Plan Review Details - Permit 14120786
Plan Review Stops For Permit 14120786
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-03 Cont ID  
Sent By rmcdouga Date 2015-02-03 Time 19:03 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 16:59 Sent To  
Notes
2015-02-03 18:32:05PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CLARIFY THE AREA DESCRIPTIONS ON SHEET A-01. THE
 FLOOR PLANS SHOW A GARAGE ON THE FIRST FLOOR AND AN
 APARTMENT ON THE SECOND FLOOR. THE AREA COMPUTATION
 LISTS THE FIRST FLOOR AS A CABANA AND THE SECOND FLOOR
 AS A PLAYROOM. PLEASE COORDINATE. FBC 107.2.1
  
 2) CLARIFY THE TYPE OF WINDOWS THAT WILL BE INSTALLED.
 THE WINDOW SCHEDULE ON A-01 SPECIFY SH (SINGLE HUNG).
 THE NOTES BELOW THE WINDOW SCHEDULE STATE ALL WINDOWS
 TO BE CASEMENT AND FIXED BY T&M WINDOWS. THE WINDOW
 PRODUCT APPROVAL IS FOR PGT DOUBLE HUNG WINDOWS. FBC
 107.2.1
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE SUBMITTALS FOR THE 8' WIDE
 DOUBLE OUTSWING GARAGE DOORS.
  
 4) FBC-R318.6 ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST
 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS.
  
 5) FBC-R311.7.7.1 HANDRAIL HEIGHT, MEASURED VERTICALLY
 FROM THE SLOPED PLANE ADJOINING THE TREAD NOSING, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE NOT LESS THAN 34
 INCHES AND NOT MORE THAN 38 INCHES.
  
 6) FBC-R704 IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES EXCEPTIONS: 1.
 PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN 5/8
 INCH THICK ADHERED DIRECTLY TO THE MASONRY FOUNDATION
 SIDEWALL. THE PLANS SPECIFY 7/8" THICK STUCCO ON THE
 MASONRY WALLS. THE STUCCO WILL BE REQUIRED TO STOP 6"
 ABOVE GRADE UNLESS IT IS LESS THAN 5/8 INCH THICK.
  
 7) R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 8) FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
  
 9) R302.6 DWELLING/GARAGE FIRE SEPARATION. THE GARAGE
 SHALL BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE THE
 GARAGE BY NOT LESS THAN 5/8-INCH TYPE X GYPSUM BOARD OR
 EQUIVALENT.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By rmcdouga Date 2015-02-04 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2015-02-04 Time 09:01 Sent To  
Notes
2015-02-04 10:02:35PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 2) SHOW COMPLIANCE WITH FBC-R314 FOR REQUIRED SMOKE
 ALARMS.
  
 3) SHOW LOCATION OF A/C EQUIPMENT AND THEIR DISCONNECTS
 ON THE ELECTRICAL PLANS. FBC 107.2.1
  
 4) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 5) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED. ALL
 RECEPTACLES LOCATED IN THE GARAGE ARE REQUIRED TO BE
 GFCI PROTECTED.
  
 6) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 8) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6 1/5 FT. ABOVE GRADE SHALL BE INSTALLED
 AT THE FRONT AND BACK OF THE DWELLING.
  
 9) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT
 LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS
 REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR
 EXITS.
  
 10) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT. NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE
 AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR
 PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR
 LESS.
  
 11) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 12) IT APPEARS THAT YOUR CALCULATIONS FOR THE
 UNBALANCED NEUTRAL LOAD ARE INCORRECT. BASED ON YOUR
 CALCULATION RESULT OF 155 AMPS, THE 1/0 NEUTRAL FEEDER
 FROM THE METER TO PANEL A IS TOO SMALL. NEC 220.16 AND
 220.61
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-04 Cont ID  
Sent By rmcdouga Date 2015-02-04 Time 13:14 Rev Time  
Received By rmcdouga Date 2014-12-23 Time   Sent To  
Notes
2014-12-23 17:17:48SENT TO R08.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 17:40 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 17:40 Sent To  
Notes
2015-02-02 18:04:34BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By rmcdouga Date 2015-02-04 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 18:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-24 Cont ID  
Sent By tklarge Date 2014-12-24 Time 14:55 Rev Time 0.00
Received By tklarge Date 2014-12-24 Time 13:19 Sent To  
Notes
2014-12-24 14:30:431) SUBMIT A WATER RISER FOR REVIEW PER WPB AMEND .TO
 2010 FBC SEC.107.3.5.3 (11).
 2) SHT. S 04 - OVERFLOW SCUPPERS SHALL BE LOCATED NO
 LESS THAN 2" NOR MORE THAN 4" ABOVE THE FINISHED ROOF
 PER 1020 FL. BLDG. CODE, RESIDENTIAL, SEC.903.4.1.
 3) A VENT IS REQD.BETWEEN THE SHOWER AND THE WATER
 CLOSET ON THE 2ND FLOOR. 2010 FBCR SEC,P3108.2.1.
 4) SHT.P.01 - SIZE ALL SECTIONS OF THE DRAINAGE PIPE ON
 THE RISER DIAGRAM.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-01-06 Cont ID  
Sent By sgraham Date 2015-01-06 Time 08:57 Rev Time 0.00
Received By sgraham Date 2015-01-06 Time 08:57 Sent To  
Notes
2015-01-06 09:00:301/6/14 ZONING FAILED.
  
 1. BUILDING CAN NOT BE DEMOLISHED, IF THE COWNER WANTS
 TO KEEP THE GARAGE APARTMENT. THE BUILDING IS A LEGAL
 NON CONFORMING USE, THE ZONING IS NOW SF7.
 ANGELLA VANN/FIRE DEPARTMENT AGREE THE BUILDING CAN BE
 REPAIRED WITHOUT BE TORN DOWN, THE DAMAGE IS TO THE
 WEST EXTERIOR WALL AND THE STAIRS.