Sent By tklarge Date 2015-06-10 Time 05:10 Rev Time 0.00
Received By tklarge Date 2015-06-10 Time 04:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-06-08 Cont ID  
Sent By tklarge Date 2015-06-08 Time 10:22 Rev Time 0.00
Received By tklarge Date 2015-06-08 Time 10:07 Sent To  
Notes
2015-06-08 10:22:421) THE PLAN DOES NOT SHOW AN EXISTING DRINKING FOUNTAIN
 IN THIS BUILDING.THIS ITEM WAS OVERLOOKED IN THE FIRST
 REVIEW. A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY AND HAS BEEN FOR QUITE A FEW CODE EDITION
 CYCLES.IF THE UNIT DOES NOT HAVE A DRINKING FOUNTAIN,
 THIS WOULD BE THE TIME TO INSTALL ONE. PROVIDE A HI-LO
 HANDICAPPPED ACCESSIBLE DRINKING FOUNTAIN FOR THIS
 OCCUPANCY IF ONE IS NOT CURRENTLY INSTALLED. SHOW THE
 DRINKING FOUNTAIN ON THE SANITARY AND WATER RISER IF IT
 IS TO BE NEW.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-30 Cont ID  
Sent By j.witmer Date 2015-05-30 Time 11:37 Rev Time 0.00
Received By tklarge Date 2015-05-30 Time 11:07 Sent To B
Notes
2015-06-03 12:23:38ROUTED TO J. WITMER'S DESK FOR BUILDING REVIEW.
  
  
  
2015-05-30 11:37:231) THE PLAN DOES NOT SHOW AN EXISTING DRINKING FOUNTAIN
 IN THIS BUILDING.THIS ITEM WAS OVERLOOKED IN THE FIRST
 REVIEW. A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY AND HAS BEEN FOR QUITE A FEW CODE EDITION
 CYCLES.IF THE UNIT DOES NOT HAVE A DRINKING FOUNTAIN,
 THIS WOULD BE THE TIME TO INSTALL ONE. PROVIDE A HI-LO
 HANDICAPPPED ACCESSIBLE DRINKING FOUNTAIN FOR THIS
 OCCUPANCY IF ONE IS NOT CURRENTLY INSTALLED. SHOW THE
 DRINKING FOUNTAIN ON THE SANITARY AND WATER RISER IF IT
 IS TO BE NEW.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-18 Cont ID  
Sent By tklarge Date 2015-04-18 Time 10:13 Rev Time 0.00
Received By tklarge Date 2015-04-18 Time 10:04 Sent To  
Notes
2015-04-18 09:57:30SUBMIT A SANITARY AND WATER RISER FOR THE RELOCATION OF
 THE TOILET ROOM. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-05-27 Cont ID  
Sent By sgraham Date 2015-05-27 Time 16:21 Rev Time 0.00
Received By sgraham Date 2015-05-27 Time 16:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-16 Cont ID  
Sent By sgraham Date 2015-04-16 Time 12:33 Rev Time 0.00
Received By sgraham Date 2015-04-16 Time 12:32 Sent To B
Notes
2015-03-25 08:56:03NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By sgraham Date 2015-01-26 Time 11:40 Rev Time 0.00
Received By sgraham Date 2015-01-26 Time 11:40 Sent To B
Notes
2015-01-26 11:42:151/26/15 ZONING APPROVED WITH A PROVISO FOR THE NEW
 WINDOWS OPENING, NEW WINDOWS MUST BE RECESSED A MINIMUN
 OF 2" FROM THE EXTERIOR FACE OF THE FACADE.