Plan Review Details - Permit 15010313
Plan Review Stops For Permit 15010313
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-02-24 Cont ID  
Sent By mmanhong Date 2015-02-24 Time 12:18 Rev Time 0.00
Received By mmanhong Date 2015-02-24 Time 12:18 Sent To  
Notes
2015-02-24 12:18:18OKAY PER STEVEN KENNEDY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-24 Cont ID  
Sent By mmanhong Date 2015-02-24 Time 12:17 Rev Time 0.00
Received By mmanhong Date 2015-02-24 Time 12:17 Sent To  
Notes
2015-02-24 12:17:53OKAY PER STEVE KENNEDY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By misc2 Date 2015-02-10 Time 10:29 Rev Time 0.00
Received By dhayes Date 2015-02-10 Time 10:27 Sent To B
Notes
2015-02-10 12:06:482/10/2015
 PROJECT: AVALON
 PERMIT#: 15010313
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 600.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION.
  
 2) NEC 600.6(A)(1) LOCATION.
 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR
 OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL
 OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS.
  
 3) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS.
  
 4) FBC, WPB AMENDMENTS 107.2.1
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471,
 668.001-668.006
  
 5) WPB AMENDMENTS FBC 109.3
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. PROVIDE ACTUAL VALUE OF ALL INCLUSIVE
 INSTALLATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-24 Cont ID  
Sent By mmanhong Date 2015-02-24 Time 12:18 Rev Time 0.00
Received By mmanhong Date 2015-02-24 Time 12:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-01-22 Cont ID  
Sent By sgraham Date 2015-01-22 Time 15:29 Rev Time 0.00
Received By sgraham Date 2015-01-22 Time 15:29 Sent To B
Notes
***NONE***