| 2015-01-30 14:05:58 | BUILDING PLAN REVIEW |
| | PERMIT: 15010772 |
| | ADD: 5300 EAST AV. / ATRIUM |
| | CONT: TRILLIUM |
| | TEL: ( 561)371-6825 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY/ JAN. 30/2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 THE ATRIUM HEAD GLAZING DETAIL DOES NOT |
| | SHOW FIRE SPRINKLERS IN ACCORDANCE WITH THE 2010 FBC-B |
| | 404.6 ENCLOSURE OF ATRIUMS. |
| | ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES |
| | BY A 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 712, OR BOTH. |
| | EXCEPTIONS: |
| | 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE |
| | AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR |
| | LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE |
| | ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM |
| | SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND |
| | 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE |
| | ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| | THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS |
| | SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE |
| | FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE |
| | GLASS BEFORE THE SPRINKLER SYSTEM OPERATES. |
| | |
| | |