Plan Review Details - Permit 15010699
Plan Review Stops For Permit 15010699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-06 Cont ID  
Sent By jwitmer Date 2015-03-06 Time 06:01 Rev Time 0.00
Received By jwitmer Date 2015-03-06 Time 05:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By jwitmer Date 2015-02-02 Time 16:39 Rev Time  
Received By jwitmer Date 2015-02-02 Time 16:13 Sent To  
Notes
2015-02-02 16:39:13BUILDING PLAN REVIEW
 REVISION: 15010699
 PERMIT: 14050183
 ADD: 2800 S. DIXIE HWY.
 CONT: ODUM CONSTRUCTION
 TEL: (561)841-9877
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 02/ 2015
 ACTION: DENIED
  
 1) MISSING WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 2) PLEASE PROVIDE COMPLIANCE WITH :2010 FBC-B 1609.8
 ROOFTOP STRUCTURES AND EQUIPMENT.
 THE LATERAL FORCE ON ROOFTOP STRUCTURES AND EQUIPMENT
 WITH AF LESS THAN (0.1BH) LOCATED ON BUILDINGS OF ALL
 HEIGHTS SHALL BE DETERMINED FROM EQUATION 29.5-1 OF
 ASCE 7 IN WHICH THE VALUE OF GCF SHALL BE TAKEN AS 3.1.
 GCF SHALL BE PERMITTED TO BE REDUCED LINEARLY FROM 3.1
 TO 1.1 AS THE VALUE OF AF IS INCREASED FROM (0.1BH) TO
 (BH). THE VALUE OF G FROM SECTION 26.9 OF ASCE 7 SHALL
 NOT BE USED. ADDITIONALLY, A SIMULTANEOUS UPLIFT FORCE
 SHALL BE APPLIED, GIVEN BY EQUATION 29.5-1 OF ASCE 7 IN
 WHICH GCF = 1.5 AND AF IS REPLACED BY THE HORIZONTAL
 PROJECTED AREA, AR, OF THE ROOFTOP STRUCTURE OR
 EQUIPMENT. FOR THE UPLIFT FORCE GCF SHALL BE PERMITTED
 TO BE REDUCED LINEARLY FROM 1.5 TO 1.0 AS THE VALUE OF
 AR IS INCREASED FROM (0.1BL) TO (BL).
  
 3) SHEET A-2 INDICATES THE FLAG POLE IS TO BE FASTENED
 TO THE BACK OF THE PARAPET AS DIRECTED BY THE
 MANUFACTURER, PLEASE SUBMIT CALCULATIONS AND THE TYPE
 OF ANCHORS AS WELL AS THE FASTENING DEVSIE OF FLAG POLE
 TO PARAPET. PLEASE NOTE THE SIZE OF FLAG WILL NEED TO
 BE KNOWN FOR THE LATERAL AFFECTS THAT WILL NEED TO BE
 CALCULATED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 07:08 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 07:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-09 Cont ID  
Sent By dhayes Date 2015-02-09 Time 14:13 Rev Time 0.00
Received By dhayes Date 2015-02-09 Time 11:10 Sent To  
Notes
2015-02-09 14:13:022/9/2015
 PROJECT: ADX
 PERMIT#: 14050183 REVISION #15010699
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE FOR AND INDICATE ON THE PLANS ADAQUATE
 CLEARANCE FOR THE PANELS, FUSABLE DISCONNECTS AND
 ELECTRICAL SERVICE AS REQUIRED BY NEC 110.26.
  
 2) ELECTRICAL SPECIFICATIONS
 #1) CALLS FOR ALL WORK TO BE DONE IN ACCORDANCE WITH
 THE 2011 NEC. CORRECT THIS TO READ THE 2008 NEC.
 #11) CALLS FOR ALL EXTERIOR LIGHTING TO BE ON SEPARATE
 HOUSE PANEL BY OTHERS. ONLY ONE SERVICE PER BUILDING
 NEC 230.2
  
 3) REVISE CONFLICT AT DRINKING FOUNTAIN. THE NOTE AT
 THE DRINKING FOUNTAIN CALLS FOR BUBBLER ONLY . NO
 ELECTRIC. HOWVER THERE IS AN OUTLET DRAWN IN UNDER THE
 DRINKING FOUNTAIN AND A CIRCUIT IN THE PANEL SCHEDULE
 THAT IS INDICATED AS FEEDING THE DRINKING FOUNTAIN. NEC
 422.52
  
 4) PROVIDE PANEL DESIGNATIONS WITH THE CIRCUIT NUMBERS
 ON THE FLOOR PLAN. WPB AMENDMENTS TO THE FBC 107.2
  
 5) CORRECT CONFLICT IN PANEL SCHEDULES FOR SHOW WINDOW
 LIGHTING CIRCUITS. THE FLOOR PLAN INDICATES THE SHOW
 WINDOW LIGHTING TO BE FIXED LIGHT FIXTURES BEING FED
 FROM PHOTO SENSOR ON UNIT NUMBER 1 PANEL SCHEDULE.
 HOWEVER BOTH PANEL SCHEDULES ALSO INDICATE SHOW WINDOW
 LIGHTING CIRCUITS ON WHAT APPEARS TO BE A SINGLE POLE
 SPACE BUT IS INDICATED AS A 2POLE 30AMP CIRCUIT ON
 #6WIRE. CLEAR UP ALL CONFLICTING INFORMATION.
  
 6) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 7) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 8) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LIGHTS APPEAR TO BE INDICATEDON RECEPTACLE
 CIRCUITS. IDENTIFY EACH BRANCH CIRCUIT ON THE FLOOR
 PLAN AND CORRESPOND WITH EACH UNIT PANEL. NEC 700.12
  
 9) PROVIDE A SIGN CIRCUIT AND OUTLET BOX FOR SIGNAGE.
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. NEC 600.5. THE SIGN CIRCUIT IS
 NOT INCLUDED IN THE LOAD CALCULATION.
  
 10) IDENTIFY THE CIRCUIT AND THE LOAD FOR THE CEILING
 FANS. I DENTIFY THE CIRCUIT IN THE PANEL SCHEDULES AND
 CORRESPONDING ON THE FLOOR PLAN.
  
 11) CONTINUOUS DUTY LOADS HAVE NOT BEEN ACCOUNTED FOR
 IN THE LOAD CALCULATION. NEC 230.(A)(1)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By scaldero Date 2015-01-26 Time 15:08 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 15:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 07:08 Rev Time 0.00
Received By dhayes Date 2015-02-27 Time 07:06 Sent To  
Notes
2015-02-28 07:23:13C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-19 Cont ID  
Sent By hmoser Date 2015-02-19 Time 18:48 Rev Time 0.00
Received By hmoser Date 2015-01-21 Time 13:41 Sent To  
Notes
2015-01-23 13:41:40C07
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-03-06 Cont ID  
Sent By jwitmer Date 2015-03-06 Time 06:03 Rev Time 0.00
Received By jwitmer Date 2015-03-06 Time 05:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-02-19 Cont ID  
Sent By hmoser Date 2015-02-19 Time 18:47 Rev Time 0.00
Received By hmoser Date 2015-02-19 Time 18:39 Sent To  
Notes
2015-02-19 18:47:42PLAN DENIED
 SHOW ON THE PLAN WHERE THE RETURN AIR FOR AIR HANDLER (
 A )
 IS GOING TO BE LOCATED THE MECHANICAL CLOSET CAN NOT BE
 A
 PLENUM WITH THE SINK. PER SECTION 602.2.1 MATERIALS
 WITHIN PLENUM'S
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-29 Cont ID  
Sent By tklarge Date 2015-01-29 Time 10:17 Rev Time 0.00
Received By tklarge Date 2015-01-26 Time 12:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By dkittrid Date 2015-02-04 Time 14:52 Rev Time 0.00
Received By llouie Date 2015-02-03 Time 08:17 Sent To  
Notes
2015-02-04 14:53:372/4/15 - ZONING APPROVED FOR THE FLAGPOLE.
2015-02-03 13:12:402/4/15 - REVISION TO 14050183, SENT TO LL. DK
2015-02-02 15:22:492/2/15