| 2015-01-14 08:34:32 | 1/14/2015 |
| | PROJECT: BENITZ BUILDING SITE LIGHTING |
| | PERMIT#: 15010121 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE BRANCH CIRCUITRY DETAILS INDICATING THE |
| | ELECTRICAL PANEL, CIRCUIT NUMBER AND CALCULATED LOAD OF |
| | THE CIRCUIT FEEDING SITE LIGHTING. |
| | |
| | 2) PROVIDE THE METHOD OF COMPLIANCE WITH THE FBC-ENEGY |
| | SECTION 505. LIGHTING SHALL HAVE AUTOMATIC CONTROLS |
| | CAPABLE OF TURNING OFF EXTERIOR LIGHTING WHEN |
| | SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING |
| | IS NOT REQUIRED DURING NIGHTTIME HOURS. |
| | |
| | 3) PROVIDE THE WIRING METHOD CONDUIT AND CONDUCTOR |
| | SIZES INDICATING THE CIRCUIT NUMBER(S) ON THE SITE |
| | PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |