Plan Review Details - Permit 15010129
Plan Review Stops For Permit 15010129
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-02 Cont ID  
Sent By jwitmer Date 2015-02-02 Time 17:28 Rev Time 0.00
Received By jwitmer Date 2015-02-02 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-20 Cont ID  
Sent By jwitmer Date 2015-01-20 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2015-01-20 Time 08:46 Sent To  
Notes
2015-01-20 08:57:37BUILDING PLAN REVIEW
 PERMIT: 15010129
 ADD: 2581 METROCENTRE BLVD. SUITE # 3 & 6
 CONT: J. J. MORLEY ENTERPRISES, INC.
 TEL: (561)843-5325
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN 20/2015
 ACTION: DENIED
  
 1) SHEET A-1.0 INDICATES THE USE OF A BREAK AREA, WITH
 A 2 BOWEL SINK, PLEASE PROVIDE COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE: 606 LAVATORIES AND SINKS606.1
 GENERAL. LAVATORIES AND SINKS SHALL COMPLY WITH 606.
  
 1A) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 1B) 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 1C) 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY
 WITH 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN
 OPEN FOR 10 SECONDS MINIMUM.
  
 1D) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND
 DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES AND SINKS.
  
 2) SHEET A-1.0 NOTE 18 INDICATES THE USE OF A MICROWAVE
 IN A DRAWER, PLEASE SHOW COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE 309 OPERABLE PARTS
  
 2A) 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH
 309.
  
 2B) 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 SHALL BE PROVIDED.
  
 2C) 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 2D) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 3) SHEET A-1.0 NOTE # 7 INDICATES A NEW EXTERIOR DOOR
 OPENING. PLEASE PROVIDE THE WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.4
 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL
 BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN
 SUFFICIENT DETAIL TO DETERMINE COMPLIANCE WITH THIS
 CODE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-30 Cont ID  
Sent By dhayes Date 2015-01-30 Time 15:59 Rev Time 0.00
Received By dhayes Date 2015-01-30 Time 15:40 Sent To  
Notes
2015-01-27 14:54:19NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-10 Cont ID  
Sent By dhayes Date 2015-01-10 Time 13:17 Rev Time 0.00
Received By dhayes Date 2015-01-10 Time 13:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-29 Cont ID  
Sent By pleduc Date 2015-01-29 Time   Rev Time 0.00
Received By pleduc Date 2015-01-29 Time 13:17 Sent To  
Notes
2015-01-29 13:23:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
2015-01-27 14:54:40NEW DRAWINGS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-16 Cont ID  
Sent By pleduc Date 2015-01-16 Time   Rev Time 0.00
Received By pleduc Date 2015-01-12 Time 16:31 Sent To  
Notes
2015-01-16 09:59:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-03 Cont ID  
Sent By hmoser Date 2015-02-03 Time 14:45 Rev Time 0.00
Received By hmoser Date 2015-01-26 Time 14:53 Sent To  
Notes
2015-01-27 14:53:51RE-SUBMITTAL SENT TO C18 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-21 Cont ID  
Sent By hmoser Date 2015-01-21 Time 14:27 Rev Time 0.00
Received By hmoser Date 2015-01-07 Time 08:04 Sent To  
Notes
2015-01-08 08:07:44C10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By hmoser Date 2015-02-03 Time 14:45 Rev Time 0.00
Received By hmoser Date 2015-02-03 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By hmoser Date 2015-01-21 Time 14:27 Rev Time 0.00
Received By hmoser Date 2015-01-21 Time 13:54 Sent To  
Notes
2015-01-21 14:27:12PLAN DENIED
 1) PROVIDE NUMBERS ON RELOCATED AIR HANDLERS.
 PER SECTION 304.12 AREA SERVED 2010 FBC (M)
 2) SHOW WHERE 20 IN. SPIRAL DUCT IS GOING ON
 4 TON RELOCATED AIR HANDLER 107 FBC
 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE
 403.3 FBC (M) 2010
 4) PROVIDE ENERGY CALCULATIONS PER SECTION
 503.2.1 CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-02-03 Cont ID  
Sent By tklarge Date 2015-02-03 Time 12:35 Rev Time 0.00
Received By tklarge Date 2015-02-03 Time 12:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-01-30 Cont ID  
Sent By tklarge Date 2015-01-30 Time 06:29 Rev Time 0.00
Received By tklarge Date 2015-01-30 Time 05:00 Sent To  
Notes
2015-01-30 05:34:211) SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECS/INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER
 FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.107.2.1.2ND
 REQUEST. THERE WERE NO SPEC/MANUAL ATTACHED.
 2) SHOW THE REQUIRED KNEE & TOE CLEARANCE DIMENSIONS
 FOR THE LAVATORIES AND THE DRINKING FOUNTAINS ON SHTS.
 A-4.1 & A-4.2. COMPLY W/ FL. ACC. CODE SEC. 306. 2ND
 REQUEST.
 3) SHT. A-4.1 - ELEVATIONS # 3 & # 4 - TYPO -THERE ARE
 IDENTIFICATION ARROWS AND ITEM NAMES ON THE PLANS
 POINTING TO NOTHING. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 4) SHT.A-4.2 - RESTROOM #122 IS CALLED OUT AS A UNISEX
 RESTROOM. PER SEC.403.5.2 & 403.5.3 OF 2010 FPC, A
 UNISEX TOILET ROOM SHALL INCLUDE ONLY ONE WATER CLOSET
 AND ONE LAVATORY (AND ONE URINAL PER EXCEPTION). UNISEX
 BATHING ROOMS SHALL ALSO INCLUDE ONE WATER CLOSET AND
 ONE LAVATORY. THIS RESTROOM DOES NOT MEET THE
 DEFINITION OF A UNISEX RESTROOM. COMPLY WITH THE STATED
 PUMBING CODE SECTIONS.
 4) SHT. A-4.2 - SHOW THE WIDTH OF THE ACCESSIBLE SHOWER
 IN ROOM # 122. MINIMUM WIDTH SHALL BE 30 INCHES. FAC
 SEC.608.2.2. 2ND REQUEST.
 5) SHT.A-4.2 - ELEVATION #4 R.R. 122- TYPO - SHOWS BOTH
 URINALS AS ADA ACCESSIBLE BUT ONE DOES NOT COMPLY.MAX.
 HEIGHT TO THE RIM SHALL BE 17 INCHES. FAC SEC.605.2.
 6) SHT.A-4.2 - THE ACCESSIBLE SHOWER SHALL HAVE A
 MINIMUM 60 INCH WIDE ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT PER THE FAC SEC.608.2.2. THE LAVATORY
 APPEARS TO ENCROACH IN THIS SPACE. CLARIFY.
 7) SHT.A-4.2 - THE ACCESSIBLE SHOWER SHALL HAVE GRAB
 BARS PROVIDED ON THREE SIDES IN ROLL IN SHOWERS WITHOUT
 SHEETS PER THE FAC SEC.608.3.2. SPACING FROM ADJACENT
 WALLS SHALL COMPLY WITH FAC SEC.608.3.2.
 8) SHT. P0.1 - SIZE ALL SECTIONS OF THE VENTING SYSTEM
 ON THE SANITARY RISER. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.2ND REQUEST. YOUR RESPONSE REFERS TO THE
 ARCHITECTURAL PAGES WHICH ARE ELEVATION DETAILS.??
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By tklarge Date 2015-01-21 Time 12:51 Rev Time 0.00
Received By tklarge Date 2015-01-20 Time 12:50 Sent To  
Notes
2015-01-21 12:49:321) SHT. CVR - PLBG. FIXTURES REQD. ALTHOUGH THE MINIMUM
 NUMBER OF FIXTURES HAS BEEN MET, PLEASE CORRECT THE
 REQUIRED FIXTURE COUNT. PER TABLE 403.1 OF THE 2010 FL.
 PLBG. CODE, 3 WATER CLOSETS ARE REQUIRED EACH FOR MALES
 AND FEMALES, NOT 2 EACH AS SHOWN.
 2) SINKS AND LAVATORIES SHALL COMPLY W/ 2010 FL.
 ACCESSIBILITY CODE. SEC606.1 & 606.3. THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE SHALL BE A MAX. OF
 34 INCHES ABOVE THE FINISH FLOOR.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECS/INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER
 FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 4) SUBMIT ENLARGED TOILET ROOM PLANS AND ELEVATION
 DETAILS SHOWING FULL COMPLIANCE WITH THE 2010 FAC.
 5) ONE OF THE URINALS SHALL BE HANDICAP ACCESSIBLE PER
 THE FAC SEC.213.3.3. SUBMIT AN ELEVATION DETAIL AND
 SHOW THE CLEAR FLOOR SPACE ON THE PLAN PER THE 2010 FAC
 305 & 605.
 6) SUBMIT AN ELEVATION DETAIL & ENLARGED PLAN FOR
 HANDICAP ACCESSIBLE SHOWER. SHOW THE DIMENSIONS OF THE
 SHOWER (LXW) AND COMPLIANCE WITH FAC SEC.608.
 7) DRINKING FOUNTAINS SHALL COMPLY WITH FAC SEC.211 &
 306. SHOW THE KNEE & TOE CLEARANCES ON THE PLAN.
 8) SIZE ALL SECTIONS OF THE VENTS ON THE SANITARY
 RISERS ON SHT.P0.1.
 9) A VACUUM RELIEF VALVE IS REQD. ON THE 30 GAL. WATER
 HEATER PER THE 2010 FPC SEC.504.2. THE PLAN SHOWS A
 VACUUM BREAKER WHICH IS NOT THE SAME.
 10) PLEASE CLARIFY WHY THERE IS A SHOWER STALL IN THE
 MEN'S RESTROOM #122 AND NOT ONE IN THE WOMEN'S.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  