Plan Review Details - Permit 15010402
Plan Review Stops For Permit 15010402
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-11 Cont ID  
Sent By jwitmer Date 2015-05-11 Time 10:40 Rev Time 0.00
Received By jwitmer Date 2015-05-11 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-25 Cont ID  
Sent By jwitmer Date 2015-04-25 Time 06:38 Rev Time 0.00
Received By jwitmer Date 2015-04-25 Time 06:01 Sent To  
Notes
2015-04-25 06:38:12BUILDING PLAN REVIEW
 PERMIT: 15010402
 ADD: 255 EVERNIA ST # 1405
 CONT: BLUEWATER BUILDERS
 TEL: (954)753-7233
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. APRIL 25/ 2015
 ACTION: DENIED
  
 NOTICE!!!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
 NOTICE: SUBMIT TEST REPORTS TO THE DESIGNER OF RECORD
 FOR REVIEW BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT.
  
 1) 2ND REQUEST, SUPPLY THE ASTM E-90 TEST REPORT FOR
 FLOOR INSULATION. SHEET A152 SHOWS AN EXISTING SINGLE
 ENTRY, SHEET A201 SHOWS A NEW PORTION OF THE CORRIDOR,
 A LOBBY AREA AND 2 NEW ENTRIES TO (2) NEW R2 UNITS. THE
 PLANS INDICATE EITHER A WALL IDENTIFICATION TAG 1 OR 2.
 SHEET A903 SHOWS BOTH WALLS AS 1 HOUR FIRE RATED WALLS,
 BOTH DETAILS ARE MISSING COMPLIANCE WITH:
 2010 FBC-B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 2) 2ND REQUEST, SUPPLY THE ASTM E-90 TEST REPORT FOR
 FLOOR INSULATION. SHEET A152 NOTE # 3 INDICATES TO
 REMOVE ALL FLOOR TILE AND GROUT. SHEET A202 SHOW NEW
 FLOOR TILE BUT THERE IS NO NOTES ABOUT THE FLOOR
 FINISHES. PLEAS PROVIDE COMPLIANCE WITH :
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3) 2ND REQUEST SUPPLY THE TEST REPORT FOR FLAME SPREAD.
 2010 FBC-B 603.2.EXCEPTION (2) INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 4) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By jwitmer Date 2015-01-26 Time 09:05 Rev Time 0.00
Received By jwitmer Date 2015-01-26 Time 09:05 Sent To  
Notes
2015-01-26 09:05:26BUILDING PLAN REVIEW
 PERMIT: 15010402
 ADD: 255 EVERNIA ST # 1405
 CONT: BLUEWATER BUILDERS
 TEL: (954)753-7233
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 26/ 2015
 ACTION: DENIED
  
 1) SHEET A152 SHOWS AN EXISTING SINGLE ENTRY, SHEET
 A201 SHOWS A NEW PORTION OF THE CORRIDOR, A LOBBY AREA
 AND 2 NEW ENTRIES TO (2) NEW R2 UNITS. THE PLANS
 INDICATE EITHER A WALL IDENTIFICATION TAG 1 OR 2. SHEET
 A903 SHOWS BOTH WALLS AS 1 HOUR FIRE RATED WALLS, BOTH
 DETAILS ARE MISSING COMPLIANCE WITH:
 2010 FBC-B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 2) SHEET A152 NOTE # 3 INDICATES TO REMOVE ALL FLOOR
 TILE AND GROUT. SHEET A202 SHOW NEW FLOOR TILE BUT
 THERE IS NO NOTES ABOUT THE FLOOR FINISHES. PLEAS
 PROVIDE COMPLIANCE WITH :
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2010 FBC-B 603.2.EXCEPTION (2) INSULATION INSTALLED
 BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT
 INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 3) SHEET A152 NOTE # 7 INDICATES REMOVE EXISTING
 DRYWALL CEILING AND FRAMING. SHEET A301 SHOWS NEW G. W.
 B. CEILINGS BUT THERE IS NO INFORMATION AS TO WHAT THE
 NEW FRAMING MEMBERS ARE CONSTRUCTED FROM, SIZE, NOR
 GAUGE OF MATERIAL, ALLOWABLE SPANS AND SPACING BETWEEN
 FRAMING MEMBERS, ATTACHMENT TO THE CONCRETE DECK ABOVE
 NOR THE THICKNESS OF THE NEW G. W. B. CEILINGS OR TYPE
 OF WALL BOARD.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: CEILING
 SYSTEMS.
  
 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT
 SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288
 OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By rlecky Date 2015-02-05 Time 13:33 Rev Time 0.00
Received By rlecky Date 2015-02-05 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-20 Cont ID  
Sent By pleduc Date 2015-01-20 Time   Rev Time 0.00
Received By pleduc Date 2015-01-20 Time 15:13 Sent To  
Notes
2015-01-20 15:13:41THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A 251, LIFE SAFETY PLAN, INDICATES NON-CURRENT
 CODE REFERENCES.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 CURRENT FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012
 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE
 CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-23 Cont ID  
Sent By lmarchan Date 2015-07-23 Time 09:51 Rev Time 0.00
Received By lmarchan Date 2015-07-21 Time 09:50 Sent To  
Notes
2015-07-23 09:51:20IN-STOP PLACED IN ERROR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-11 Cont ID  
Sent By jwitmer Date 2015-05-11 Time 10:41 Rev Time 0.00
Received By jwitmer Date 2015-05-08 Time   Sent To  
Notes
2015-05-08 18:29:10SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-25 Cont ID  
Sent By jwitmer Date 2015-04-25 Time 06:38 Rev Time 0.00
Received By jwitmer Date 2015-04-10 Time   Sent To  
Notes
2015-04-10 18:44:20B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-07 Cont ID  
Sent By hmoser Date 2015-03-07 Time 13:32 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 18:31 Sent To  
Notes
2015-01-14 18:32:01B16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-23 Cont ID  
Sent By hmoser Date 2015-04-23 Time 09:41 Rev Time 0.00
Received By hmoser Date 2015-04-23 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-07 Cont ID  
Sent By hmoser Date 2015-03-07 Time 13:31 Rev Time 0.00
Received By hmoser Date 2015-03-07 Time 12:56 Sent To  
Notes
2015-03-07 13:31:36PLAN DENIED
 1) REFER TO SECTION 304.1 GENERAL
 PROVIDE A COPY OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS
 FOR THE CLOTHES DRYER 2010 FBC (M)
 2) SECTION 504.6.4.1 SPECIFIED LENGTH EXCEPTION PERMITS
 BOOSTER FANS . HOWEVER WEST PALM BEACH FIRE RESCUE
 DOES NOT. IN THE 5TH EDITION 2014 OF THE FLORIDA CODES
 THE EXCEPTION FOR CLOTHES DRYER BOOSTER FANS HAS BEEN
 DELETED.
 3) REFER TO SECTION 602.2.1 MATERIALS WITH IN PLENUM'S.
 2010 FBC (M) INCLUDING A/C CLOSET DOORS AND CONDENSATE
 LINES.
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR MASTER
 BEDROOM
 TO SMALL, BEDROOM 2,3 LOOK LIKE THEY ARE JUMPING IN TO
 EACH OTHER
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-24 Cont ID  
Sent By tklarge Date 2015-01-24 Time 10:25 Rev Time 0.00
Received By tklarge Date 2015-01-24 Time 10:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-03 Cont ID  
Sent By aaponte Date 2015-02-03 Time 14:48 Rev Time 0.00
Received By aaponte Date 2015-02-03 Time 14:48 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved