Plan Review Details - Permit 14120736
Plan Review Stops For Permit 14120736
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-23 Cont ID  
Sent By hmoser Date 2014-12-23 Time 14:16 Rev Time 0.00
Received By hmoser Date 2014-12-23 Time 13:55 Sent To  
Notes
2014-12-22 16:54:11MECHANICAL OVER 5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-12-23 Cont ID  
Sent By hmoser Date 2014-12-23 Time 14:16 Rev Time 0.00
Received By hmoser Date 2014-12-23 Time 13:55 Sent To  
Notes
2014-12-23 14:16:43PLAN DENIED
  
 1) PROVIDE ENERGY CALCULATIONS WITH THE PLAN.
 PER SECTION 403.6.1 FLORIDA ENERGY CODE 2010
 2) PROVIDE EQUIPMENT SCHEDULE ON THE PLAN
 PER SECTION 107 FBC 2010
 3) SHOW A COMPLETE DUCT DRAWING DUCT WORK AND
 SIZE,VENTILATION,
 EQUIPMENT SCHEDULE NAME OF PERSON WHO DREW THE PLAN
 AND LICENSE NUMBER. TWO COPY OF SURVEY
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676