| 2014-12-23 15:35:41 | 600 OKEECHOBEE BOULEVARD |
| | PERMIT #14120664 |
| | MASTER #14050111 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: PLANS INDICATE UNDERGROUND FIRE PROTECTION |
| | PIPING TO BE INSTALLED BY OTHERS. IS THIS TO BE DONE |
| | UNDER A SEPARATE PERMIT AND CONTRACTOR OR IS THIS PART |
| | OF SUMMER'S PERMIT AND SUMMERS IS HIRING A |
| | SUBCONTRACTOR? |
| | |
| | GENERAL: ELIMINATE THE 1-1/2" REDUCER FROM THE 2-1/2" |
| | HOSE VALVES. |
| | |
| | GENERAL: SUBMIT PRODUCT DATA FOR FIRE/JOCKEY PUMP, |
| | CONTROLLERS, TRANSFER SWITCH, PRESSURE REGULATING |
| | VALVES, BACKFLOW PREVENTERS, JOINT RESTRAINT |
| | ASSEMBLIES, PIPE, FITTINGS, HANGERS, ETC. |
| | |
| | GENERAL: NORTH ARROWS (ALL SHEETS) APPEAR TO BE |
| | POINTING IN THE WEST DIRECTION. |
| | |
| | SHEET FP-1: CANNOT LOCATE A SECONDARY FIRE DEPARTMENT |
| | CONNECTION REQUIRED FOR HIG-RISE BUILDINGS. |
| | |
| | SHEET FP-1: SPRINKLER NOTE #5 DOES NOT INDICATE WHICH |
| | ROOMS OR AREAS ARE DESIGNED AS LIGHT OR ORDINARY |
| | HAZARD. SHEET FP-2 EVEN INDICATES A STORAGE ROOM |
| | DESIGNATED AS ORDINARY HAZARD GROUP II WITH A DESIGN |
| | DENSITY OF 0.20 GPM/SF. |
| | |
| | SHEET FP-2: CONFIRM FIRE PUMP ROOM IS LARGE ENOUGH FOR |
| | PROPER INSTALLATION, CONTROLLER CLEARANCES AND WORKING |
| | SPACE. PROVIDE PLAN VIEW DIMENSIONING EQUIPMENT TO BE |
| | PROVIDED IN THIS ROOM. |
| | |
| | SHEET FP-2: COULD NOT LOCATE SPRINKLERS IN THE BASEMENT |
| | POOL EQUIPMENT ROOM #B020. |
| | |
| | SHEET FP-3: SPRINKLER COVERAGES IN SERVICE CORRIDOR |
| | APPEAR TO BE FOR LIGHT HAZARD. ORDINARY HAZARD MAY BE |
| | MORE APPROPRIATE FOR THE EQUIPMENT AND STORAGE |
| | TYPICALLY GATHERED IN THESE SPACES. |
| | |
| | SHEET FP-4: COULD NOT LOCATE SPRINKLER PROTECTION FOR |
| | HYDRAULIC SERVICE ELEVATOR ADJACENT TO STAIR #4. |
| | |
| | SHEET FP-6: VERIFY (WITH LOAD CALCULATIONS) BAR TERRACE |
| | CANOPY STRUCTURE CAN SUPPORT 5X THE WEIGHT OF |
| | WATER-FILLED SPRINKLER PIPE. |
| | |
| | SHEET FP-8: PUMP ROOM #253 IS LOCATED ON THE SECOND |
| | FLOOR. THESE SPRINKLERS WILL NEED TO BE SUPPLIED FROM |
| | THE SECOND FLOOR SYSTEM/FLOW SWITCH TO AVOID CONFUSION |
| | THINKING THERE IS A FIRE ON THE FIRST FLOOR WHEN IT IS |
| | ACTUALLY ON THE SECOND. |
| | |
| | SHEET FP-9: COULD NOT LOCATE A FIRE DEPARTMENT HOSE |
| | VALVE IN STAIR #3. |
| | |
| | SHEET FP-14: PLANS IN THE CENTRAL ELEVATOR LOBBY |
| | INDICATE AN 1-1/2" LINE GOING UP TO THE ROOF; HOWEVER, |
| | THE LINE SIZE INDICATES 1-INCH. |
| | |
| | SHEET FP-14: PLANS INDICATE RESIDENTIAL TYPE SPRINKLERS |
| | TO BE USED IN THE PRES SUITE #1238; HOWEVER, THE |
| | SCHEDULE INDICATES A QR TYPE SPRINKLER WITH A K-FACTOR |
| | OF 5.6. |
| | |
| | SHEET FP-16: THE FIRE PUMP ROOM SECTION VIEW SHOWS THE |
| | FIRE PUMP BEING FED FROM BELOW IN LIEU OF OVERHEAD. |
| | PROVIDE ACCURATE DETAIL ENSURING LAMINAR/NON-TURBULENT |
| | FLOW INTO THE FIRE PUMP SUCTION FLANGE. PER NFPA 20 |
| | (2007 EDITION) SECTION 5.14.6.3.2, THE DISTANCE OF THE |
| | FIRE PUMP SUCTION FLANGE AND ANY ADJACENT SUCTION PIPE |
| | ELBOW/TEE FLANGE SHALL BE SEPARATED BY AT LEAST 10 PIPE |
| | DIAMETERS WHEN THE ELBOW/TEE HAS A CENTERLINE PLANE |
| | PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT. NOTE: |
| | THE CODE REQUIREMENTS HAVE NOT CHANGED IN THE LATEST |
| | EDITION OF THE STANDARD; HOWEVER, DIAGRAMS OF |
| | CORRECT/INCORRECT SUCTION PIPE INSTALLATIONS HAVE BEEN |
| | UPDATED IN FIGURE A4.14.6 OF NFPA 20 - 2013 EDITION. |
| | |
| | GENERAL: FOR SYSTEM PRESSURES EXCEEDING 100 PSI, |
| | ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS |
| | SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL |
| | BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE |
| | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING |
| | UPWARD MOVEMENT. |
| | |
| | GENERAL: FOR THE AREAS EXPOSED TO STRUCTURE (NO |
| | CEILING) INDICATE IF THE SPACE IS OBSTRUCTED |
| | CONSTRUCTION OR UNOBSTRUCTED CONSTRUCTION AND INDICATE |
| | THE SPRINKLER DISTANCE BELOW THE STRUCTURE OR ROOF DECK |
| | (IF OBSTRUCTED CONSTRUCTION). |
| | |
| | GENERAL: PER NFPA 13 (2007 EDITION) SECTION 24.2.1.2, |
| | PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO SYSTEM |
| | WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE TESTED |
| | AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING PRESSURE |
| | AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR |
| | 2-HOURS. |
| | |
| | GENERAL: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES |
| | FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |
| | GENERAL: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | GENERAL: PROVIDE PERMANENT WEATHERPROOF SIGN MARKING |
| | THE FIRE DEPARTMENT CONNECTION. |
| | |
| | GENERAL: INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE |
| | ON EACH FLOOR. SPECIFY THE FLOORS THAT WILL HAVE |
| | PRESSURE REGULATING VAVLES AND THEIR DESIGN SETTINGS. |
| | RECOMMEND FIELD ADJUSTABLE TYPE VALVES. |
| | |
| | PRESSURE REGULATING VALVES: PER NFPA 14 SECTION 7.2.2 |
| | WHEN SYSTEM PRESSURE-REGULATING DEVICES ARE USED IN |
| | LIEU OF PROVIDING SEPARATE PUMPS, MULTIPLE ZONES SHALL |
| | BE PERMITTED TO BE SUPPLIED BY A SINGLE PUMP AND |
| | PRESSURE-REGULATING DEVICE(S) UNDER THE FOLLOWING |
| | CONDITIONS: |
| | (1) PRESSURE-REGULATING DEVICE(S) SHALL BE PERMITTED TO |
| | CONTROL PRESSURE IN THE LOWER ZONE(S). |
| | (2) A METHOD TO ISOLATE THE PRESSURE-REGULATING |
| | DEVICE(S) SHALL BE PROVIDED FOR MAINTENANCE AND REPAIR. |
| | (3) REGULATING DEVICES SHALL BE ARRANGED SO THAT THE |
| | FAILURE OF ANY SINGLE DEVICE DOES NOT ALLOW PRESSURE IN |
| | EXCESS OF 175 PSI (12.1 BAR) TO MORE THAN TWO HOSE |
| | CONNECTIONS. |
| | (4) AN EQUALLY SIZED BYPASS AROUND THE |
| | PRESSURE-REGULATING DEVICE(S), WITH A NORMALLY CLOSED |
| | CONTROL VALVE, SHALL BE INSTALLED. |
| | (5) PRESSURE-REGULATING DEVICE(S) SHALL BE INSTALLED |
| | NOT MORE THAN 7 FT 6 IN. (2.31 M) ABOVE THE FLOOR. |
| | (6) THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED |
| | WITH INLET AND OUTLET PRESSURE GAUGES. |
| | (7) THE FIRE DEPARTMENT CONNECTION(S) SHALL BE |
| | CONNECTED TO THE SYSTEM SIDE OF THE OUTLET ISOLATION |
| | VALVE. |
| | (8) THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED |
| | WITH A PRESSURE RELIEF VALVE IN ACCORDANCE WITH THE |
| | MANUFACTURERS RECOMMENDATIONS. |
| | (9) REMOTE MONITORING AND SUPERVISION FOR DETECTING |
| | HIGH PRESSURE FAILURE OF THE PRESSURE-REGULATING DEVICE |
| | SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 72, NATIONAL |
| | FIRE ALARM CODE. |
| | |
| | DRAIN: PER NFPA 14 SECTION 7.11.1 A PERMANENTLY |
| | INSTALLED 3 INCH DRAIN RISER WITH 2-1/2 INCH TEE (ON AT |
| | LEAST EVERY OTHER FLOOR) SHALL BE PROVIDED ADJACENT TO |
| | EACH STANDPIPE EQUIPPED WITH PRESSURE-REGULATING |
| | DEVICES TO FACILITATE TESTING OF EACH DEVICE. |
| | |
| | JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1, |
| | ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND |
| | HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT |
| | BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS. |
| | |
| | CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION |
| | 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS, |
| | WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE |
| | CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR |
| | OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL. |
| | |
| | HYDRAULIC CALCULATIONS: |
| | BASEMENT CALCULATION INDICATES A OH GROUP 1; HOWEVER, |
| | DRAWINGS AND CALCULATION INDICATE A DESIGN DENSITY OF |
| | 0.20 GPM/SF. |
| | |
| | CALCULATIONS INDICATE PRESSURES AVAILABLE AS HIGH AS |
| | 213 PSI? WHERE ARE THE 165 PSI PRVS IN THESE |
| | CALCULATIONS? |
| | |
| | NO CALCULATIONS PERFORMED OR SUBMITTED FOR ROOF LEVEL |
| | SPRINKLERS. |
| | |
| | CALCULATIONS DO NOT NECESSARILY SUPPORT THE MOST |
| | HYDRAULICALLY DEMANDING PORTION OF THE SYSTEMS |
| | CALCULATED. FOR EXAMPLE, THE 12TH FLOOR CALCULATION |
| | SUPPORTS THE USE OF TWO RESIDENTIAL STYLE SPRINKLERS ON |
| | A 1-INCH PIPE; HOWEVER, PRES SUITE #1238 SHOWS 3 |
| | SPRINKLERS SUPPLIED FROM AN 1-1/4" PIPE WHICH IS NOT |
| | SUPPORTED BY THE CALCULATIONS. THE BASEMENT LEVEL |
| | RESTROOM (MENS' B009) IS CERTAINLY LOCATED MORE REMOTE |
| | AND SUPPLIES 8 SPRINKLERS FROM 2-INCH PIPING WHICH IS |
| | NOT SUPPORTED BY CALCULATIONS. |
| | |
| | PLAN REVIEW HAS BEEN DISCONTINUED AT THIS TIME DUE TO |
| | TOO MANY COMMENTS. ADDITIONAL PLAN REVIEW COMMENTS MAY |
| | BE GENERATED WHEN PLANS ARE RESUBMITTED. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |