Plan Review Details - Permit 15010629
Plan Review Stops For Permit 15010629
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-30 Cont ID  
Sent By wjolin Date 2015-04-30 Time 11:55 Rev Time 0.00
Received By wjolin Date 2015-04-22 Time 11:45 Sent To  
Notes
2015-04-30 12:16:36STEEL WILL BE PROTECTED WITH "PITTCHAR XP" TO ACHIEVE A
 2-HOUR FIRE RESISTANCE RATING PER UNITED FIRE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By wjolin Date 2015-02-26 Time 15:51 Rev Time 0.00
Received By wjolin Date 2015-02-26 Time 14:30 Sent To  
Notes
2015-02-26 15:27:136651 NORTH JOG ROAD - FIRE PUMPS DIESEL STORAGE TANKS
 PERMIT #15010629
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NFPA 1 SECTION 66.22.5.2.4 STEEL SUPPORT STRUCTURES OR
 EXPOSED PILING FOR TANKS STORING CLASS I, CLASS II, OR
 CLASS IIIA LIQUIDS SHALL BE PROTECTED BY MATERIALS
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 2
 HOURS.
  
 NFPA 1 SECTION 66.21.7.2.1 IDENTIFICATION FOR EMERGENCY
 RESPONDERS. A SIGN OR MARKING THAT MEETS THE
 REQUIREMENTS OF NFPA 704, STANDARD SYSTEM FOR THE
 IDENTIFICATION OF THE HAZARDS OF MATERIALS FOR
 EMERGENCY RESPONSE, OR ANOTHER APPROVED SYSTEM, SHALL
 BE APPLIED TO STORAGE TANKS CONTAINING LIQUIDS. THE
 MARKING SHALL BE LOCATED WHERE IT CAN BE SEEN, SUCH AS
 ON THE SIDE OF THE TANK, THE SHOULDER OF AN ACCESSWAY
 OR WALKWAY TO THE TANK OR TANKS, OR ON THE PIPING
 OUTSIDE OF THE DIKED AREA. IF MORE THAN ONE TANK IS
 INVOLVED, THE MARKINGS SHALL BE SO LOCATED THAT EACH
 TANK CAN BE IDENTIFIED.
  
 NFPA 1 SECTION 66.27.9 PIPING SYSTEMS SHALL BE BONDED
 AND GROUNDED. ANY ELECTRICALLY ISOLATED SECTION OF
 METALLIC PIPING OR EQUIPMENT SHALL BE BONDED AND
 GROUNDED TO PREVENT HAZARDOUS ACCUMULATION OF STATIC
 ELECTRICITY.
  
 NFPA 20 SECTION 11.4.2 FUEL LINE PROTECTION: A GUARD,
 PIPE PROTECTION, OR APPROVED DOUBLE-WALLED PIPE SHALL
 BE PROVIDED FOR ALL EXPOSED FUEL LINES.
  
 NFPA 20 SECTION 11.4.5.7 MEANS OTHER THAN SIGHT TUBES
 FOR CONTINUOUS INDICATING OF THE AMOUNT OF FUEL IN EACH
 STORAGE TANK SHALL BE PROVIDED.
  
 NFPA 20 SECTION 11.4.7.4 THE GRADE OF FUEL OIL SHALL BE
 INDICATED ON THE FUEL TANK BY LETTERS THAT ARE A
 MINIMUM OF 6-INCHES IN HEIGHT AND IN CONTRASTING COLOR
 TO THE TANK.
  
 NFPA 20 SECTION 11.6.4.1 THE FUEL STORAGE TANKS SHALL
 BE KEPT AS FULL AS PRACTICAL AT ALL TIMES, BUT NEVER
 BELOW 66 PERCENT (TWO-THIRDS) OF TANK CAPACITY. A FUEL
 LEVEL INDICATOR ON THE FIRE PUMP CONTROLLER SHALL BE
 PROVIDED TO ACTIVATE AT THE TWO-THIRDS TANK LEVEL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-21 Cont ID  
Sent By lmarchan Date 2015-05-21 Time 11:20 Rev Time 0.00
Received By lmarchan Date 2015-05-07 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-05 Cont ID  
Sent By cpuell Date 2015-05-05 Time 08:01 Rev Time 0.00
Received By cpuell Date 2015-04-09 Time 13:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-27 Cont ID  
Sent By hmoser Date 2015-02-27 Time 14:42 Rev Time 0.00
Received By hmoser Date 2015-02-19 Time 10:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-24 Cont ID  
Sent By hmoser Date 2015-04-24 Time 15:27 Rev Time 0.00
Received By hmoser Date 2015-04-24 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-02-27 Cont ID  
Sent By hmoser Date 2015-02-27 Time 14:22 Rev Time 0.00
Received By hmoser Date 2015-02-27 Time 14:22 Sent To  
Notes
2015-02-27 14:42:35PLAN DENIED
 1) REFER TO SECTION 1301.2 STORAGE AND PIPING
 SYSTEM. 2010 FBC (M) . REFER TO FIRE
 COMMENTS.
 2) PROVIDE ENGINEERING ON ANCHORING FUEL
 TANK TO SLAB PROVIDE ANCHOR TYPE AND SIZE
 ON THE DETAIL. PER SECTION 301.12 WIND RESISTANCE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-06-01 Cont ID  
Sent By skennedy Date 2015-06-01 Time 16:48 Rev Time 0.00
Received By skennedy Date 2015-06-01 Time 15:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-21 Cont ID  
Sent By eschneid Date 2015-05-21 Time 10:12 Rev Time 0.50
Received By eschneid Date 2015-05-21 Time 10:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-20 Cont ID  
Sent By eschneid Date 2015-04-20 Time 18:23 Rev Time 0.50
Received By eschneid Date 2015-04-20 Time 18:23 Sent To  
Notes
2015-04-20 18:26:56FAILED
  
 1) PROVIDE A SITE PLAN SHOWING WHERE THIS FUEL TANK
 WILL BE LOCATED.
  
 2) HOW IS THIS FUEL TANK SCREENED? SECTION 94-444(B) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS SPECIFY
 THAT FUEL TANKS BE SCREENED BY SOLID WALL AND
 LANDSCAPE.
  
 3) PROVIDE THE OVERALL HEIGHT OF THE TANK FROM GRADE.
 THE ENTIRE HEIGHT SHALL BE SCREENED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.