 |
Plan Review Details - Permit 15010430
| Plan Review Stops For Permit 15010430 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-04-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-10 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-04-10 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2015-04-10 12:04:19 | THIS MORNING THE ROOF DRAIN ISSUES IN THE STAIRWELL WAS | | | RESOLVED, WITH SCUPPERS AND EMERGENCY SCUPPERS, THE | | | PLUMBING PORTION OF THIS SUBMITTAL IS PULLED FROM THE | | | REVISION AND WILL BE REFILED UNDER REVISION # 11. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-03-18 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2015-04-09 09:14:20 | BUILDING PLAN REVIEW | | | REVISION: 15010430 | | | PERMIT: 14040379 | | | ADD: 2101 OKEECHOBEE BLVD. | | | CONT: HEDRICK BROTHERS | | | TEL: (561)568-8931 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE:APRIL 09/2015 | | | ACTION: DENIED | | | | | | 1) SHEET A-001. THIS COMMENT IS A RESULT OF THE | | | PLUMBING PLANS REVIEWER BRINGING TO MY ATTENTION THAT | | | THE EXIT ENCLOSURES STAIR # 1 & 3 SHOWING THE STAIRS | | | WITH THE ROOF DRAIN AND RISER WITHIN THE EXIT | | | ENCLOSURE. MONTHS AGO THE PLUMBING ENGINEER SPOKE WITH | | | ME ON THIS ISSUE THAT THE STARWAYS BEING ON THE | | | EXTERIOR CORNERS OR EXTERIOR WALL OF THE BUILDING DID | | | NOT HAVE TO HAVE THE WALL RATED AND INFACT COULD BE | | | OPEN. IN THAT REASONING WHY THE ROOF DRAIN WAS ALLOWED. | | | THE ARCHITECT OF RECORD STILL SHOWS THE EXIT ENCLOSURES | | | AS 1 HOUR FIRE RATED AND THE ONLY MATERIALS ALLOWED ARE | | | MATERIALS THAT ARE REQUIRED BY 2010 FBC-B 1022.4 | | | PENETRATIONS. | | | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT | | | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT | | | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT | | | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT | | | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING | | | THE EXIT ENCLOSURE AND TERMINATING AT A STEEL BOX NOT | | | EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH | | | PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH | | | SECTION 713. THERE SHALL BE NO PENETRATIONS OR | | | COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT, | | | BETWEEN ADJACENT EXIT ENCLOSURES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-02-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-02-12 |
Time |
13:33 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-02-07 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2015-02-07 10:08:54 | BUILDING PLAN REVIEW | | | REVISION: 15010430 | | | PERMIT: 14040379 | | | ADD: 2101 OKEECHOBEE BLVD. | | | CONT: HEDRICK BROTHERS | | | TEL: (561)568-8931 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: | | | ACTION: DENIED | | | | | | IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 | | | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED | | | ELECTRONICALLY | | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | | NAMING CONVENTION FOR EACH DOCUMENT | | | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT | | | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS | | | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES | | | AVAILABLE | | | | | | | | | 1A) A-101 & A-121 DETAILS 2 & 3 SHEET A-122 SHOWS NEW | | | CAR LIFTS, SHEET A-122 DETAIL 2 & 3 SHOW THESE LIFTS | | | WITH A PIT, THERE HAS BEEN NO STRUCTURAL | | | SHEETS IN THIS SUBMITTAL, NO DETAILS AS TO THE TYPE OF | | | LIFT, TRACTION OR HYDROLIC ETC. | | | | | | 1B) SHEET A-121 SHOWS THE FINISH FLOOR AS A FLOOR TILE, | | | A OIL SEPARATOR WAS NOT RREQUIRED BECAUSE OF THE | | | NON-ABSORBENT SURFACE OF THE TILE, THAT THE OILS AND | | | GREASE WERE TO BE CLEANED UP, THIS SHEET DOES NOT | | | INDICATE THE SURFACE FINISH OF THE AREA WALLS NOR | | | FLOOR. PLEASE PROVIDE COMPLIANCE WITH | | | 2010 FBC-B: 406.6.4 FLOOR SURFACE. | | | REPAIR GARAGE FLOORS SHALL BE OF CONCRETE OR SIMILAR | | | NONCOMBUSTIBLE AND NONABSORBENT MATERIALS. | | | EXCEPTION: SLIP-RESISTANT, NONABSORBENT, INTERIOR FLOOR | | | FINISHES HAVING A CRITICAL RADIANT FLUX NOT MORE THAN | | | 0.45 W/CM2, AS DETERMINED BY NFPA 253, SHALL BE | | | PERMITTED. | | | | | | | | | | | | | | | BUILDING PROVISO FROM ISSUED PLANS: | | | | | | 1) THE DESIGNER OF RECORD WOULD LIKE TO DEFER THE | | | PRODUCT APPROVALS AS A DEFERRED SUBMITTAL 2010 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1, ADMINISTRATION107.3.4.2. | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 | | | COMPONENTS & CLADDING | | | | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, RAINSCREEN PERFORATED CORRUGATED | | | METAL PANEL SYSTEM | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) PRE-ENGINEERED A/C STANDS | | | | | | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-03-25 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-03-25 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-03-25 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2015-03-25 10:04:31 | 2/25/2015 | | | PROJECT: BRAMAN AUDI | | | PERMIT#: 14040379, REVISION #15010430 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: APPROVED WITH EXCEPTION. | | | THE PLANS HAVE BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES PRIOR TO INSPECTION | | | WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT | | | OF RE-INSPECTION FEE(S). | | | | | | 1) SHEET E3.1.1 | | | A) NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE | | | PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER | | | PROTECTION. | | | B) NEC 110.3(B) PROVIDE EQUIPMENT SUBMITTALS ON | | | MOTORIZED BLINDS. VERIFY LISTING ON MOTORIZED BLINDS TO | | | VERIFY THEY ARE APPROVED FOR INSTALLATION AS SHOWN. | | | | | | 2) NEC 110.16 ADD NOTE: PROVIDE SAFETY LABELING FOR ARC | | | FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS. | | | | | | 3) NEC 511.10. BATTERY CHARGING EQUIPMENT. BATTERY | | | CHARGERS AND THEIR CONTROL EQUIPMENT, AND BATTERIES | | | BEING CHARGED, SHALL NOT BE LOCATED WITHIN LOCATIONS | | | CLASSIFIED IN NEC 511.3. | | | | | | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR SITE LIGHTING, FUEL DISPENSING, FIRE | | | ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, | | | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-02-03 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-02-03 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-02-03 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2015-02-03 14:32:27 | 2/3/2015 | | | PROJECT: BRAMAN AUDI | | | PERMIT#: 14040379, REVISION #15010430 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) SHEET E1.2 | | | NOTE 14 CALLS FOR A NEW WEATHERPROOF BOX AND EMPTY | | | CONDUIT WITH PULL STRING FOR CCTV CAMERAS. IF THE IDEA | | | HERE IS TO INSTALL CCTV CAMERAS ON THE LIGHT POLES, | | | PROVIDE A SEPARATE RACEWAY FOR THE CCTV CONDUCTORS IN | | | THE LIGHT POLE TO SEPARATE THEM FROM THE HIGH VOLTAGE | | | CONDUCTORS IN THE POLE FOR THE LIGHTS. | | | | | | 2) E2.1.1 | | | NEC 700.16 PROVIDE ADEQUATE EMERGENCY ILLUMINATION TO | | | EFFECTIVELY ILLUMINATE ALL MEANS OF EGRESS. | | | | | | 3) SHEET E3.1.1 | | | A) NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE | | | PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER | | | PROTECTION. | | | B) NEC 110.3(B) PROVIDE EQUIPMENT SUBMITTALS ON | | | MOTORIZED BLINDS | | | | | | 4) SHEET E4.1 | | | NEC 110.26 (C)(3) WHERE EQUIPMENT RATED 1200 A OR MORE | | | THAT CONTAINS OVERCURRENT DEVICES, SWITCHING DEVICES, | | | OR CONTROL DEVICES IS INSTALLED AND THERE IS A | | | PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS | | | FROM THE WORKING SPACE LESS THAN 25? FROM THE NEAREST | | | EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL OPEN IN | | | THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC | | | BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE | | | NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. | | | REVISE THE MOUTH ELECTRICAL ROOM DOOR TO BE EQUIPPED | | | WITH PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT | | | ARE NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. | | | | | | 5) SHEET E6.1 | | | PANEL L1AA INDICATES A TOTAL CONNECTED LOAD OF 72.5 KVA | | | ON A 120/208V 3PHASE WYE 200AMP OCPD AND FEEDER. | | | 72.5KVA / 208V, 3PH (X1.732) IS JUST OVER 200AMP. | | | REVISE THE PANEL SCHEDULE AND LOADS ON THE PANEL TO | | | ALLEVIATE THE OVERLOAD CONDITION. | | | | | | 6) NEC 110.9 VERIFY THE ELECTRICAL SERVICE | | | DISCONNECTING MEANS HAS A FAULT CURRENT RATING THAT IS | | | SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT | | | THAT MUST BE INTERRUPTED. | | | | | | 7) NEC 110.16 ADD NOTE: ?PROVIDE SAFETY LABELING FOR | | | ARC FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS.? | | | 8) NEC 511.10 BATTERY CHARGING EQUIPMENT. BATTERY | | | CHARGERS AND THEIR CONTROL EQUIPMENT, AND BATTERIES | | | BEING CHARGED, SHALL NOT BE LOCATED WITHIN LOCATIONS | | | CLASSIFIED IN NEC 511.3. | | | | | | 9) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR SITE LIGHTING, FUEL DISPENSING, FIRE | | | ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, | | | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-03-05 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-03-05 |
Time |
14:53 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-04-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-04-21 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-04-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-04-10 18:33:20 | SENT TO T LARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-04-09 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-04-09 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2015-04-07 09:56:15 | SENT TO T. K. LARGES' DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-03-26 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-03-26 |
Time |
06:40 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-03-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-03-17 06:44:37 | SENT TO C30. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-03-05 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-03-05 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-01-15 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2015-03-05 15:19:40 | FILED LARGE UNDER "H". | | 2015-01-15 16:55:34 | SENT TO C-26. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-03-20 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-03-20 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-03-20 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2015-03-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2015-03-02 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2015-03-02 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2015-04-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-04-11 |
Time |
06:10 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-04-11 |
Time |
05:54 |
Sent To |
|
|
| Notes |
| 2015-04-11 05:51:58 | A MEETING WAS HELD ON 4/10/15 WITH DOUG SNYDER ( | | | ARCHITECT OF RECORD ), ERIC HIMMEL ( CONTRACTOR HEDRICK | | | BROS) , DOUG HARVEY ( ABO), JIM WITMER AND TIM LARGE. | | | THE ISSUE INVOLVING THE 3" RAINWATER RISER IN THE | | | STAIRWELLS #1 & #3 HAS BEEN RESOLVED AND ROOF SCUPPERS | | | WILL BE INSTALLED ON THE ROOF OF THE STAIRWELL. THE | | | ROOF DRAIN WILL BE CAPPED OFF. THE PLUMBING SHEETS HAVE | | | BEEN REMOVED FROM THIS REVISION AND WILL BE RESUBMITTED | | | UNDER THEIR REVISION # 11. T.LARGE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-04-09 |
Time |
06:51 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-04-08 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2015-04-09 06:14:21 | 1) SHT. P.5.2 - THE RAINWATER RISER FOR THE SHOWROOM | | | AREA DOES NOT MATCH THE PLAN VIEW ON P2.1.1. ONE | | | SECTION SHOWS A WYE CONNECTION ABOVE GROUND AND THE | | | RISER SPLITTING INTO TWO HORIZONTAL BRANCES ON THE PLAN | | | VIEW ON P2.1.1 AND THE SAME SECTION IS SHOWN AS ONE | | | LINE RISING UP AND COLLECTING 4 ROOF DRAINS. CLARIFY. | | | 2) SHT. P2.1.2.- THERE ARE TWO 4" RAINWATER BRANCHES | | | THAT JUST END AND HAVE NO CONNECTION TO ROOF DRAINS OR | | | SHOW A NOTE DETAILING CONTINUATION POINTS. THESE LINES | | | ARE LOCATED IN THE PARTS AREA #135. I HAVE HIGHLIGHTED | | | AND CLOUDED THE AREA IN RED. ONE TERMINATES NEAR GRID | | | LINE G-2.2 AND THE OTHER IS BY GRID LINE F-1 BY STAIR | | | #2. CLARIFY. 2ND REQUEST. | | | 3) SHT.P2.1.3. - THE TRANSAIR ALUMINUM PIPE THAT IS | | | CALLED OUT ON THE PLAN IS SHOWN AS BEING INSTALLED | | | UNDERGROUND. I HAVE RESEARCHED THE PIPNG AND IT APPEARS | | | IT MAY ONLY BE APPROVED FOR ABOVE GROUND INSTALLATION. | | | SUBMIT VERIFICATION FROM THE MANUFACTURER THAT IT IS | | | APPROVED FOR UNDERGROUND INSTALLATION. THIS CAN BE A | | | DEFERRED SUBMITTA.WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 4) SHT. P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP | | | ABOVE CEILING BUT THERE IS NOTHING SHOWN. I HAVE | | | HIGHLIGHTED THE AREA OF ISSUE.THERE IS A NOTE THAT ALSO | | | STATES" SEE SHT. P2.1.2 FOR CONTINUATION" BUT NOTHING | | | IS SHOWN ON SHT. P2.1.2.CLARIFY. 2ND REQUEST. | | | 5) SHT.P2.1.2. - SHOWS A 3" RAINWATER LEADER IN STAIR | | | ENCLOSURE # 3 AND ALSO IN STAIR #1 . I HAVE REVIEWED | | | YOUR RESPONSE TO MY COMMENT. THE ARCHITECT OF RECORD | | | HAS RATED BOTH OF THESE ENTIRE ENCLOSURES AS ONE HOUR | | | ON SHT.A-001. THE RAINWATER PIPING CANNOT PENETRATE ANY | | | WALLS OF THESE RATED ENCLOSURES PER 2010 FBC 1022.4. | | | THIS CODE SECTION DOES NOT JUST APPLY TO ADJACENT | | | SPACES OR ENCLOSURES.IF THE 3" RAINWATER RISER ENTERS | | | THE ENCLOSURES FROM UNDERGROUND THROUGH THE GROUND | | | FLOOR SLAB OF THE ENCLOSURE, THEN THERE IS NOT AN ISSUE | | | BUT THAT IS NOT WHAT THE RAINWATER RISER ON SHT. P5.2 | | | DEPICTS OR THE PLAN VIEWS ON P2.1.1 OR P2.1.2. IF THIS | | | IS SUCH THE CASE, THEN CLEARLY IDENTIFY THIS ON BOTH | | | SHEETS. SHT. 5.2 SHOWS THIS 3" LINE CONNECTING TO THE | | | STORM DRAIN LINE BELOW THE ROOF SLAB, NOT UNDERGROUND. | | | CLARIFY. | | | | | | PLEASE CONTACT ME AT THE NUMBER BELOW TO SET UP AN | | | APPOINTMENT OR TO DISCUSS THE COMMENTS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-03-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-03-26 |
Time |
06:39 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-03-21 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2015-03-25 15:24:50 | 1) SUBMIT A RISER DIAGRAM FOR THE RAINWATER SYSTEM.WPB | | | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. | | | 2) SHT. P2.1.2 - THERE IS A 4" RAIN WATER LEADER IN THE | | | PARTS AREA 3 135 THAT TERMINATES NOWHERE. CLARIFY. | | | 3) SHT. P5.1 - SIZE THE VENT FOR THE HANDICAP WATER | | | CLOSET IN THE MEN'S RESTROOM # 112. | | | 4) THE 3" VTR'S FOR THE SHOWROOM AND SERVICE AREA | | | REDUCE FROM 3" TO 2" .CLARIFY. | | | 5) SHT.P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP | | | ABOVE CEILING BUT NOTHING IS SHOWN. CLARIFY. | | | 6) SHT. P2.1.2 - SHOWS A 4" RAINWATER LINE WITH NO | | | TERMINATION POINT AND ALSO SHOWS A 4" RAINWATER LEADER | | | WITH 870 SQ. FT. WITH NO TERMINATION POINT.SEE PARTS | | | AREA PLAN.CLARIFY. | | | 7) SUBMIT A CONDENSATE RISER DIAGRAM. SHOW ALL PIPE | | | SIZES. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 8) SHT. P2.1.2 - THERE IS A CONDENSATE BRANCH NEAR THE | | | EXTERIOR WALL IN THE SERVICE ARE BY GRID LINE 5F THAT | | | GOES NOWHERE. CLARIFY. | | | 9) SUBMIT A REVISED RAINWATER RISER DIAGRAM THAT | | | CLEARLY REFLECTS ALL THE CHANGES TO THE STORWATER | | | PIPING SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3. | | | 10) SHT.P2.1.2 - SIZE THE CONDENSATE LINE EXITING THE | | | BUILDING . | | | 11) SHT.P2.1.3 - INDICATE THE TYPE OF PIPING BEING | | | UTILIZED FOR THE COMPRESSED AIR SYSTEM. PVC IS NOT | | | APPROVED TO BE USED FOR COMPRESSED AIR. | | | 12) SHT.P2.1.3 - THE UNDERGROUND COMPRESSED AIR AND THE | | | WATER LINES ARE NOT SHOWN CONTINUING ON SHT. P2.1.2. | | | CLARIFY. | | | 13) SHT. P2.1.3 - SHOWS A 1" COMPRESSED AIR LINE | | | ENTERING AN AREA THAT COULD BE THE COMRESSOR ROOM # | | | 143. IF SO, IDENTIFY THE LINE AS SUCH. | | | 14) SHT. P2.1.2 - LOCATION OF EYEWASH AT EQUIPMENT | | | STORAGE AREA # 145 SHOWN ON RISER DOES NOT CORRELATE | | | WITH THE RSANITARY TISER ON SHT.P5.1. | | | 15) SHT.P2.1.2 - SHOWS A 3" RAINWATER LEADER IN STAIR | | | ENCLOSURE # 3. PENETRATIONS INTO AND OPENINGS THROUGH | | | AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT AS PROVIDED IN | | | 2010 FBC SEC.1022.4. | | | 16) SUPPLY CONFIRMATION FROM SCHIER PRODUCTS THAT THE | | | OIL/SAND CALCULATIONS HAVE BEEN REVIEWED AND THAT THE | | | SIZE OF THE INTERCEPTOR IS SIZED PROPERLY.2010 FPC | | | SEC.1003.2. YOU CAN CONTACT LEE SCHNEEWEISS AT | | | 1-800-538-4792 & [email protected]. I HAVE CALCULATED | | | THE SQUARE FOOTAGE OF THIS AREA FROM SHT.A114 AND THE | | | RESULT I HAVE IS APPROXIMATELY 1900 SQ. FEET WHICH IS | | | HIHER THAN YOUR CALCULATIONS. | | | 17.) SUBMIT SPECIFICATIONS FOR THE AIR COMPRESSORS. WPB | | | AMEND. TO 2010 FBC SEC.107.2.1. | | | 18) SHT.P3.1.2 - THE NUMBER OF COMPRESSED AIR OULETS DO | | | NOT CORRELATE WITH SHT.P6.1. THERE ARE 2 ADDITIONAL | | | OUTLETS ON THE COMPRESSED AIR RISER. CLARIFY. | | | 19) SHT. P5.1 - THE HANDICAPPPED LAVATORY IN THE MEN'S | | | RESTROOM #141 IS NOT SHOWN ON THE SANITARY RISER. | | | CLARIFY. | | | 20) SHT. P6.1 - THE WATER RISER ON P6.1 DOES NOT | | | CORRELATE WITH SHT.P3.1.2. ( SERVICE AREA DOMESTIC | | | WATER PLAN ) CLARIFY. | | | 21) SHT.P6.1 - WATER RISER - THE NUMBER OF HOSE BIBBS, | | | THE LAYOUT OF THE HOSE BIBBS, WHERE THE WATER MAUN | | | ENTERS THE BUILDING DOES NOT SEEM TO CORRELATE WITH | | | SHT. P3.1.2. | | | 22) SHT. P6.1 SHOWS AN 1 1/2" LINE TO SK-2. IS THIS | | | CORRECT? | | | 23) SHT. P6.1 - THE WATER LINE GOES FROM 2 1/2" TO 2" | | | THEN BACK TO 2 1/2" AGAIN. CLARIFY. SEE AREA AT MEN'S | | | RESTROOM #112. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-01-29 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-01-29 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-28 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2015-01-29 06:10:33 | 1) TRENCH DRAINS SHALL COMPLY WITH ASME 112.6.3 PER THE | | | 2010 FL. PLBG. CODE SEC.412.1. SUBMIT DOCUMENTATION TO | | | SHOW COMPLIANCE. | | | 2) SHT.P2.1.2. HAS ARROWS INDICATING AN UNDERGROUND | | | STORM DRAIN BUT NO PIPING IS SHOWN ON THE PLAN.SUBMIT | | | DRAWINGS THAT CLEARLY REFLECT THE PIPING AND THE SCOPE | | | OF WORK TO BE DONE. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 3) THE CONDENSATE LINES ON THE PLAN ARE VERY LIGHT AND | | | DIFFICULT TO READ. THESE WILL NOT SHOW WHEN THE PLANS | | | ARE SCANNED FOR RECORD RETENTION. THE CONDENSATE LINES | | | AND ALL OTHER PIPING ON THE PLUMBING PLANS SHALL BE | | | CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. | | | 4) SHT.P2.1.2. - SHOWS P-TRAPS ON CONDENSATE LINES BUT | | | THE PLAN DOES NOT SHOW TO WHAT THEY ARE CONNECTED. | | | CLARIFY. | | | 5) THERE ARE NOTES & ARROWS ALL OVER THE PLANS ( | | | P2.1.2, P2.1.3, P3.1.2) IDENTIFYING ITEMS BUT NOTHING | | | IS SHOWN AT THE LOCATION,E.G. STORM DRAIN LINE, RAIN | | | WATER LEADERS, 4" STORM DRAIN LINE, BFP DEVICE, 3" VENT | | | BELOW GRADE, ETC. WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SHT. P2.1.3 - CALLS OUT A 4" SANITARY LINE | | | DISCHARGING INTO THE OIL/SAND SEPARATOR. WHAT | | | DISCHARGES INTO THIS LINE? SANITARY LINES SHALL NOT | | | DISCHARGE INTO THE SEPARATOR. WASTES THAT DO NOT | | | REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED | | | INTO ANY INTERCEPTOR OR SEPARATOR. 2010 1003.2. PLANS | | | REFER TO "BROADWAY EQUIPMENT PLANS." CLARIFY. | | | 7) INDICATE THE TYPE OF PIPE MATERIAL BEING USED FOR | | | THE COMPRESSED AIR SYSTEM. PVC PIPING CANNOT BE USED | | | FOR COMPRESSED AIR PER MANUFACTURER'S SPECIFICATIONS. | | | FPC SEC.303.2 | | | 8) SHT.P2.1.3 - CLEANOUTS SHALL BE INSTALLED IN THE | | | TRENCH DRAIN SYSTEM PER THE 2010 FPC SEC. 708. | | | 9) CLEARLY IDENTIFY ALL PIPE LINES ON THE PLANS, AND | | | SIZE ALL LINES. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | 10) SHT.P5.1 - THERE ARE LINES INTO THE INTERCEPTOR | | | THAT HAVE NO BEGINNING POINT ( 3" & 4" LINES). CLARIFY. | | | 11) SHT. P5.1 - A LAVATORY IN THE WOMEN'S RESTROOM IS | | | MISSING FROM THE SANITARY RISER FOR THE SERVICE AREA.. | | | 12) SHT. P6.1 - THE DOMESTIC WATER RISER IS SO LIGHT ON | | | THE PLANS IT IS ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE | | | DRAWINGS THE REFLECT THE SCOPE OF WORK.WPB AMEND. TO | | | 2010 FBC SEC.107.2.1. | | | 13) SHT. P6.1 - THE COMPRESSED AIR RISER IS SO LIGHT ON | | | THE PLANS IT IS ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE | | | DRAWINGS THE REFLECT THE SCOPE OF WORK.WPB AMEND. TO | | | 2010 FBC SEC.107.2.1. | | | 14) SHT. P5.1 - THERE IS A LAVATORY MISSING ON THE | | | SERVICE AREA SANITARY RISER. | | | 15) THE SANITARY PIPING FOR THE EMERGENCY | | | EYEWASH/SHOWER ON THE RISER DOES NOT CORRELATE WITH THE | | | FLOOR PLAN. CLARIFY. | | | 16) THE WASTE LINES SHOWN ON THE RISER BY THE OIL/SAND | | | SEPARATOR ARE NOT SHOWN ON SHT. P2.1.2.CLARIFY. | | | 17) PLEASE ASSEMBLE THE PLANS INTO TWO COMPLETE SETS OF | | | PLANS WITH THE SHEETS BOUND TOGETHER. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-04-20 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-04-20 |
Time |
19:05 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2015-04-20 |
Time |
19:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-02-25 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-02-25 |
Time |
14:30 |
Rev Time |
2.00 |
| Received By |
eschneid |
Date |
2015-02-24 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2015-02-25 15:34:22 | FAILED | | | | | | 1) THE SERVICE AREA SHOWS THREE ADDITIONAL SERVICE BAYS | | | FROM THE CURRENTLY APPROVED PLANS. THEY THREE | | | ADDITIONAL BAYS (37 TOTAL) REQUIRE THE PROVISION OF ONE | | | ADDITIONAL PARKING SPACE. A REVISED SHEET A-101 WHICH | | | SHOWS THE CORRECT SERVICE BAY AND PARKING COUNTS IS | | | REQUIRED. PLEASE NOTE THAT THIS WILL ALSO NEED TO BE | | | REFLECTED ON THE PLANS FOR THE RECENTLY SUBMITTED MINOR | | | PD AMENDMENT. | | | | | | REMAINDER OF REVISED SHEETS COMPLY WITH ZONING. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2015-02-10 10:32:23 | 2/10/15 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |