Plan Review Details - Permit 15010788
Plan Review Stops For Permit 15010788
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-10 Cont ID  
Sent By shill Date 2015-03-10 Time 13:06 Rev Time 0.00
Received By shill Date 2015-03-10 Time 13:06 Sent To  
Notes
2015-03-20 10:11:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE AN ENGINEERED STRUCTURAL DETAIL FOR PROPOSED
 INSTALLATION. FBC 1604.9, FBC1609. THIS IS TO INCLUDE
 WIND DESIGN CRITERIA INCLUDING RISK FACTOR.
  
 2. FBC 1603.1.7, INCLUDE THE INFORMATION REQUIRED FOR
 FLOOD DESIGN DATA. SEE ASCE 24 REGARDING FREEBOARD
 REQUIREMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By dhayes Date 2015-02-26 Time 16:45 Rev Time 0.00
Received By dhayes Date 2015-02-26 Time 16:45 Sent To  
Notes
2015-02-26 16:57:092/26/2015
 PROJECT: GENERATOR
 PERMIT#: 15010788
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE SUBJECT PROPERTY IS LOCATED IN A FLOOD ZONE.
 PROVIDE AN ELEVATION CERTIFICATE OR OTHER APPROVED
 EVIDENCE THAT THE PROJECT SITE MEETS THE REQUIRED ONE
 FT FREEBOARD. FBC 1612.4
  
 2) REVISE RISER DIAGRAM TO INCLUDE CONDUIT AND WIRE
 SIZES FOR FEEDERS.
  
 3) REVISE THE RISER DIAGRAM TO INCLUDE THE CORRECT
 SYSTEM VOLTAGE ON BOTH THE UTILITY AND THE GENERATOR.
 IT APPEARS BY THE EQUIPMENT SUBMITTALS THE SYSTEM
 VOLTAGE IS PROVIDED AT 277/480 HOWEVER THE RISER DIARAM
 ILLUSTRATES A SYSTEM VOLTAGE OF 120/208 AT THE SERVICE
 UTILITY. CLARIFY FOR CONSISTANCY.
  
 4) CHECK THE APPROPRIATE BOXES IN THE EQUIPMENT
 SUBMITTALS TO INDICATE THE ACTUAL MODEL NUMBER, SYSTEM
 VOLTAGE ETC..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-30 Cont ID  
Sent By pleduc Date 2015-01-30 Time   Rev Time 0.00
Received By pleduc Date 2015-01-30 Time 11:29 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-10 Cont ID  
Sent By shill Date 2015-03-10 Time 13:15 Rev Time 0.00
Received By shill Date 2015-01-22 Time 13:35 Sent To  
Notes
2015-02-26 18:03:302/26 TO SH DESK
  
2015-01-23 13:37:08SENT TO ZONING
2015-01-22 13:01:06ROUTED TO ELECTRICAL GREATER THAN $5K NSD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By hmoser Date 2015-02-26 Time 17:59 Rev Time 0.00
Received By hmoser Date 2015-02-26 Time 17:37 Sent To B
Notes
2015-02-26 17:59:16PLAN DENIED
 1) PROVIDE A FUEL PIPING PLAN FROM SECONDARY FUEL TANK
 TO GENERATOR
 PER SECTION 107 FBC 2010
 2) PROVIDE THE SIZE OF THE SECONDARY FUEL TANK ON THE
 PLAN
 SUBMIT THE PLAN TO PALM BEACH COUNTY DERM BE FOR
 SUBMITTING IT TO
 THE CITY FOR REVIEW.
 3) PROVIDE A PLAN SHOWING SIZE AND LOCATION OF THE
 EXHAUST FROM THE
 GENERATOR AND THE TERMINATION OF THE EXHAUST.
 4) REFER TO SECTION 1305.2.1 FLOOD HAZARD FLOOD
 ELEVATION IS 14.5 FT
 FLOOD ZONE IS A 8
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-01-23 Cont ID  
Sent By sgraham Date 2015-01-23 Time 15:45 Rev Time 0.00
Received By sgraham Date 2015-01-23 Time 15:45 Sent To B
Notes
***NONE***