Plan Review Details - Permit 15010032
Plan Review Stops For Permit 15010032
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-03-25 Cont ID  
Sent By pleduc Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-25 Time 15:35 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-09 Cont ID  
Sent By pleduc Date 2015-02-09 Time   Rev Time 0.00
Received By pleduc Date 2015-02-09 Time 15:16 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-12 Cont ID  
Sent By pleduc Date 2015-01-12 Time   Rev Time 0.00
Received By pleduc Date 2015-01-12 Time 12:03 Sent To M
Notes
2015-01-12 12:07:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SUBMITTED PLAN DOES NOT PROVIDE SUFFICIENT DETAIL.
  
 PROVIDE LOCATION OF HOOD IN BUILDING WITH ACCURATE
 DIMENSIONS AND INCLUDE THE EXHAUST FAN DETAIL THROUGH
 AND TO THE TOP OF ROOF.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-25 Cont ID  
Sent By hmoser Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-19 Time 09:33 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-19 Cont ID  
Sent By hmoser Date 2015-02-19 Time 12:16 Rev Time 0.00
Received By hmoser Date   Time   Sent To  
Notes
2015-02-07 07:13:24INCOMING SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 14:37 Rev Time 0.00
Received By hmoser Date 2015-01-05 Time 13:59 Sent To  
Notes
2015-01-05 13:59:25TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-03-23 Cont ID  
Sent By pleduc Date 2015-03-25 Time 15:38 Rev Time 0.00
Received By hmoser Date 2015-03-23 Time 11:23 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-19 Cont ID  
Sent By hmoser Date 2015-02-19 Time 11:54 Rev Time 0.00
Received By hmoser Date 2015-02-19 Time 11:54 Sent To  
Notes
2015-02-19 12:16:26PLAN DENIED
 PROVIDE ENGINEERING FOR THE EXHAUST FAN CURB
 AND SUPPLY FAN CURB SHOWING CURB TO ROOF
 TIEDOWN. PROVIDE TYPE, SIZE AND SPACING
 OF THE ANCHOR. PROVIDE A DETAIL ON THE FANS TIE DOWN TO
 CURB. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 2) SAFETY GUARD ON PAGE H.1 MUST EXTEND
 30 IN BEYOND END OF THE APPLIANCE.
 PER SECTION 304.11 GUARDS 2010 FBC (M)
 3) PROVIDE TWO SETS OF PLANS ONLY ONE SUBMITTED
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 14:37 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 14:27 Sent To  
Notes
2015-01-14 14:36:55PLAN DENIED
 1) PROVIDE A COMPLETE SET OF PLANS
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER FOR
 ANCHORING OF THE FAN CURB AND FAN.
 PER SECTION 301.12 WIND RESISTANCE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676