Plan Review Details - Permit 15010671
Plan Review Stops For Permit 15010671
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-04 Cont ID  
Sent By rmcdouga Date 2015-03-04 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2015-03-04 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-06 Cont ID  
Sent By jgomez Date 2015-02-06 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2015-02-06 Time 14:38 Sent To  
Notes
2015-02-06 14:38:57SEE ELECTRICAL COMMENTS REGARDING SMOKE ALARMS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-04 Cont ID  
Sent By rmcdouga Date 2015-03-04 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2015-03-04 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-06 Cont ID  
Sent By rmcdouga Date 2015-02-06 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2015-02-06 Time 13:08 Sent To  
Notes
2015-02-06 13:52:27PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 240.24(A) & (B) PANELS SHALL BE READILY
 ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS.
 SPECIFY THE LOCATION OF THE PANEL FOR UNIT #2 ON THE
 ELECTRICAL FLOOR PLAN (SHEET R E-1).
  
 2) A 200 AMP ELECTRIC PANEL IS SHOWN ON SHEET R-1 FOR
 UNIT #2 ON THE BUILDING FLOOR PLAN. THE ELECTRICAL
 RISER PLAN ON SHEET R E-1 SHOWS BOTH PANELS AS 150 AMP.
 PLEASE CORRECT. FBC 107.2.1
  
 3) A SMOKE ALARM IS REQUIRED IN THE BEDROOM OF UNIT #2.
 TWO SMOKE ALARMS ARE SHOWN IN THE LIVING ROOM. FBC
 FBC-R314.3.1
  
 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET.
  
 5) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 6) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6.5 FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF EACH UNIT OF THE DWELLING.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-04 Cont ID  
Sent By rmcdouga Date 2015-03-04 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2015-02-24 Time 12:51 Sent To  
Notes
2015-02-25 12:51:45REVISION RE-SUBMITTAL SENT TO ROBERT MCDOUGAL FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-06 Cont ID  
Sent By rmcdouga Date 2015-02-06 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2015-01-21 Time 07:39 Sent To  
Notes
2015-01-23 07:43:17R03
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-04 Cont ID  
Sent By rmcdouga Date 2015-03-04 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2015-03-04 Time 16:24 Sent To  
Notes
2015-02-25 12:52:14NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-28 Cont ID  
Sent By tklarge Date 2015-01-28 Time 06:24 Rev Time 0.00
Received By tklarge Date 2015-01-28 Time 06:14 Sent To  
Notes
***NONE***