Plan Review Details - Permit 15010702
Plan Review Stops For Permit 15010702
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-17 Cont ID  
Sent By shill Date 2015-03-17 Time 14:43 Rev Time 0.00
Received By shill Date 2015-03-17 Time 14:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By shill Date 2015-02-02 Time 10:59 Rev Time 0.00
Received By shill Date 2015-02-02 Time 10:59 Sent To  
Notes
2015-01-29 17:22:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 2. PROVIDE STRUCTURAL DETAILS FOR FRAMING AND FLOORING
 REPAIRS, FBC 107. DETAIL IS TO INCLUDE DESIGN CRITERIA
 FBC 2010 RESIDENTIAL 301, WIND DESIGN CRITERIA, PRINTED
 NAME AND SIGNATURE IF PROVIDED BY SOMEONE OTHER THAN AN
 INDIVIDUAL LICENSED UNDER FS 471 OR 481 (IN THAT CASE
 PLANS NEED A TITLE BLOCK , SIGNATURE AND SEAL).
  
 3. PROVIDE A PLAN WHICH SHOWS LOCATION SCOPE OF
 STRUCTURAL REPAIRS, FBC 107.
  
 4. PROVIDE A PLAN WHICH SHOWS LOCATION AND SCOPE OF
 DRYWALL REPAIR, FBC 107.
  
 5. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 6. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 INCLUDE THE ROOM DESIGNATION.
  
 7. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 1 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-02-25 Cont ID  
Sent By dhayes Date 2015-02-20 Time 08:23 Rev Time 0.00
Received By dhayes Date 2015-02-20 Time 08:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2015-01-29 Cont ID  
Sent By shill Date 2015-01-29 Time 17:25 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-17 Cont ID  
Sent By shill Date 2015-03-17 Time 17:20 Rev Time 0.00
Received By shill Date 2015-03-13 Time 17:56 Sent To  
Notes
2015-03-13 17:56:35SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-02 Cont ID  
Sent By shill Date 2015-02-02 Time 11:14 Rev Time 0.00
Received By shill Date 2015-01-23 Time 07:00 Sent To  
Notes
2015-01-29 17:23:351/29 TO FIRE
  
2015-01-23 07:00:38TO MISC 1
  