Plan Review Details - Permit 15010524
Plan Review Stops For Permit 15010524
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-12 Cont ID  
Sent By jwitmer Date 2015-03-12 Time   Rev Time 0.00
Received By jwitmer Date 2015-03-12 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-01-30 Cont ID  
Sent By jwitmer Date 2015-01-30 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2015-01-30 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-03 Cont ID  
Sent By dhayes Date 2015-02-03 Time 08:41 Rev Time 0.00
Received By dhayes Date 2015-02-03 Time 08:41 Sent To  
Notes
2015-02-03 08:43:501) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-26 Cont ID  
Sent By scaldero Date 2015-01-26 Time 12:24 Rev Time 0.00
Received By scaldero Date 2015-01-26 Time 12:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-16 Cont ID  
Sent By tklarge Date 2015-03-16 Time 14:57 Rev Time 0.00
Received By tklarge Date 2015-02-26 Time 15:52 Sent To  
Notes
2015-02-27 15:53:39C02
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By tklarge Date 2015-03-16 Time 14:58 Rev Time 0.00
Received By tklarge Date 2015-01-16 Time 11:28 Sent To  
Notes
2015-01-20 11:28:42SENT TO C2 BIN FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-02-19 Cont ID  
Sent By hmoser Date 2015-02-19 Time 17:42 Rev Time 0.00
Received By hmoser Date 2015-02-19 Time 17:25 Sent To  
Notes
2015-02-19 17:42:11WALK IN COOLERS ARE NOT INCLUDED IN THIS REVIEW
 SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED.
 PLAN SHOWS CONDENSER IS EXISTING . IS THE AIRHANDLER
 EXISTING IF SO PLEASE MARK ON PLAN
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-16 Cont ID  
Sent By tklarge Date 2015-03-16 Time 14:57 Rev Time 0.00
Received By tklarge Date 2015-03-16 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-25 Cont ID  
Sent By tklarge Date 2015-01-25 Time 07:58 Rev Time 0.00
Received By tklarge Date 2015-01-25 Time 06:42 Sent To  
Notes
2015-01-25 07:58:021) SUBMIT SPECIFICATIONS FOR THE MOP SINK. SEE
 SHT.A6.1, DETAIL #6. THIS DETAIL CONFLICTS WITH THE MOP
 SINK DETAI ON SHT.P-1, CLARIFY.
 2) SHT.A6.1 - ELEVATION "C"- SHOW THE SPACING OF THE
 REAR GRAB BAR TO COMPLY W/2010 FAC SEC.604.5.2.
 3) SIZE THE VENT FOR THE MOP SINK ON SHT. P-1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By aaponte Date 2015-02-12 Time 10:10 Rev Time 0.00
Received By aaponte Date 2015-02-12 Time 10:10 Sent To  
Notes
***NONE***