Plan Review Details - Permit 15010696
Plan Review Stops For Permit 15010696
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-01-27 Cont ID  
Sent By tklarge Date 2015-01-27 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2015-01-27 Time 17:00 Sent To  
Notes
2015-01-27 17:24:16BUILDING PLAN REVIEW
 PERMIT: 15010696
 ADD: 2000 PRESIDENTIAL WAY SUITE # 1101
 CONT: ELITE AMERICAN, INC
 TEL: (954)812-6907
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 28/ 2015
 ACTION: BUILDING PROVISO
  
 NEW FLOOR COVERINGS NOT INDICATED:
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2010 603.2 EXCEPTION 2. INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 703.4 NONCOMBUSTIBILITY TESTS.
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-30 Cont ID  
Sent By dhayes Date 2015-01-30 Time 10:18 Rev Time 0.00
Received By dhayes Date 2015-01-30 Time 10:18 Sent To  
Notes
2015-01-30 10:37:211/30/2015
 PROJECT: CONDO RENOVATION 1101
 PERMIT#: 15010696
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
  
 PROVIDE AS BUILT PLANS TO THE INSPECTOR ADDRESSING THE
 FOLLOWING COMMENTS:
  
 1) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 2) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE PANEL SCHEDULE PROVIDED.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. WPB AMENDMENTS TO THE FBC 107.3.2
  
 3) VERIFY SMOKE DETECTORS ARE EXISTING OR INSTALL AS
 REQUIRED. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 4) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. FBC 2704 BONDING METAL FRAMING
 MEMBERS
  
 5) VERIFY BATHROOM CIRCUIT REQUIRED. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 NEC 210.11(C)(3)
  
 6) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL
 OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE
 BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE
 COUNTERTOP. NEC 210.52 (D)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By scaldero Date 2015-01-26 Time 11:54 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-05 Cont ID  
Sent By hmoser Date 2015-02-05 Time 10:56 Rev Time 0.00
Received By hmoser Date 2015-01-21 Time 07:07 Sent To  
Notes
2015-01-23 07:08:06B06
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By hmoser Date 2015-02-05 Time 10:55 Rev Time 0.00
Received By hmoser Date 2015-02-05 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By tklarge Date 2015-01-26 Time 12:38 Rev Time 0.00
Received By tklarge Date 2015-01-26 Time 12:25 Sent To  
Notes
***NONE***