Plan Review Details - Permit 15010560
Plan Review Stops For Permit 15010560
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time 07:29 Rev Time 0.00
Received By   Date 2015-02-09 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-24 Cont ID  
Sent By jwitmer Date 2015-01-24 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2015-01-24 Time 10:19 Sent To  
Notes
2015-01-24 10:29:16BUILDING PLAN REVIEW
 REVISION: 15010560
 PERMIT: 14110435
 ADD: 1270 PALM BEACH LAKES
 CONT: EVANS PETROLEUM
 TEL: (305)796-9695
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. / JAN. 24/ 2015
 ACTION: DENIED
  
 1) SHEET A-1 DOES NOT PROVIDE DETAILS OF THE SODA
 FOUNTAINS, HOT OPTIONS OR HOT DOG ROTESSERIES FOR REACH
 RANGES NOR IF SIDE APPROACH OR FRONTAL APPROACH. NOTE
 THE PLANS DO INDICATE A 34 INCH COUNTER.
  
 2010 FBC-ACCESSIBILITY 308 REACH RANGES
 308.2 FORWARD REACH
 308.3 SIDE REACH
  
 309 OPERABLE PARTS
 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH 309.
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-20 Cont ID  
Sent By dhayes Date 2015-01-20 Time 11:03 Rev Time 0.00
Received By dhayes Date 2015-01-20 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By scaldero Date 2015-01-26 Time 11:28 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 11:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-09 Cont ID  
Sent By   Date 2015-02-09 Time   Rev Time 0.00
Received By shill Date 2015-02-04 Time 08:55 Sent To  
Notes
2015-02-04 08:55:18****EXPEDITED****
 B10
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By hmoser Date 2015-01-26 Time 15:05 Rev Time 0.00
Received By hmoser Date 2015-01-20 Time 10:48 Sent To  
Notes
2015-01-20 10:52:24B09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By hmoser Date 2015-01-26 Time 15:05 Rev Time 0.00
Received By hmoser Date 2015-01-26 Time 15:00 Sent To  
Notes
2015-01-26 15:05:30NO REVISION FOR MECHANICAL SUBMITTED

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 07:21 Rev Time 0.00
Received By tklarge Date 2015-02-07 Time 06:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-25 Cont ID  
Sent By tklarge Date 2015-01-25 Time 06:06 Rev Time 0.00
Received By tklarge Date 2015-01-25 Time 05:38 Sent To  
Notes
2015-01-25 06:06:031) THE VENT FOR THE MOP SINK MUST BE WASHED BY THE
 FIXTURE. DRY VENTS ARE PROHIBITED PER 2010 FL. PLBG.
 CODE SEC.905.3.;
 2) SHT. P-2 - THE GREASE WASTE RISER REFERS TO SHT. U-1
 FOR THE GREASE TRAP LOCATION. THE DRAWING IS NOT
 INCLUDED.SUBMIT THE DRAWING FOR REVIEW.WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) THE DRINKING FOUNTAIN SHALL BE A HI-LO UNIT PER THE
 FAC SEC.211.2 & FL. EXISTING BUILDING CODE SEC. 706.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy