Plan Review Details - Permit 15010183
Plan Review Stops For Permit 15010183
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-20 Cont ID  
Sent By skennedy Date 2015-01-20 Time 09:01 Rev Time 0.00
Received By skennedy Date 2015-01-20 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-13 Cont ID  
Sent By hmoser Date 2015-01-13 Time 09:27 Rev Time  
Received By hmoser Date 2015-01-08 Time   Sent To  
Notes
2015-01-09 07:56:20INCOMING SENT TO J. GOMEZ DESK. JW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-01-20 Cont ID  
Sent By skennedy Date 2015-01-20 Time 09:01 Rev Time 0.00
Received By skennedy Date 2015-01-20 Time 09:01 Sent To  
Notes
2015-01-20 09:04:54REVISION WAS CORRECTED TO SHOW 16 SEER EQUIPMENT WAS
 INSTALLED. INSPECTION RECORD ONLY INDICATED R/A DUCT TO
 GUEST SUITE WAS CHANGED FROM 12" TO 10". THE REVISED
 PLAN IS CONSISTANT WITH THE ORIGINAL PLAN. THE ONLY
 CHANGE IS THE AFORMENTIONED DUCT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-01-13 Cont ID  
Sent By hmoser Date 2015-01-13 Time 09:27 Rev Time 0.00
Received By hmoser Date 2015-01-13 Time 09:16 Sent To  
Notes
2015-01-13 09:27:33REVISION DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 GUEST SUITE.
 2) PROVIDE DUCT SIZE ON DUCT GOING TO GUEST SUITE
 3) ENERGY CALCULATION CALL FOR A 16 SEER PLAN
 SHOWS 14 SEER REVISE ENERGY CALCULATION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 651-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-01-13 Cont ID  
Sent By jgomez Date 2015-01-13 Time 08:38 Rev Time 0.00
Received By jgomez Date 2015-01-13 Time 07:34 Sent To  
Notes
2015-01-13 08:38:49REVISION SENT TO HAROLD MOSER FOR REVIEW. JG.