Plan Review Details - Permit 15010757
Plan Review Stops For Permit 15010757
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-11 Cont ID  
Sent By rmcdouga Date 2015-03-11 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2015-03-11 Time 09:28 Sent To  
Notes
2015-03-11 09:29:11RED-LINED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-10 Cont ID  
Sent By rmcdouga Date 2015-03-10 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2015-03-10 Time 09:25 Sent To  
Notes
2015-03-10 09:25:37PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WINDOWS THAT ARE SPECIFIED AS EGRESS WINDOWS ARE
 53" X 50" WHICH DO NOT MEET THE EGRESS SIZE
 REQUIREMENTS OF FBC R310 AND FBC EXISTING BUILDING 604.
 THE 32" X 63" WINDOW DOES COMPLY. IT APPEARS THAT THE
 EGRESS WINDOW MAY BE THE ONE THAT IS PROPOSED TO BE
 ENCLOSED IN BEDROOM #1. PROVIDE THE SIZE OF THE
 EXISTING WINDOW THAT WILL BE IN-FILLED IN BED ROOM #1
 AND THE TYPE (IE SINGLE HUNG, HORIZONTAL SLIDING, ETC.)
 OF EXISTING WINDOW THAT IS IN THE 53" X 50" OPENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 17:22 Rev Time 0.00
Received By rmcdouga Date 2015-01-26 Time 17:22 Sent To  
Notes
2015-01-26 17:56:58PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE EXISTING
 WINDOW OPENINGS WILL BE ENCLOSED. FBC 107.2.1
  
 4) SPECIFY THE WIND SPEED AND EXPOSURE CATEGORY ON THE
 PLANS. FBC 107.2.1.3
  
 5) FBC 107.3.5.3 (5) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.1
  
 6) R310.1 EVERY SLEEPING ROOM SHALL HAVE AT LEAST ONE
 OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR.
 R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530
 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
  
 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT SINGLE HUNG WINDOWS ( NOA NO.11-1013.14 ) HAVE
 INCOMPLETE INSTALLATION INSTRUCTIONS. IT APPEARS THAT
 THE INSTALLATION DRAWINGS WERE NOT SHRUNK DOWN TO FIT
 ON THE 8.5" X 11" PAPER. SUBMIT COMPLETE INSTALLATION
 DRAWINGS AS REQUIRED BY DCA RULE 9N-3.
  
 NOTE: IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-10 Cont ID  
Sent By rmcdouga Date 2015-03-10 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2015-03-09 Time 18:38 Sent To  
Notes
2015-03-10 07:11:49APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 18:51 Rev Time 0.00
Received By rmcdouga Date 2015-01-26 Time 18:23 Sent To  
Notes
2015-01-26 18:01:02PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 , NEC 2008
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 4) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE.
  
 5) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 6) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 8) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 9) NEC 110.26 SUFFICIENT ACCESS AND WORKING SPACE SHALL
 BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. THE WATER HEATER SHALL
 NOT ENCROACH INTO THE REQUIRED WORKING SPACE IN FRONT
 OF THE ELECTRICAL PANEL.
  
 10) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By fmittner Date 2015-12-30 Time 15:46 Rev Time 0.00
Received By fmittner Date 2015-12-30 Time 15:46 Sent To  
Notes
2015-12-30 15:51:54ALTERATIONS OF OPENINGS ON HISTORIC STRUCTUERES
 REQUIRES SUBMITTAL OF A COA (CERTIFICATE OF
 APPROPRIATENESS). QUESTIONS PLEASE CONTACT FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT
 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-10 Cont ID  
Sent By rmcdouga Date 2015-03-10 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2015-03-10 Time 09:26 Sent To  
Notes
2015-02-24 17:35:23SENT TO R. MCDOUGALS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 18:51 Rev Time 0.00
Received By rmcdouga Date 2015-01-23 Time 11:23 Sent To  
Notes
2015-01-23 11:23:58SENT TO R MCDOUGAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2015-01-26 Time 17:20 Sent To  
Notes
2015-01-26 17:22:15INSTALL BATHROOM EXHAUST DUCTED TO OUTDOORS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 17:11 Rev Time 0.00
Received By rmcdouga Date 2015-01-26 Time 17:11 Sent To  
Notes
2015-01-26 17:14:26APPROVED WITH EXCEPTION. THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED ON
 THE PLANS. FBC 107.2.1