Plan Review Details - Permit 15010463
Plan Review Stops For Permit 15010463
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-11 Cont ID  
Sent By skennedy Date 2015-03-11 Time 16:40 Rev Time 0.00
Received By skennedy Date 2015-03-11 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-01-21 Cont ID  
Sent By jgomez Date 2015-01-21 Time 12:45 Rev Time 0.00
Received By jgomez Date 2015-01-21 Time 12:27 Sent To E
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By skennedy Date 2015-03-13 Time 08:15 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-29 Cont ID  
Sent By sciard Date 2015-01-29 Time 11:21 Rev Time 0.00
Received By sciard Date 2015-01-29 Time 11:21 Sent To  
Notes
2015-01-29 11:30:151. FBC 107.3.5.3. PROVIDE PANEL SCHEDULE AND CIRCUITRY
 FOR OUTLETS ON PLANS.
 2. N.E.C. 210.11(C)1. IDENTIFY A MININUM OF TWO SMALL
 APPLIANCE CIRCUITS SUPPLYING KITCHEN COUNTERTOP
 RECEPTACLES.
 3. FBC SECTION R314 LOCATION OF SMOKE ALARMS
 4. N.E.C. 210.12 ARC FAULT PROTECTION FOR OUTLETS ON 15
 AND 20 AMPERE BRANCH CIRCUITS FOR AREAS SPECIFIED IN
 THIS CODE SECTION,(T.V. ENTERTAINMENT AREA.)
 5. N.E.C. 406.11 TAMPER RESISTANT RECEPTACLES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-13 Cont ID  
Sent By skennedy Date 2015-03-13 Time 08:15 Rev Time 0.00
Received By skennedy Date 2015-03-11 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-29 Cont ID  
Sent By sciard Date 2015-01-29 Time 11:21 Rev Time 0.00
Received By sciard Date 2015-01-21 Time 14:08 Sent To  
Notes
2015-01-21 14:08:33SENT TO ELECTRICAL BIN FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-11 Cont ID  
Sent By skennedy Date 2015-03-11 Time 16:40 Rev Time 0.00
Received By skennedy Date 2015-03-11 Time 16:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By jgomez Date 2015-01-21 Time 12:37 Rev Time 0.00
Received By jgomez Date 2015-01-21 Time 12:37 Sent To  
Notes
2015-01-21 12:44:46RESIDENTIAL (R3) ALTERATION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PLUMBING RISER DIAGRAM. SEC. 107.3.5.3 (11)
 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]