Plan Review Details - Permit 14120907
Plan Review Stops For Permit 14120907
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By rmcdouga Date 2015-06-09 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2015-06-09 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 13:28 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 13:16 Sent To E
Notes
2015-02-02 13:19:41PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BASED ON THE ZONING REVIEW THE STRUCTURE IS REQUIRED TO
 BE RETURNED TO A SINGLE FAMILY DWELLING. IT APPEARS
 THAT THE STRUCTURE MAY HAVE BEEN ILLEGALLY CONVERTED TO
 A TWO FAMILY DWELLING.
 UNLESS YOU CAN LOCATE RECORDS THAT SHOW THIS DWELLING
 WAS ORIGINALLY CONSTRUCTED AS A TWO FAMILY DWELLING OR
 THAT IT WAS CONVERTED FROM A SINGLE FAMILY WITH THE
 PROPER PERMITS AND INSPECTIONS, YOU WILL BE REQUIRED TO
 RETURN IT TO A SINGLE FAMILY. IF ZONING WILL ALLOW IT,
 YOU CAN OBTAIN PERMITS TO CONVERT THE EXISTING DWELLING
 TO A TWO FAMILY DWELLING. THE PLANS WILL BE REQUIRED TO
 SHOW THAT THE CONVERSION COMPLIES WITH THE 2010 FBC AND
 THE NEW AND PREVIOUS WORK WILL HAVE TO INSPECTED AND
 APPROVED.
  
 1)FBC- R302.3 DWELLING UNITS IN TWO-FAMILY DWELLINGS
 SHALL BE SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR
 ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH
 ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED
 FLOOR-CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND
 BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES
 SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF
 THE ROOF SHEATHING.
  
 2) FBC-R303.8 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  
 3) FBC-R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE. EXCEPTION: THE
 GLAZED AREAS SHALL NOT BE REQUIRED WHERE ARTIFICIAL
 LIGHT AND A MECHANICAL VENTILATION SYSTEM ARE PROVIDED.
  
 4) FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED.
 EVERY SLEEPING ROOM SHALL HAVE AT LEAST ONE OPERABLE
 EMERGENCY ESCAPE AND RESCUE OPENING.
  
 5) R310.1.1 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SQUARE
 FEET. EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5 SQUARE FEET.
  
 6) R311.2 AT LEAST ONE EGRESS DOOR SHALL BE PROVIDED
 FOR EACH DWELLING UNIT. THE EGRESS DOOR SHALL BE
 SIDE-HINGED, AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF
 32 INCHES WHEN MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. THE
 MINIMUM CLEAR HEIGHT OF THE DOOR OPENING SHALL NOT BE
 LESS THAN 78 INCHES (1981 MM) IN HEIGHT MEASURED FROM
 THE TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.
  
 7) R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 8) R807.1 ATTIC ACCESS. BUILDINGS WITH COMBUSTIBLE
 CEILING OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS
 OPENING TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8
 M2) AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN
 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. (ONE IN EACH UNIT)
  
 9) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 10) FBC ENERGY CONSERVATION - SECT. 403.6.1 EQUIPMENT
 SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 20:39 Rev Time 0.00
Received By albarran Date 2015-07-13 Time 19.48 Sent To I
Notes
2015-07-13 20:41:46ELECTRICAL PROVISO FOR PERMIT 14120907
  
 HEATING AS DESCRIBED ON PLANS IS NOT COMPLIANT
 CORRECT ACCORDINGLY:
 R303.8 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-26 Cont ID  
Sent By albarran Date 2015-05-26 Time 19:55 Rev Time 0.00
Received By albarran Date 2015-05-26 Time 18:59 Sent To B
Notes
2015-05-26 19:49:51SECOND ELECTRICAL REVIEW FAILED AS MENTIONED BELOW:
 BOTH NEC & FBC HAVE MINIMUM REQUIREMENTS THAT SHALL BE
 COMPLIED WITH AND ARE NOT REFLECTED ON THE SUBMITTED
 DRAWINGS.
 1. FBC-R 303, REQUIRES THAT YOU PROVIDE HEAT
 2. FBC-R 306, REQUIRES THAT YOU HAVE HOT WATER AND
 THOUGH INDICATED IN THE PANEL SCHEDULE, A WATER HEATER
 IS NOT INDICATED ON THE PLANS.
 3. THE PANEL SCHEDULE REFLECTS THE REQUIRED LAUNDRY
 CIRCUIT, BUT THE DRAWING DOES NOT.
 4. THE PANEL SCHEDULE REFLECTS AN AHU & A CU AS WELL,
 BUT THEY ARE NOT INDICATED ON THE DRAWINGS.
 5. THE PANEL SCHEDULE REFLECTS AN ELECTRIC OVEN, BUT
 NOT AN ELECTRIC RANGE, YET THE DRAWING INDICATES A
 RANGE AND NO OVEN. CLARIFY IF THEY ARE ONE OF THE SAME.
 IF NOT AND THE RANGE IS A GAS APPLIANCE, AS PER FBC-R
 315, CARBON MONOXIDE DETECTION IS REQUIRED.
 6 OUTLET PLACEMENT SHALL BE AS INDICATED BY NEC 210.52,
 CHECK THE DENIED PLAN FOR ASSISTANCE WITH OUTLET
 PLACEMENT.
  
 CORRECT THE ELECTRICAL SUBMITTAL AS INDICATED ABOVE.
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL ME, I CAN BE REACHED BY CALLING MIKE AT
 561-805-6743

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 15:49 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 15:49 Sent To  
Notes
2015-02-02 16:03:50PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE ZONING REVIEW STATES THAT A TWO UNIT DWELLING IS
 NOT ALLOWED.
  
 1) SUBMIT AN ELECTRICAL RISER DIAGRAM WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.FOR A SINGLE FAMILY DWELLING. FBC 107.3.5.3
  
 2) SUBMIT A PANEL SCHEDULE FOR A SINGLE FAMILY
 DWELLING. FBC 107.3.5.3
  
 3) SUBMIT ELECTRICAL LOAD CALCULATIONS FOR A SINGLE
 FAMILY DWELLING. NEC 220.40
  
 4) REVISE THE FLOOR PLAN TO A SINGLE FAMILY DWELLING.
 FBC 107.2.1
  
 5) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 6) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 7) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP
 SURFACES ARE REQUIRED TO BE GFCI PROTECTED.
  
 8) NEC 210.52 (E)(1) ? AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6 ? FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF THE DWELLING.
  
 9) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT.
  
 10) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 11) NEC 210.12 (B) ? OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 12) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-13 Cont ID  
Sent By albarran Date 2015-07-13 Time 20:41 Rev Time 0.00
Received By albarran Date 2015-07-09 Time 14:19 Sent To  
Notes
2015-07-13 20:44:167/131/15 - PASSED ELECTRICAL REVIEW W/PROVISO.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN
 "A". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2015-06-09 Time   Rev Time 0.00
Received By shill Date 2015-05-14 Time 07:34 Sent To  
Notes
2015-06-01 18:10:246/1 TO RM DESK
  
2015-05-15 07:35:12TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2014-12-31 Time 08:42 Sent To  
Notes
2015-01-03 08:44:39R05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 15:27 Sent To  
Notes
2015-02-02 15:30:53NO MECHANICAL PERMIT APPLICATION OR MECHANICAL PLANS
 WERE SUBMITTED. A SEPARATE PERMIT, APPLICATION AND
 REVIEW IS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-18 Cont ID  
Sent By tklarge Date 2015-05-18 Time 12:57 Rev Time 0.00
Received By tklarge Date 2015-05-18 Time 12:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-06 Cont ID  
Sent By tklarge Date 2015-01-06 Time 13:41 Rev Time 0.00
Received By tklarge Date 2015-01-06 Time 11:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-18 Cont ID  
Sent By sgraham Date 2015-05-18 Time 12:41 Rev Time 0.00
Received By sgraham Date 2015-05-18 Time 12:41 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-01-20 Cont ID  
Sent By sgraham Date 2015-01-20 Time 15:45 Rev Time 0.00
Received By sgraham Date 2015-01-20 Time 15:45 Sent To  
Notes
2015-01-20 15:47:441/19/15 ZONING FAILED
  
 1. ZONING DISTRICT IS SF7, THE HOUSE WAS BUILT AS A
 SINGLE FAMILY HOME, SECOND KITCHEN MUST BE REMOVE AND
 NO NEW ELECTRIC SERVICE CAN BE ADDED. AN ENTRANCE FROM
 THE ADDITION TO THE MAIN HOUSE MUST BE
 INSTALLED.