Plan Review Details - Permit 14120751
Plan Review Stops For Permit 14120751
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By jgomez Date 2015-01-26 Time 08:56 Rev Time 0.00
Received By jgomez Date 2015-01-26 Time 07:46 Sent To  
Notes
2015-01-26 08:57:22RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PLANS NEED TO PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH THE LIGHT AND VENTILATION REQUIREMENTS OF SEC.
 R303.3 OF 2010 FBC-RESIDENTIAL. CLEARLY SPECIFY IF
 COMPLIANCE WILL BE PROVIDED WITH A WINDOW OR BY MEANS
 OF MECHANICAL VENTILATION.
  
 2- PROVIDE COMPLETE PLANS WITH DIMENSIONS SHOWING
 COMPLIANCE WITH SEC. R307 OF 2020 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By skennedy Date 2015-01-26 Time 09:13 Rev Time 0.00
Received By skennedy Date 2015-01-26 Time 09:13 Sent To  
Notes
2015-01-26 09:18:591ST REVIEW: FBC 2010
  
 PROVIDE A PLAN PER FBC 107.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM. IF APPLICABLE.
  
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 SHOW OUTLETS AND LIGHTS. NEC 210. - OUTLETS TO BE GFCI
 PROTECTED.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By skennedy Date 2015-01-26 Time 09:13 Rev Time 0.00
Received By skennedy Date 2014-12-22 Time 18:02 Sent To  
Notes
2015-01-26 09:15:021ST REVIEW: FBC 2010
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
2014-12-22 18:03:04R09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By jgomez Date 2015-01-26 Time 08:11 Rev Time 0.00
Received By jgomez Date 2015-01-26 Time 08:11 Sent To  
Notes
2015-01-26 09:10:43NO MECHANICAL WORK SHOWN.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-24 Cont ID  
Sent By tklarge Date 2014-12-24 Time 13:19 Rev Time 0.00
Received By tklarge Date 2014-12-24 Time 13:02 Sent To  
Notes
2014-12-24 13:18:151) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 REVIEW. SHOWW ALL THE PIPE SIZES ON THE RISER DIAGRAM.
 SIZES SHALL COMPLY W/ 2010 FL. PLUMBING CODE
 SECS.604.5, TABLE 604.5, & TABLE 709.1.
 2) INDICATE ON THE PLAN IF THE WATER HEATER IS NEW OR
 EXISTING AND IF IT IS ELECTRIC OR GAS. WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) SHOW THE DISTANCE FROM THE CENTERLINE OF THE WATER
 CLOSET TO THE EDGE OF THE TUB AND ALSO TO THE EDGE OF
 THE SINK.COMPLY W/2010 FPC SEC.405.
 4) SHOW THE DIMENSIONS OF THE BATHROOM ON THE PLAN. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  