| 2015-02-26 16:57:09 | 2/26/2015 |
| | PROJECT: GENERATOR |
| | PERMIT#: 15010788 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE SUBJECT PROPERTY IS LOCATED IN A FLOOD ZONE. |
| | PROVIDE AN ELEVATION CERTIFICATE OR OTHER APPROVED |
| | EVIDENCE THAT THE PROJECT SITE MEETS THE REQUIRED ONE |
| | FT FREEBOARD. FBC 1612.4 |
| | |
| | 2) REVISE RISER DIAGRAM TO INCLUDE CONDUIT AND WIRE |
| | SIZES FOR FEEDERS. |
| | |
| | 3) REVISE THE RISER DIAGRAM TO INCLUDE THE CORRECT |
| | SYSTEM VOLTAGE ON BOTH THE UTILITY AND THE GENERATOR. |
| | IT APPEARS BY THE EQUIPMENT SUBMITTALS THE SYSTEM |
| | VOLTAGE IS PROVIDED AT 277/480 HOWEVER THE RISER DIARAM |
| | ILLUSTRATES A SYSTEM VOLTAGE OF 120/208 AT THE SERVICE |
| | UTILITY. CLARIFY FOR CONSISTANCY. |
| | |
| | 4) CHECK THE APPROPRIATE BOXES IN THE EQUIPMENT |
| | SUBMITTALS TO INDICATE THE ACTUAL MODEL NUMBER, SYSTEM |
| | VOLTAGE ETC.. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |