Plan Review Details - Permit 15010618
Plan Review Stops For Permit 15010618
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-29 Cont ID  
Sent By dhayes Date 2015-01-29 Time 09:40 Rev Time 0.00
Received By dhayes Date 2015-01-29 Time 09:40 Sent To  
Notes
2015-01-29 09:58:01VERIFY COMPLIANCE WITH THE FOLLOWING:
  
 1) NEC 210.4 MULTIWIRE BRANCH CIRCUITS. (A) GENERAL.
 BRANCH CIRCUITS RECOGNIZED BY THIS ARTICLE SHALL BE
 PERMITTED AS MULTIWIRE CIRCUITS. A MULTIWIRE CIRCUIT
 SHALL BE PERMITTED TO BE CONSIDERED AS MULTIPLE
 CIRCUITS. ALL CONDUCTORS OF A MULTIWIRE BRANCH CIRCUIT
 SHALL ORIGINATE FROM THE SAME PANELBOARD OR SIMILAR
 DISTRIBUTION EQUIPMENT.
  
 2) NEC 210.7 BRANCH-CIRCUIT REQUIREMENTS FOR DEVICE
 CONNECTIONS AND LOCATIONS.
 (A) RECEPTACLE OUTLET LOCATION. RECEPTACLE OUTLETS
 SHALL BE LOCATED IN BRANCH CIRCUITS IN ACCORDANCE WITH
 PART III OF ARTICLE 210.
 (B) MULTIPLE BRANCH CIRCUITS. WHERE TWO OR MORE BRANCH
 CIRCUITS SUPPLY DEVICES OR EQUIPMENT ON THE SAME YOKE,
 A MEANS TO SIMULTANEOUSLY DISCONNECT THE UNGROUNDED
 CONDUCTORS
  
 3) NEC 300.13 MECHANICAL AND ELECTRICAL CONTINUITY ?
 CONDUCTORS. (B) DEVICE REMOVAL. IN MULTIWIRE BRANCH
 CIRCUITS, THE CONTINUITY OF A GROUNDED CONDUCTOR SHALL
 NOT DEPEND ON DEVICE CONNECTIONS SUCH AS LAMPHOLDERS,
 RECEPTACLES, AND SO FORTH, WHERE THE REMOVAL OF SUCH
 DEVICES WOULD INTERRUPT THE CONTINUITY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-22 Cont ID  
Sent By dhayes Date 2015-01-22 Time 09:40 Rev Time 0.00
Received By dhayes Date 2015-01-22 Time 09:14 Sent To  
Notes
2015-01-22 09:40:34REVISE PLANS FOR CLARIFICATION IN RESPONSE TO THE
 FOLLOWING:
  
 1) PROVIDE PANEL NAMES ON SITE PLAN CORRESPONDING TO
 THE PANEL NAMES ON THE RISER.
 2) PROVIDE CIRCUIT NUMBERS ON SITE PLAN CORRESPONDING
 TO PANEL SCHEDULES.
 3) PROVIDE WIRE SIZES ON SITE PLAN CORRESPONDING TO
 CIRCUIT NUMBERS ON PANEL SCHEDULES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-29 Cont ID  
Sent By dhayes Date 2015-01-29 Time 09:58 Rev Time 0.00
Received By dhayes Date 2015-01-28 Time 18:47 Sent To  
Notes
2015-01-28 18:48:46TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-22 Cont ID  
Sent By dhayes Date 2015-01-22 Time 09:40 Rev Time 0.00
Received By dhayes Date 2015-01-20 Time 09:13 Sent To  
Notes
***NONE***