Plan Review Details - Permit 15010279
Plan Review Stops For Permit 15010279
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By jwitmer Date 2015-02-03 Time 06:28 Rev Time 0.00
Received By jwitmer Date 2015-02-03 Time 05:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By jwitmer Date 2015-01-14 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2015-01-14 Time 09:37 Sent To  
Notes
2015-01-14 10:02:15BUILDING PLAN REVIEW
 PERMIT: 15010279
 ADD: 415 S DIXIE HWY
 CONT: SOUTH FLORIDA BUILDING SERVICES
 TEL: (561)644-1581
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN.14/ 2015
 ACTION: DENIED
  
 1) SHEET 1 INDICATES A NEW EGRESS CORRIDOR 4'-1" WIDE
 THE MINIMUM REQUIRED WIDTH FOR EGRESS IS 4'-6" 2010
 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A MEANS
 OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY,
 OR LANDING, NOR PROJECT MORE THAN 7 INCHES (178 MM)
 INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN. THIS SAME
 DIMENSION IS REQUIED UNDER THE 2010 FLORIDA
 ACCESSIBILITY CODE SEE FIGURE 404.2.4.1 (I).
  
 2) PLEASE REVIEW THE REAR DOOR VERSES WHERE THE
 ACCESIBLE RAMP STARTS TO DECLINE. 2010 FLORIDA
 ACCESSIBILITY CODE SEE FIGURE 404.2.4.1 (I) REQUIRES 24
 INCHES CLEAR SPACE BEFORE THE START OF THE RAMP. THE
 SECOND ISSUE IS THE RAMP IS 54 INCHES WIDE, IN
 REVIEWING THE REQUIRED WIDTH TO MAKE A TURN AT THE DOOR
 FIGURE 404.2.4.1(I) REQUIRES A MINIMUM OF 54" CHANGE OF
 DIRECTION FOR RAMPS REQUIRES A MINIMUM OF 60 INCHES SEE
 405.7.4. THE 60 INCHES WILL NEED TO ALIGN WITH THE 24
 INCHES LATCH SIDE OF DOOR.
  
 3) THE BACK RAMP DOES NOT SHOW A CODE COMPLIANT BOTTOM
 LANDING SEE 2010 FL ACC CODE 405.7.3 , PLEASE NOTE THAT
 AT THE BOTTOM OF THE RAMP THE PLANS INDICATE THE USE OF
 DETECTABLE WARNINGS. PLEASE SEE 2010 FL ACCESS. CODE
 SECTION CURB RAMPS SUBJECT TO DEPARTMENT OF
 TRANSPORTATION REGULATION 49 CFR 37.21 SHALL HAVE A
 DETECTABLE WARNING COMPLYING WITH 705. THIS IS THE ONLY
 TIME DETECTABLE WARNINGS ARE TO BE USED, WHEN CROSSING
 STREETS!!!!
  
 4) THE BACK RAMP WILL ALSO NEED TO PROVIDE HANDRAIL
 SINCE IT IS OVER 6 FEET LONG. 2010 FL ACC CODE 405.8
 HANDRAILS. RAMP RUNS WITH A RISE GREATER THAN 6 INCHES
 (150 MM) SHALL HAVE HANDRAILS COMPLYING WITH 505. 505.2
 WHERE REQUIRED. HANDRAILS SHALL BE PROVIDED ON BOTH
 SIDES OF STAIRS AND RAMPS. 505.3 CONTINUITY., 505.4
 HEIGHT., 505.10 HANDRAIL EXTENSIONS. & 505.10.1 TOP,
 BOTTOM EXTENSION AT RAMPS AND EDGE PROTECTION 405.9.
  
 5) THE FRONT RAMP:
 5A) THE PLANS ARE NOT INDICATING COMPLIANCE WITH THE
 REQUIED BOTTOM LANDING SEE 2010 FL ACCESS CODE 405.7.3
 , , PLEASE NOTE THAT AT THE BOTTOM OF THE RAMP THE
 PLANS INDICATE THE USE OF DETECTABLE WARNINGS. PLEASE
 SEE 2010 FL ACCESS. CODE SECTION CURB RAMPS SUBJECT TO
 DEPARTMENT OF TRANSPORTATION REGULATION 49 CFR 37.21
 SHALL HAVE A DETECTABLE WARNING COMPLYING WITH 705.
 THIS IS THE ONLY TIME DETECTABLE WARNINGS ARE TO BE
 USED, WHEN CROSSING STREETS!!!!
  
 5B) THE PLANS ONLY SHOW A HANDRAIL ON THE EXTERIOR SIDE
 OF THE RAMP, HANDRAILS & EDGE PROTECTION WILL BE
 REQUIRED FOR BOTH SIDES OF THE PROPOSED RAMP.
 2010 FL ACCESS CODE 505.2 WHERE REQUIRED. HANDRAILS
 SHALL BE PROVIDED ON BOTH SIDES OF STAIRS AND RAMPS.
 505.3 CONTINUITY., 505.4 HEIGHT., 505.10 HANDRAIL
 EXTENSIONS. & 505.10.1 TOP, BOTTOM EXTENSION AT RAMPS
 AND EDGE PROTECTION 405.9.
  
 5C) THE PLANS INDICATE THE MID LANDING BEING 7'-2 "
 WIDE. THE 2010 FBC-B 1010.5.1. THE CLEAR WIDTH OF A
 RAMP BETWEEN HANDRAILS, OR OTHER PERMISSIBLE
 PROJECTIONS SHALL BE 36 INCHES (914 MM) MINIMUM. WITH
 THE WIDTH OF THE HANDRAILS AND THE REQUIRED DISTANCE TO
 SET THE RAILING FROM THE EDGE WILL BE GREATER THAN THE
 PROPOSED 7'-2".
  
 5D) THE PLAN DOES NOT PROVIDE THE DISTANCE FROM THE
 BUILDING TO THE SIDE OF THE TOP RAMP. WITH THIS AS A
 UNKNOWN AND THE PLANS ALSO ARE MISSING THE PROJECTION
 FROM THE BUILDING FOR THE TOP LANDING. THE MANEUVERING
 CLEARANCES FOUND ON THE 2010 FL ACCESS CODE FIGURE
 FIGURE 404.2.4.1(E) A MINIMUM OF 42 INCHES PST THE DOOR
 WILL BE REQUIRED, AS WELL AS THE REQUIREMENT FOR CHANGE
 OF DIRECTION 495.7.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-01-13 Cont ID  
Sent By skennedy Date 2015-01-13 Time 13:59 Rev Time 0.00
Received By skennedy Date 2015-01-13 Time 13:59 Sent To  
Notes
2015-01-13 13:59:55NONE SHOWN.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By cranford Date 2015-01-26 Time 10:04 Rev Time 0.00
Received By cranford Date 2015-01-26 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-02-05 Time   Rev Time 0.00
Received By pleduc Date 2015-02-05 Time 14:32 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-16 Cont ID  
Sent By pleduc Date 2015-01-16 Time   Rev Time 0.00
Received By pleduc Date 2015-01-16 Time 11:30 Sent To  
Notes
2015-01-16 16:48:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE REVIEW AND ADDRESS COMMENTS OF THE BUILDING
 DEPARTMENT AS THE PROPOSED ALSO DOES NOT MEET THE
 FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 7,
 MEANS OF EGRESS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-02-05 Time   Rev Time 0.00
Received By pleduc Date   Time   Sent To  
Notes
2015-01-30 14:44:08INCOMING SENT TO J. W. DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-22 Cont ID  
Sent By tklarge Date 2015-01-22 Time 12:46 Rev Time 0.00
Received By tklarge Date 2015-01-13 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-22 Cont ID  
Sent By tklarge Date 2015-01-22 Time 12:45 Rev Time 0.00
Received By tklarge Date 2015-01-22 Time 12:45 Sent To  
Notes
***NONE***