Plan Review Details - Permit 14120646
| Plan Review Stops For Permit 14120646 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-01-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-01-23 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-23 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-01-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-01-15 |
Time |
03:29 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-15 |
Time |
03:29 |
Sent To |
|
|
| Notes |
| 2015-01-15 03:45:42 | 1) THE MODEL NUMBER ON THE MANUFACTURER'S SPEC SHEETS | | | FOR THE GENERAC GENERATOR IS NOT LISTED IN THE APPROVED | | | GENERAC MODEL LIST ON SHEET 1 OF 3 OF THE AMERICAST | | | SLAB DRAWINGS.CLARIFY. | | | 2) THE MODEL NUMBER OF THE GENERATOR ON THE SUBMITTED | | | MANUFACTURER'S SPEC SHEET AND THE AMERICAST SHEET ARE | | | ALL DIFFERENT. CLARIFY.( THERE IS A SPEC SHEET WITH THE | | | GAS DRAWING AND TWO OTHER SHEETS WITH THE OLANS AND | | | NONE OF THE MODEL NUMBERS MATCH THE NUMBERS ON THE | | | AMERICAST PLANS.) | | | 3)TTHERE ARE CALCULATIONS DONE ON SHT, 1 OF THE | | | AMERICAST PLANS FOR THE GENERATOR ANCHORING BUT THESE | | | CALCULATIONS ARE FOR A KOHLER GENERATOR, NOT A GENERAC. | | | CLARIFY. | | | 4) IDENTIFY ON THE MANUFACTURER'S SPEC SHEETS THE | | | CORRECT MODEL OF THE GENERATOR BEING INSTALLED. WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 5) THE GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FT. | | | FROM THE EXTERIOR WALL PER NFPA 37 SEC.4.1.4. SHOW THE | | | DISTANCE FROM THE EXTERIOR WALL ON THE SURVEY. | | | 6) THE GENERATOR EXHAUST SHALL BE A MINIMUM OF 10 FT. | | | AWAY FROM ANY BUILDING OPENINGS. SHOW THIS ON THE | | | SURVEY. WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-12-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2014-12-23 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-12-23 |
Time |
16:37 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2014-12-23 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2014-12-23 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2014-12-23 |
Time |
13:13 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2015-01-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-01-15 |
Time |
03:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-15 |
Time |
02:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2014-12-24 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-24 |
Time |
05:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-24 |
Time |
05:10 |
Sent To |
|
|
| Notes |
| 2014-12-24 05:42:11 | 1) GALVANIZED PIPNG IS NOT PERMITTED BELOW GRADE PER | | | THE 2010 FL. GAS CODE SECS.403.8, 404.9, 404.9.2. | | | 2) ON THE SURVEY, SHOW THE DISTANCE OF THE GENERATOR | | | FROM THE EXTERIOR WALL OF THE STRUCTURE. COMPLY WITH | | | NFPA 37 SEC. 4.1.4. | | | 3) THE GENERATOR EXHAUST SHALL BE A MIN. 10 FT. FROM | | | ANY BUILDING OPENINGS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-01-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2015-01-23 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-20 |
Time |
09:56 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-01-15 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-01-15 |
Time |
03:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-01-15 |
Time |
02:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-12-24 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-24 |
Time |
05:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-18 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2014-12-18 13:55:38 | SENT TO ZONING BIN FOR REVIEW. JG. | | 2014-12-18 13:31:48 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-12-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-12-19 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-12-19 |
Time |
13:41 |
Sent To |
FIRE |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy