Plan Review Details - Permit 14120697
Plan Review Stops For Permit 14120697
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-12 Cont ID  
Sent By jgomez Date 2016-02-11 Time 18:39 Rev Time 0.00
Received By jgomez Date 2016-02-11 Time 18:39 Sent To Z
Notes
2016-02-11 18:44:54 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-12-22 Cont ID  
Sent By jgomez Date 2015-12-22 Time 08:32 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 08:31 Sent To  
Notes
2015-12-21 18:26:56RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLAT ROOF LIQUID ROOFING NOA 13-0204.17 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC.
 NOTE: THREE ASSEMBLIES WITH DESIGN PRESSURES OF -60PSF
 WERE UNDERLINED ON NOA SUBMITTED. THESE THREE
 ASSEMBLIES ARE FOR INSULATED ROOF SYSTEMS. PLANS DON'T
 SPECIFY INSULATED ROOF SYSTEMS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301.
 NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION
 #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW ENHANCED
 FASTENING. SEE GENERAL LIMITATION #9 ON-LAST PAGE OF
 NOA SUBMITTED.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) REVISE FORM 402-2010. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.:
 (1)ANSWERS FOR ITEMS #6(A) IS INCORRECT. SEE GENERAL
 INSTRUCTION NOTE #2 ON FIRST PAGE OF FORM.
  
 (2) NEED TO ANSWER ITEM #6(B). SEE GENERAL INSTRUCTION
 NOTE #2 ON FIRST PAGE OF FORM.
  
 (3) ITEM # 8(A). THERE IS NOT R-VALUE REQUIREMENT FOR
 FOR SLAB ON GRADE. ON THE OTHER HAND, ANY R-VALUE IS
 FOR THE INSULATION MATERIAL ONLY. SEE NOTE #3 ON SECOND
 PAGE OF FORM SUBMITTED.
  
 (4) ITEM #9 IS INCORRECT. INSULATION ON CONCRETE BLOCK
 WALL NEED TO COMPLY WITH NOTE #3 ON SECOND PAGE OF FORM
 SUBMITTED.
 NOTE: NEED TO COMPLY WITH THE R-VALUE FOR THE INTERIOR
 AND EXTERIOR OF THE WALL.
  
 (5) ITEM #14. A/C EQUIPMENT IS NOT ALLOWED TO BE
 OVERSIZED. SEC. 403.6.1.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 3- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR WINDOWS
 U-FACTOR AND SHGC FACTOR SHOWN ON THE ENERGY
 CALCULATIONS. SEC. 103.2.2 AND SEC. 303.1.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 NOTE: THE ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES
 THE PLAN REVIEW FEE IF THE ENERGY CALCULATIONS ARE
 DENIED FOR A FOURTH TIME. SEE F.S. 553.80(2)(B)
  
 ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-18 Cont ID  
Sent By JGomez Date 2015-09-17 Time 16:14 Rev Time 0.00
Received By jgomez Date 2015-09-17 Time 16:14 Sent To E
Notes
2015-09-17 16:15:30RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2-PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAILS.
 NOTE: BUCK SIZE NEEDS TO PROVIDE FULL SUPPORT TO THE
 DOOR/WINDOW FRAME. SEE SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL.
 ***RESPONSE:
 A) DETAIL 4/A-5 DOESN'T SPECIFY WINDOW BUCK SIZE. NOTE:
 "BUCKS SHALL EXTEND BEYOND THE INTERIOR FACE OF THE
 WINDOW OR DOOR FRAME SUCH THAT FULL SUPPORT OF THE
 FRAME IS PROVIDED". SEE SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL AND PRODUCT APPROVALS SUBMITTED. REVISE
 DETAIL AS REQUIRED.
 B) SIZE OF DOOR BUCK SPECIFIED ON DETAIL 5/A-5 DOESN'T
 PROVIDE DOOR FRAME FULL SUPPORT. NOTE: "BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED".
 SEE SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL AND
 PRODUCT APPROVALS SUBMITTED. REVISE DETAIL AS REQUIRED.
 AND CLARIFY WHAT'S "2"X4" DOOR METAL BUCK"?. SEE DOOR
 PRODUCT APPROVAL SUBMITTED.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) NEW WINDOWS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON SHEET A-3..
 ***RESPONSE:
 (1) FLORIDA PRODUCT APPROVAL FL5455-R6 SUBMITTED SAYS
 "PENDING FBC APPROVAL". NEED APPROVED PRODUCT APPROVAL.
  
 (2) PROVIDE COMPLETE REPORT ONLY SHEETS 1 OF 6 AND 2 OF
 6 WERE SUBMITTED. NEED COMPLETE DRAWINGS.
  
 B) NEW DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER ON SHEET A-3.
 *** RESPONSE:
 PROVIDE COMPLETE DOOR DRAWINGS. ONLY SHEET 1 OF 7 WAS
 SUBMITTED. AND MARK TYPE OF JAMB TO BE USED: WOOD OR
 PVC?.
  
 C) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON
 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW
 SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
 *** RESPONSE:
 PROVIDE COMPLETE INFORMATION. ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE FL6623-R2 WAS SUBMITTED. AND, NEED
 TO IDENTIFY THE SELECTED ASSEMBLY.
 NOTE: ROOF LIQUID APPLIED ROOF SYSTEM FL6623-R2
 SUBMITTED SHOW ONLY ONE PRODUCT FOR WOOD DECKS. IT'S
 NOA 08-1112.14. THIS NOA EXPIRED ON 01/01/14. THEREFORE
 CAN'T NOT BE USED. NEED TO PROVIDE ANOTHER ROOF PRODUCT
 APPROVAL. KEEP IN MIND THAT IF SELECTED FLAT ROOF
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY
 R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL
 BE REQUIRED. ALSO< REVISE DRAWINGS ACCORDING TO FLAT
 ROOF PRODUCT APPROVAL SELECTED.
  
 D) VENTED ALUMINUM SOFFIT NOA 13-0402.02. PROVIDE
 COMPLETE NOA. ONLY THE COVER PAGE AND PAGE 2 OF 3 WAS
 SUBMITTED.
  
 4- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY/DATE AT THE BOTTOM OF FORM
 SUBMITTED.
  
 B) REVISE FORM 402-2010. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.:
 (1)ITEM #1 IS INCORRECT. ARE THE CALCULATIONS FOR
 ENTIRE HOUSE OR FOR JUST THE ENCLOSED ADDITION.
  
 (2)ANSWERS FOR ITEMS #6(A), #6(B) AND #10(A) ARE
 INCORRECT. SEE GENERAL INSTRUCTION NOTE #2 ON FIRST
 PAGE OF FORM.
  
 (3) REVISE ITEM #10. SEE GENERAL INSTRUCTION NOTE #2 ON
 FIRST PAGE OF FORM.
  
 (4) COMPLETE ITEM #12. PROVIDE EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY SEC. 401.2 AND SEC.
 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 6-PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW GETTING THE R- 9.06 VALUE ON THE FLOOR AS SPECIFIED
 ON THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
 NOTE: ONLY THE R VALUE OF THE INSULATION NEEDS TO BE
 CONSIDERED. SEE NOTE#3 ON SECOND PAGE OF ENERGY
 CALCULATIONS SUBMITTED.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW GETTING THE R-10.06 ON MASONRY WALLS AS SPECIFIED
 ON THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
 NOTE: ONLY THE R VALUE OF THE INSULATION NEEDS TO BE
 CONSIDERED. SEE NOTE#3 ON SECOND PAGE OF ENERGY
 CALCULATIONS SUBMITTED.
  
 8- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR WINDOWS
 U-FACTOR AND SHGC FACTOR SHOWN ON THE ENERGY
 CALCULATIONS. SEC. 103.2.2 AND SEC. 303.1.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By jgomez Date 2015-01-14 Time 09:07 Rev Time 0.00
Received By jgomez Date 2015-01-14 Time 08:52 Sent To  
Notes
2015-01-14 09:10:33RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS TO FBC.
 UPDATE VALUATION.
  
 3- DESIGNER OF RECORD TO SPECIFY THE COMBINATION OF
 LEVELS OF ALTERATION AS REQUIRED BY SEC. 401.4 OF 2010
 FBC-EXISTING BUILDING.
  
 4- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAILS.
 NOTE: BUCK SIZE NEEDS TO PROVIDE FULL SUPPORT TO THE
 DOOR/WINDOW FRAME. SEE SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) NEW WINDOWS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON SHEET A-3..
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 C) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING
 DON'T HAVE HURRICANE IMPACT GLASS. AND NEED TO PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 D) NEW DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER ON SHEET A-3.
  
 E) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON
 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW
 SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR ENGINEER MAY LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AS SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 7- SECTION B-B ON SHEET A-2:
 A) SHINGLES ARE NOT ALLOWED ON 1/4 PER 12 PITCH. SEE
 SEC. R905.2.2 OF 2010 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 B) SIZE OF RAFTERS AND BLOCKING SPECIFIED DON'T MATCH
 SIZE SHOWN ON "OPEN SHED ROOF STRUCTURE FRAMING PLAN ON
 SHEET A-4. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR THE
 UNDER-FLOOR SPACE SHOWN. SPECIFY VENTILATION AND ACCESS
 AS REQUIRED BY SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 8- SECTION A-A ON SHEET A-2:
 A) WINDOW SHOWN ON THIS SECTION DOESN'T MATCH WINDOW
 SHOWN ON NEW NORTH ELEVATION ON SHEET A-3: REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) SPECIFY SIZE OF EXISTING FOOTING WHERE NEW CONCRETE
 BLOCK WALL IS GOING TO BE ERECTED. SEC. R401.2 OF 2010
 FBC-RESIDENTIAL.
  
 C) PROVIDE SPECIFICATIONS SHOWING COMPLIANCE FOR THE
 PROTECTION OF THE "NEW 1" X 3" STRIPPING" SPECIFIED FOR
 THE NEW WALL. SEC. R317.1(7) OF 2010 FBC-RESIDENTIAL.
  
 9- SECTION C-C ON SHEET A-4:
 A) SECTION DETAIL IS TOO SMALL FOR FILING PURPOSES.
 PROVIDE A LARGER SCALE DRAWING WITH LARGER LETTERING AS
 REQUIRED BY SEC. 107.2.1.4 CITY AMENDMENTS.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 SOFFIT SHOWING COMPLIANCE WITH SEC. R703.1.3 OF 2010
 FBC-RESIDENTIAL.
  
 C) PROVIDE DETAILS AND SPECIFICATIONS FOR ROOF CROSS
 VENTILATION AS REQUIRED BY SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 D) SPECIFY SIZE OF EXISTING FOOTING WHERE NEW CONCRETE
 BLOCK WALL IS GOING TO BE ERECTED. SEC. R401.2 OF 2010
 FBC-RESIDENTIAL.
  
 E) PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR THE
 UNDER-FLOOR SPACE SHOWN. SPECIFY VENTILATION AND ACCESS
 AS REQUIRED BY SEC. R408 OF 2010 FBC-RESIDENTIAL.
  
 10 - DETAIL 1 ON SHEET A-4: NEED TO SPECIFY RING SHANK
 NAILS FOR ROOF SHEATHING FASTENING AS REQUIRED BY SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 11- ENERGY CALCULATIONS SUBMITTED:
 A) ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE
 SIGNED AND SEALED DOCUMENTS AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 B) CALCULATIONS SUBMITTED SHOWING COMPLIANCE WITH TOTAL
 UA ALTERNATIVE SEC. 402.1.1.3 OF THE 2010 FBC-ENERGY
 CONSERVATION ARE INCORRECT. THE DOORS AND FLOOR U
 FBC-2010 FACTORS ARE INCORRECT. ALSO, MISSING THE
 WINDOWS U FACTOR.
 (NOTE: THE A/C WALL UNIT NEED TO COMPLY WITH THE
 EQUIPMENT EFFICIENCY OF SEC. 402.1.2.4).
  
 C) REVISE FORM 402-2010: (1)ANSWERS FOR ITEMS #1 AND #2
 ARE INCORRECT. (2)ANSWERS FOR ITEMS #6(A), #6(B) AND
 #10(A) ARE INCORRECT. SEE GENERAL INSTRUCTION NOTE #2
 ON FIRST PAGE OF FORM. (3)COMPLETE ITEM #12(B). (3)ITEM
 # 14. PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED
 BY SEC. 401.2 AND SEC. 403.6.1.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW GETTING THE R- 0.32 VALUE ON THE CONCRETE SLAB AS
 SPECIFIED ON THE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW GETTING THE R-9.6 ON MASONRY WALLS AS SPECIFIED ON
 THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 14- PROVIDE DOCUMENTATION SHOWING COMPLIANCE WITH THE
 ACTUAL U-FACTOR USED IN THE CALCULATIONS USED FOR THE
 ENERGY CALCULATIONS. SEC. 103.2.2 AND SEC. 303.1.3 OF
 2010 FBC-ENERGY CONSERVATION.
  
 15- PLANS SPECIFY "RELOCATED A/C UNIT". THE UNIT IS
 SHOWN ON THE SAME LOCATION ON THE EXISTING AND
 DEMOLITION FLOOR PLAN AND IN THE PROPOSED PLANS AND
 ELEVATIONS. CLARIFY?. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: A/C RELOCATION REQUIRES MECHANICAL PERMIT. .
  
 16- STRUCTURAL WINDSTORM CALCULATIONS SUBMITTED:
 A) CALCULATIONS NEED TO BE PROPERLY SIGNED AND SEALED
 (ORIGINALS) AS REQUIRED BY CHAPTER 471 FL. ST.
  
 B) OPEN SHED: REVISE TYPE OF ROOF SHEATHING FASTENERS.
 ACCORDING TO SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL
 NEED TO USE 8D RING SHANK NAILS. REVISE CALCULATIONS
 AND DRAWINGS ACCORDINGLY OR PROVIDE CALCULATIONS
 SHOWING THAT 10D NAILS ARE EQUIVALENT TO THE RING SHANK
 NAILS. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 C) SIZE OF 2-PLY GIRDERS SHOWN ON THE CALCULATIONS
 DOESN'T MATCH SIZE SHOWN ON PLANS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-02-22 Cont ID  
Sent By mvaldes Date 2016-02-22 Time 12:26 Rev Time 0.00
Received By mvaldes Date 2016-02-22 Time 12:26 Sent To  
Notes
2016-02-12 13:24:47NEW DRAWINGS SUBMITTED. WALL MOUNTED A/C UNIT LOCATED
 IN THE NEW STORAGE ROOM WAS REMOVED. JG.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-23 Cont ID  
Sent By mvaldes Date 2015-12-23 Time 14:06 Rev Time 0.00
Received By mvaldes Date 2015-12-23 Time 11:22 Sent To  
Notes
2015-12-23 14:10:401ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PROVISO
  
 230.24 CLEARANCES. OVERHEAD SERVICE CONDUCTORS SHALL
 NOT
 BE READILY ACCESSIBLE AND SHALL COMPLY WITH 230.24(A)
 THROUGH (E) FOR SERVICES NOT OVER 600 VOLTS, NOMINAL.
 (A) ABOVE ROOFS. CONDUCTORS SHALL HAVE A VERTICAL
 CLEARANCE
 OF NOT LESS THAN 2.5 M (8 FT) ABOVE THE ROOF SURFACE.
 THE VERTICAL CLEARANCE ABOVE THE ROOF LEVEL SHALL BE
 MAINTAINED
 FOR A DISTANCE OF NOT LESS THAN 900 MM (3 FT) IN ALL
 DIRECTIONS FROM THE EDGE OF THE ROOF.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-22 Cont ID  
Sent By ppetty Date 2015-09-22 Time 10:26 Rev Time 0.00
Received By ppetty Date 2015-09-22 Time 10:18 Sent To  
Notes
2015-09-22 10:22:24PLEASE COMPLY WITH NOTES AND VERIFY PIPE AND WIRE SIZE
 ON PLAN FOR SERVICE
 220.83 NEED LOAD CALC.
 PP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-19 Cont ID  
Sent By rlecky Date 2015-02-19 Time 11:38 Rev Time 0.00
Received By rlecky Date 2015-02-19 Time 10:34 Sent To  
Notes
2015-02-19 11:39:48 
 14120697
 828 HILLCREST BLVD
 SF ADDITION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN WHICH SHOWS THE MAIN
 DISCONNECT, PANEL BOARDS, METERS AND FEEDERS. INDICATE
 ON THE PLAN WHERE THE PANELS ARE LOCATED AND WHERE THE
 MAIN DISCONNECTS ARE LOCATED. INCLUDE A PANEL SCHEDULE
 FOR EACH PANEL. SHOW THE SERVICE GROUNDING. NEC 110.2,
 110.26, 215.5
  
 A MAIN ELECTRICAL DISCONNECT IS REQUIRED AT THE POINT
 OF SERVICE. NEC 230.70
  
 PROVIDE A DETAIL FOR THE OVERHEAD SERVICE DROP WHICH
 PROVIDES 8 FEET OF CLEARANCE AND SHOWS HOW THE MAST
 WILL BE SUPPORTED. NEC 230.22, 230.28
  
 INDICATE THE SIZE OF THE BRANCH CIRCUIT TO THE AIR
 CONDITIONING. SHOW THE MAIN DISCONNECT FOR THE AC
 EQUIPMENT. NEC
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED IN THE SHED.
 NEC 210.8, 210.52
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-02-22 Cont ID  
Sent By jgomez Date 2016-02-22 Time 16:21 Rev Time 0.00
Received By jgomez Date 2016-02-01 Time 12:40 Sent To  
Notes
2016-02-02 12:41:06RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-23 Cont ID  
Sent By cpuell Date 2015-12-23 Time 14:45 Rev Time 0.00
Received By cpuell Date 2015-12-04 Time 08:48 Sent To  
Notes
2015-12-07 08:49:09R09

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-22 Cont ID  
Sent By lmarchan Date 2015-09-22 Time 10:30 Rev Time 0.00
Received By lmarchan Date 2015-08-31 Time 15:15 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-19 Cont ID  
Sent By rlecky Date 2015-02-19 Time 11:39 Rev Time 0.00
Received By rlecky Date 2014-12-19 Time 16:27 Sent To  
Notes
2014-12-19 16:31:47R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status N Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-24 Time 12:58 Rev Time 0.00
Received By jgomez Date 2016-02-24 Time 12:58 Sent To  
Notes
2016-02-24 13:00:41NO IMPACT FEES. ASKED OWNER TO TAKE PLANS TO THE COUNTY
 SO THEY UPDATE CLOSING THE EXISTING CARPORT TO STORAGE
 ROOM AND ADDITION OF REAR PORCH. NO ACTION WAS TAKEN BY
 THE COUNTY. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2016-02-24 Cont ID  
Sent By jgomez Date 2016-02-12 Time 13:22 Rev Time 0.00
Received By jgomez Date 2016-02-12 Time 12:57 Sent To  
Notes
2016-02-12 13:23:101-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-12-22 Cont ID  
Sent By jgomez Date 2015-12-22 Time 08:41 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 08:41 Sent To  
Notes
2015-12-22 08:41:411-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-09-18 Cont ID  
Sent By jgomez Date 2015-09-18 Time 10:42 Rev Time 0.00
Received By jgomez Date 2015-09-18 Time 10:42 Sent To  
Notes
2015-09-18 10:42:251-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By jgomez Date 2015-01-14 Time 09:05 Rev Time 0.00
Received By jgomez Date 2015-01-14 Time 09:05 Sent To  
Notes
2015-01-14 09:07:361-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-01-15 Cont ID  
Sent By jgomez Date 2015-01-15 Time 10:51 Rev Time 0.00
Received By jgomez Date 2015-01-14 Time 13:20 Sent To  
Notes
2015-01-15 10:52:24NO INFORMATION SUBMITTED AT THIS TIME.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2016-02-12 Cont ID  
Sent By jgomez Date 2016-02-12 Time 13:20 Rev Time 0.00
Received By jgomez Date 2016-02-12 Time 13:20 Sent To  
Notes
2016-02-12 13:22:01MODIFIED BITUMEN FLORIDA PRODUCT APPROVAL FL16709-R2.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2015-12-22 Cont ID  
Sent By jgomez Date 2015-12-22 Time 13:32 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 13:31 Sent To  
Notes
2015-12-22 13:33:011- FLAT ROOF LIQUID ROOFING NOA 13-0204.17 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC.
 NOTE: THREE ASSEMBLIES WITH DESIGN PRESSURES OF -60PSF
 WERE UNDERLINED ON NOA SUBMITTED. THESE THREE
 ASSEMBLIES ARE FOR INSULATED ROOF SYSTEMS. PLANS DON'T
 SPECIFY INSULATED ROOF SYSTEMS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301.
 NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION
 #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW ENHANCED
 FASTENING. SEE GENERAL LIMITATION #9 ON-LAST PAGE OF
 NOA SUBMITTED.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-09-18 Cont ID  
Sent By jgomez Date 2015-09-18 Time 18:50 Rev Time 0.00
Received By jgomez Date 2015-09-18 Time 18:50 Sent To  
Notes
2015-09-18 18:51:591- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON
 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW
 SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 *** RESPONSE:
 PROVIDE COMPLETE INFORMATION. ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE FL6623-R2 WAS SUBMITTED. AND, NEED
 TO IDENTIFY THE SELECTED ASSEMBLY.
 NOTE: ROOF LIQUID APPLIED ROOF SYSTEM FL6623-R2
 SUBMITTED SHOW ONLY ONE PRODUCT FOR WOOD DECKS. IT'S
 NOA 08-1112.14. THIS NOA EXPIRED ON 01/01/14. THEREFORE
 CAN'T NOT BE USED. NEED TO PROVIDE ANOTHER ROOF PRODUCT
 APPROVAL. KEEP IN MIND THAT IF SELECTED FLAT ROOF
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY
 R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL
 BE REQUIRED. ALSO, REVISE DRAWINGS ACCORDING TO FLAT
 ROOF PRODUCT APPROVAL SELECTED.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By jgomez Date 2015-01-14 Time 13:28 Rev Time 0.00
Received By jgomez Date 2015-01-14 Time 13:20 Sent To  
Notes
2015-01-14 13:30:04PROVIDE ROOF PRODUCT APPROVAL:
  
 1) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON
 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW
 SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-02-20 Cont ID  
Sent By ajones Date 2016-02-20 Time 12:10 Rev Time 0.00
Received By ajones Date 2016-02-20 Time 12:10 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-12-11 Cont ID  
Sent By   Date 2015-12-11 Time   Rev Time 0.00
Received By   Date 2015-12-11 Time   Sent To  
Notes
2015-12-11 10:35:5112/11/15 ZONING FAILED 3RD CHECKLIST
  
 1. SUBMIT TWO CERTIFIED UP TO DATE SURVEYS

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By lmarchan Date 2015-09-22 Time 10:30 Rev Time 0.00
Received By   Date 2015-09-04 Time   Sent To B
Notes
2015-09-04 14:26:369/4/15 ZONING FAILED
  
 1. SUBMIT TWO COPIES OF AN UP TO DATE SURVEY, SHOWING
 LOCATION OF ADDITION/CARPORT ENCLOSURE

Review Stop Z ZONING
Rev No 1 Status F Date 2015-01-20 Cont ID  
Sent By sgraham Date 2015-01-20 Time 15:51 Rev Time 0.00
Received By sgraham Date 2015-01-20 Time 15:51 Sent To  
Notes
2015-01-20 15:53:031/19/15 ZONING FAILED.
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY
 HIGHLIGHTING THE ADDITION AND THE CARPORT CORVERSION.


Account Summary | Usage Policy | Privacy Policy