| 2015-03-04 18:13:33 | RESIDENTIAL (R3) ADDITION /ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N. |
| | JOG RD) TO VERIFY ASSESSMENT OF IMPACT FEES. BRING BACK |
| | COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES |
| | ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED |
| | LAND DEVELOPMENT CODE. |
| | |
| | 2- WINDOWS FOR BEDROOM #3: PROVIDE MANUFACTURER'S CUT |
| | SHEETS FOR WINDOW SIZE SPECIFIED ON PLANS TO VERIFY |
| | COMPLIANCE WITH ALL THE EGRESS REQUIREMENTS OF SEC. |
| | R310 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- SHEET A-2, A-3 AND S-2: |
| | A) ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE |
| | "C" NOT "B". REVISE THE DESIGN INFORMATION, INCLUDING |
| | THE DOORS/WINDOWS DESIGN PRESSURES. |
| | |
| | B) ACCORDING TO FOOTNOTE ON FIGURE R301.2(7) THE |
| | MINIMUM DISTANCE "A" IN THE WALL ELEVATION IS 4'-0" NOT |
| | 3'-0". REVISE WALL ELEVATION DETAIL AS REQUIRED. |
| | |
| | C) THERE IS ONE WINDOW ON BEDROOM #3 THAT IS LOCATED IN |
| | THE END ZONE #5. SEE ITEM #3(B) ABOVE. REVISE THE |
| | DESIGN PRESSURES ACCORDINGLY. SEC. R301.2.1.4.3. |
| | |
| | 4-REVISE DETAIL 3/SD-1. FOOTING SIZE TO MATCH SIZE |
| | SHOWN ON FOUNDATION PLAN. SEC. 107.2.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 5- REVISE DETAIL 4/SD-1. FOOTING TO BE 12" MIN. BELOW |
| | GRADE. SEC. R403.1.4 OF 2010 FBC-RESIDENTIAL. AND, |
| | COORDINATE SIZE WITH SIZE SHOWN ON FOUNDATION PLAN. |
| | |
| | 6- ENERGY CALCULATIONS: |
| | A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE ITEM #10 TO MATCH PLANS. ARCHITECT DIDN'T |
| | DESIGNED UNVENTED ATTIC. SEE PLANS AND REVISE AS |
| | REQUIRED. AND COORDINATE R-VALUE WITH ARCHITECT'S |
| | SPECS. SEC. 103.2.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) REVISE THE WINDOWS OVERHANG DEPTH AND OVERHANG |
| | SEPARATION ON PAGE 3 OF 6 TO MATCH ARCHITECTURAL PLANS. |
| | SEC. 103.2.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | D) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER, BUILDER, PERMIT OFFICE AND |
| | JURISDICTION #. SEC. 103.2.1.1.2 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ENTRY DOOR WITH SQUARE TOP THAT MATCHES TYPE OF DOOR |
| | SHOWN ON PLANS. |
| | |
| | B) WINDOW MULLIONS. SUBMITTED NOA 13-0815.05 WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| | |
| | C) ALL FIXED WINDOWS AS SHOWN ON PLANS.( ARCHED AND |
| | SQUARE). |
| | |
| | D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | SPECIFY THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE |
| | SPECIFIED CONNECTOR. ALSO, UPDATE THE FLORIDA PRODUCT |
| | APPROVAL NUMBERS SPECIFIED ON CONNECTOR SCHEDULE ON |
| | SHEET S-2. THEY DON'T CORRESPOND TO THE 2010 FBC CODE |
| | VERSION. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. |
| | |
| | 9- GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA 13-1022.15 |
| | SUBMITTED: |
| | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 OF |
| | 2010 FBC. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION $7 ON LAST PAGE OF NOA. |
| | NEED THE NAIL ENHANCING CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301. |
| | |
| | 10- PROVIDE FRAMING DETAILS AND SPECIFICATIONS FOR ALL |
| | ARCHED OPENING SHOWN ON ELEVATIONS. SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | ***PLEASE PROVIDE LETTER ADDRESSING EACH COMMENT TO |
| | HELP EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE AND REPLACE EACH REVISED SHEET. |
| | |