| 2015-01-22 15:20:56 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- EAGLE ROOF TILE FLORIDA PRODUCT APPROVAL FL7473-R3 |
| | SUBMITTED DOESN'T SPECIFY THE ATTACHMENT RESISTANCE |
| | VALUE WITH THE USE OF 3M COMPONENT FOAM ROOF TILE |
| | ADHESIVE AH-160. SEE LIMITATION 5.5 ON PAGE 3 OF 4 OF |
| | FL7473-R3. ON THE OTHER HAND, ROOF TILE ADHESIVE AH-160 |
| | NOA 14-0805.01 SUBMITTED REQUIRES THE ROOF TILE |
| | ASSEMBLY TO LIST THE AH-160 AND THE CORRESPONDING |
| | ATTACHMENT RESISTANCE VALUE. PLEASE PROVIDE PROPER |
| | PRODUCT APPROVALS FOR ROOF TILE AND ROOF TILE ADHESIVE |
| | SHOWING THE ATTACHMENT RESISTANCE. DCA RULE 9N-3. |
| | |
| | 2- POLYSTICK TU PLUS UNDERLAYMENT FLORIDA PRODUCT |
| | APPROVAL FL5259-R20 SUBMITTED. CLEARLY IDENTIFY WHICH |
| | ASSEMBLY IS GOING TO BE INSTALLED. DIRECT BOND DECK OR |
| | BOND TO MECHANICALLY ATTACHED BASE LAYER: |
| | A) IF USING THE DIRECT BOND TO DECK, THEN KEEP IN MIND |
| | THAT SEC. 5.5.4.1 ON PAGE 5 OF 11 OF FL5259-R20 SHOWS A |
| | MAXIMUM DESIGN PRESSURES OF -90 PSF . IT DOESN'T MEET |
| | THE DESIGN PRESSURES AT CORNER AREAS. THEREFORE, IT |
| | CAN'T BE USED FOR CORNER AREAS. NEED TO USE ANOTHER |
| | ASSEMBLY WITH HIGHER DESIGN PRESSURES FOR CORNER AREAS. |
| | |
| | B) IF USING THE BOND TO MECHANICALLY ATTACHED BASE |
| | LAYER, THEN PROVIDE THE SPECIFICATIONS FOR THE BASE |
| | SHEET FASTENING SHOWING COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.1 OF 2010 FBC-RESIDENTIAL. SEE |
| | SEC. 5.5.3 ON PAGE 5 OF 11 OF FL5259-R20. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION WAS UPDATED TO $24,157, SEC. 109.3 CITY |
| | AMENDMENTS TO FBC. THE PERMIT FEE BALANCE IS $566.94. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |