Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 15:43 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 15:30 Sent To  
Notes
2015-05-01 15:54:33BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE ICYNENE ICC EVALUATION REPORT (2 COPIES).
 (NO FEE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-10 Time 14:36 Rev Time 0.00
Received By jgomez Date 2015-04-10 Time 14:36 Sent To  
Notes
2015-04-10 14:37:52BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- FLAT ROOF: ENGINEER TO REVISE THE RAS 117
 CALCULATIONS. NAIL SPACING SHOWN FOR ROOF ZONE #1
 DOESN'T MATCH NAIL SPACING SHOWN ON NOA 13-1022.15.
 REVISE ALL CALCULATIONS AS REQUIRED. SEE SEC. 8.1 OF
 RAS 117.
 2- REVISE ALL NOTES ON SHEET SP-1. THIS IS A NEW SINGLE
 FAMILY RESIDENCE NOT REMODELING. EXISTING HOUSE WILL BE
 COMPLETELY DEMOLISHED.
 3- REVISE TYP. WALL SECTION 1/A-2. ATTIC VENTED OR
 ICYNENE INSULATION. COORDINATE WITH THE ENERGY
 CALCULATIONS.
 4- PROVIDE ICYNENE ICC EVALUATION REPORT (2 COPIES).
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL SIMPSON
 STRUCTURAL CONNECTORS SPECIFIED ON ALL PLANS AND
 DETAILS OR SPECIFY THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED CONNECTOR. ALSO, UPDATE THE
 FLORIDA PRODUCT APPROVAL NUMBERS SPECIFIED ON CONNECTOR
 SCHEDULE ON SHEET S-2. THEY DON'T CORRESPOND TO THE
 2010 FBC CODE VERSION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jgomez Date 2015-03-05 Time 07:30 Rev Time 0.00
Received By jgomez Date 2015-03-04 Time 17:53 Sent To  
Notes
2015-03-04 18:13:33RESIDENTIAL (R3) ADDITION /ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD) TO VERIFY ASSESSMENT OF IMPACT FEES. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
 2- WINDOWS FOR BEDROOM #3: PROVIDE MANUFACTURER'S CUT
 SHEETS FOR WINDOW SIZE SPECIFIED ON PLANS TO VERIFY
 COMPLIANCE WITH ALL THE EGRESS REQUIREMENTS OF SEC.
 R310 OF 2010 FBC-RESIDENTIAL.
  
 3- SHEET A-2, A-3 AND S-2:
 A) ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE
 "C" NOT "B". REVISE THE DESIGN INFORMATION, INCLUDING
 THE DOORS/WINDOWS DESIGN PRESSURES.
  
 B) ACCORDING TO FOOTNOTE ON FIGURE R301.2(7) THE
 MINIMUM DISTANCE "A" IN THE WALL ELEVATION IS 4'-0" NOT
 3'-0". REVISE WALL ELEVATION DETAIL AS REQUIRED.
  
 C) THERE IS ONE WINDOW ON BEDROOM #3 THAT IS LOCATED IN
 THE END ZONE #5. SEE ITEM #3(B) ABOVE. REVISE THE
 DESIGN PRESSURES ACCORDINGLY. SEC. R301.2.1.4.3.
  
 4-REVISE DETAIL 3/SD-1. FOOTING SIZE TO MATCH SIZE
 SHOWN ON FOUNDATION PLAN. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 5- REVISE DETAIL 4/SD-1. FOOTING TO BE 12" MIN. BELOW
 GRADE. SEC. R403.1.4 OF 2010 FBC-RESIDENTIAL. AND,
 COORDINATE SIZE WITH SIZE SHOWN ON FOUNDATION PLAN.
  
 6- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE ITEM #10 TO MATCH PLANS. ARCHITECT DIDN'T
 DESIGNED UNVENTED ATTIC. SEE PLANS AND REVISE AS
 REQUIRED. AND COORDINATE R-VALUE WITH ARCHITECT'S
 SPECS. SEC. 103.2.2 OF 2010 FBC-RESIDENTIAL.
  
 C) REVISE THE WINDOWS OVERHANG DEPTH AND OVERHANG
 SEPARATION ON PAGE 3 OF 6 TO MATCH ARCHITECTURAL PLANS.
 SEC. 103.2.2 OF 2010 FBC-RESIDENTIAL.
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER, PERMIT OFFICE AND
 JURISDICTION #. SEC. 103.2.1.1.2 OF 2010
 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOOR WITH SQUARE TOP THAT MATCHES TYPE OF DOOR
 SHOWN ON PLANS.
  
 B) WINDOW MULLIONS. SUBMITTED NOA 13-0815.05 WAS
 SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA.
  
 C) ALL FIXED WINDOWS AS SHOWN ON PLANS.( ARCHED AND
 SQUARE).
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 SPECIFY THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE
 SPECIFIED CONNECTOR. ALSO, UPDATE THE FLORIDA PRODUCT
 APPROVAL NUMBERS SPECIFIED ON CONNECTOR SCHEDULE ON
 SHEET S-2. THEY DON'T CORRESPOND TO THE 2010 FBC CODE
 VERSION.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS.
  
 9- GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA 13-1022.15
 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 OF
 2010 FBC.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION $7 ON LAST PAGE OF NOA.
 NEED THE NAIL ENHANCING CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.
  
 10- PROVIDE FRAMING DETAILS AND SPECIFICATIONS FOR ALL
 ARCHED OPENING SHOWN ON ELEVATIONS. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE LETTER ADDRESSING EACH COMMENT TO
 HELP EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE EACH REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-28 Cont ID  
Sent By dhayes Date 2015-04-28 Time 12:08 Rev Time 0.00
Received By rlecky Date 2015-04-28 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By dhayes Date 2015-01-21 Time 11:42 Rev Time 0.00
Received By dhayes Date 2015-01-21 Time 10:57 Sent To  
Notes
2015-01-21 11:42:311/21/2015
 PROJECT: JAMES BROOKS RESIDENCE
 PERMIT#: 15010607
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO INDICATE THE FEEDER TO
 THE POOL PANEL. NEC 215.5
  
 2) PROVIDE A PANEL SCHEDULE FOR BOTH PANELS NEC 408.4
  
 3) REVISE GROUNDING ELECTRODE SYSTEM TO INCLUDE TWO
 DRIVEN GROUND RODS AND A INTERSYSTEM BOND BAR. NEC
 250.50 AND 250.94
  
 4) ALL OUTLETS IN THE GARAGE INCLUDING THOSE FOR THE
 GARAGE DOOR OPENERS SHALL BE GFI PROTECTED. NEC 210.8
  
 5) PROVIDE A FAULT CURRENT CALCULATION TO VERIFY THE
 ELECTRICAL SERVICE DISCONNECTING MEANS HAS A FAULT
 CURRENT RATING THAT IS SUFFICIENT FOR THE CURRENT THAT
 MUST BE INTERRUPTED. NEC 110.9
  
 6) PROVIDE ARC FAULT CIRCUIT INTERUPTER PROTECTION ON
 ALL BRANCH CIRCUITS AS REQUIRED. NEC 210.12
  
 7) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 8) BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL
 BE USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC
 314.27(C)
  
 9) PROVIDE PRODUCT APPOVALS FOR JACUZZI TUB. GFI
 REQUIRED. NEC 680.71
  
 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, AUDIO/VIDEO SYSTEM,
 SECURITY, AND CCTV..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 15:15 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 15:15 Sent To  
Notes
2015-05-01 15:15:52SUBMITTAL OF PLANS WITH IMPACT FEES. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-29 Cont ID  
Sent By tklarge Date 2015-04-29 Time 09:59 Rev Time 0.00
Received By tklarge Date 2015-03-25 Time 16:53 Sent To  
Notes
2015-03-25 16:36:41R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-05 Cont ID  
Sent By jgomez Date 2015-03-05 Time 14:30 Rev Time 0.00
Received By jgomez Date 2015-01-20 Time 12:14 Sent To  
Notes
2015-01-21 12:14:50R14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 15:30 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 15:16 Sent To  
Notes
2015-05-01 15:43:12MU-2015-010290. $417.24 PAID. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-04-10 Cont ID  
Sent By jgomez Date 2015-04-10 Time 15:06 Rev Time 0.00
Received By jgomez Date 2015-04-10 Time 15:06 Sent To  
Notes
2015-04-10 15:07:191- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD) TO VERIFY ASSESSMENT OF IMPACT FEES. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-04 Cont ID  
Sent By jgomez Date 2015-03-04 Time 18:09 Rev Time 0.00
Received By jgomez Date 2015-03-04 Time 18:09 Sent To  
Notes
2015-03-04 18:12:421- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD) TO VERIFY ASSESSMENT OF IMPACT FEES. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 10:24 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 10:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jgomez Date 2015-03-05 Time 14:07 Rev Time 0.00
Received By jgomez Date 2015-03-05 Time 12:42 Sent To  
Notes
2015-03-05 14:30:29RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS:
 A) REVISE THE EQUIPMENT SIZING CALCULATIONS.
 CALCULATIONS WERE DONE TRANSFERRING THE INFORMATION
 FROM THE ENERGY CALCULATIONS. ENERGY CALCULATIONS WERE
 DONE BASED ON THE WORST CASE SCENARIO. A/C EQUIPMENT
 SIZING CALCULATIONS CAN NOT BE DONE BASED ON THE WORST
 CASE SCENARIO. THEY NEED TO BE DONE BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 B) REVISE THE OVERHANG LENGTH AND OVERHANG HEIGHT TO
 MATCH PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION
  
 C) HOUSE ATTIC WAS DESIGNED AS VENTED NOT UNVENTED. SEE
 PLANS AND REVISE AS REQUIRED. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION
  
 D) REVISE NUMBER OF OCCUPANTS. THERE ARE NOT 10
 OCCUPANTS AND 32 OCCUPANTS IN A 3 BEDROOM SINGLE FAMILY
 RESIDENCE. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN ON THE A/C PLAN AS REQUIRED
 BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 ***PLEASE PROVIDE LETTER ADDRESSING EACH COMMENT TO
 HELP EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE EACH REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-29 Cont ID  
Sent By tklarge Date 2015-04-29 Time 09:39 Rev Time 0.00
Received By tklarge Date 2015-04-29 Time 09:17 Sent To  
Notes
2015-04-10 17:21:46NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-25 Cont ID  
Sent By tklarge Date 2015-01-25 Time 05:34 Rev Time 0.00
Received By tklarge Date 2015-01-25 Time 05:10 Sent To  
Notes
2015-01-25 05:35:38SEPARATE PLANS AND PERMIT REQUIRED FOR GAS.TKL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 09:49 Rev Time 0.00
Received By jgomez Date 2015-04-13 Time 07:40 Sent To  
Notes
2015-04-13 07:40:331- GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA
 13-1022.15.
  
 2- EAGLE CONCRETE TILE NOA 11-0321.03.
  
 3- 3M FOAM NOA 14-0805.01

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jgomez Date 2015-03-05 Time 14:06 Rev Time 0.00
Received By jgomez Date 2015-03-05 Time 12:31 Sent To  
Notes
2015-03-05 14:07:30GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA 13-1022.15
 SUBMITTED:
  
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 OF
 2010 FBC.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION $7 ON LAST PAGE OF NOA.
 NEED THE NAIL ENHANCING CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-04-14 Cont ID  
Sent By sgraham Date 2015-04-14 Time 09:13 Rev Time 0.00
Received By sgraham Date 2015-04-14 Time 09:13 Sent To  
Notes
2015-04-10 17:20:23NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-02 Cont ID  
Sent By sgraham Date 2015-03-02 Time 15:10 Rev Time 0.00
Received By sgraham Date 2015-03-02 Time 15:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By sgraham Date 2015-02-04 Time 13:22 Rev Time 0.00
Received By sgraham Date 2015-02-04 Time 13:22 Sent To  
Notes
2015-02-04 13:33:092/4/15 ZONING FAILED
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved