Plan Review Details - Permit 15010121
Plan Review Stops For Permit 15010121
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-24 Cont ID  
Sent By aaponte Date 2015-01-24 Time 16:00 Rev Time 0.00
Received By dhayes Date 2015-01-24 Time 15:49 Sent To Z
Notes
2015-01-24 16:00:06ALL UNDERGROUND INSPECTIONS ARE REQUIRED AT THE TIME OF
 TRENCHING AND INSTALATION AND SHALL COMPLY WITH THE NEC
 300.5.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By sgraham Date 2015-01-14 Time 08:21 Rev Time 0.00
Received By dhayes Date 2015-01-14 Time 07:42 Sent To Z
Notes
2015-01-14 08:34:321/14/2015
 PROJECT: BENITZ BUILDING SITE LIGHTING
 PERMIT#: 15010121
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE BRANCH CIRCUITRY DETAILS INDICATING THE
 ELECTRICAL PANEL, CIRCUIT NUMBER AND CALCULATED LOAD OF
 THE CIRCUIT FEEDING SITE LIGHTING.
  
 2) PROVIDE THE METHOD OF COMPLIANCE WITH THE FBC-ENEGY
 SECTION 505. LIGHTING SHALL HAVE AUTOMATIC CONTROLS
 CAPABLE OF TURNING OFF EXTERIOR LIGHTING WHEN
 SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING
 IS NOT REQUIRED DURING NIGHTTIME HOURS.
  
 3) PROVIDE THE WIRING METHOD CONDUIT AND CONDUCTOR
 SIZES INDICATING THE CIRCUIT NUMBER(S) ON THE SITE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-27 Cont ID  
Sent By aaponte Date 2015-01-27 Time 12:58 Rev Time 0.00
Received By aaponte Date 2015-01-23 Time   Sent To  
Notes
2015-01-27 12:59:05TO STEVE KENNEDY
2015-01-24 08:44:56SENT TO D. HAYES' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-01-20 Time   Rev Time 0.00
Received By dhayes Date 2015-01-07 Time 07:42 Sent To  
Notes
2015-01-20 17:16:27TO SHIRLEY FOR PROCESSING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-01-27 Cont ID  
Sent By aaponte Date 2015-01-27 Time 12:58 Rev Time 0.00
Received By aaponte Date 2015-01-27 Time 12:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-01-20 Cont ID  
Sent By aaponte Date 2015-01-20 Time 17:16 Rev Time 0.00
Received By aaponte Date 2015-01-20 Time 17:16 Sent To  
Notes
***NONE***