Plan Review Details - Permit 14120596
Plan Review Stops For Permit 14120596
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-02-02 Cont ID  
Sent By jgomez Date 2015-02-02 Time 11:16 Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 11:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-01-29 Cont ID  
Sent By jgomez Date 2015-01-29 Time 15:39 Rev Time 0.00
Received By jgomez Date 2015-01-29 Time 14:31 Sent To  
Notes
2015-01-29 15:39:27RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533 SUBMITTED
 :
  
 A) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF SYSTEM AND
 BASE SHEET FASTENING OPTION FROM PRODUCT APPROVAL
 PROVIDED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 B) IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1, THEN PROVIDE SIGNED
 AND SEALED NAIL ENHANCING CALCULATIONS (2 COPIES WITH
 ORIGINAL SEAL AND SIGNATURE). CALCULATIONS ARE USUALLY
 REFERRED AS RAS 117 CALCULATIONS.
  
 2- FLORIDA PRODUCT APPROVAL FL2533-R11 SUBMITTED WAS
 REVISED. THE CURRENT PRODUCT APPROVAL IS FL2533-R12.
 PLEASE PROVIDE TWO COPIES OF THE CURRENT PRODUCT
 APPROVAL. DCA RULE 9N-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By jgomez Date 2014-12-18 Time 09:48 Rev Time 0.00
Received By jgomez Date 2014-12-18 Time 09:48 Sent To  
Notes
2014-12-18 10:39:32RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS TO FBC. VALUATION WAS UPDATED TO
 $8,700. THE PERMIT FEE BALANCE IS $260.70.
  
 2- FLAT ROOF:
 A) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE FLAT ROOF SYSTEM TO BE INSTALLED.
  
 B) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF SYSTEM AND
 BASE SHEET FASTENING OPTION FROM PRODUCT APPROVAL
 PROVIDED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1, THEN PROVIDE SIGNED
 AND SEALED NAIL ENHANCING CALCULATIONS (2 COPIES WITH
 ORIGINAL SEAL AND SIGNATURE). CALCULATIONS ARE USUALLY
 REFERRED AS RAS 117 CALCULATIONS.
  
 3- SPECIFY SHINGLES ROOF PITCH TO VERIFY COMPLIANCE
 WITH SEC. R905.2.2 OF 2010 FBC-RESIDENTIAL.
  
 4- NOTICE OF COMMENCEMENT IS REQUIRED BY SEC,. 713 OF
 FLORIDA STATUTE.
  
 ***NOTE: PERMIT APPLICATION NEEDS OWNER'S NOTARIZED
 SIGNATURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-02 Cont ID  
Sent By jgomez Date 2015-02-02 Time 11:16 Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-29 Cont ID  
Sent By jgomez Date 2015-01-29 Time 14:31 Rev Time 0.00
Received By jgomez Date 2015-01-29 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-18 Cont ID  
Sent By jgomez Date 2014-12-18 Time 09:48 Rev Time 0.00
Received By jgomez Date 2014-12-17 Time 07:32 Sent To B
Notes
2014-12-18 07:33:15TO J. GOMEZ DESK