Plan Review Details - Permit 14120591
Plan Review Stops For Permit 14120591
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-12-30 Cont ID  
Sent By rmcdouga Date 2014-12-30 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2014-12-30 Time 18:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-14 Cont ID  
Sent By dhayes Date 2015-01-14 Time 14:37 Rev Time 0.00
Received By dhayes Date 2015-01-14 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By dhayes Date 2014-12-18 Time 07:49 Rev Time 0.00
Received By dhayes Date 2014-12-18 Time 07:49 Sent To  
Notes
2014-12-18 08:18:2612/18/2014
 PROJECT: WOMELSDORFF
 PERMIT#: 14120591
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 LEVEL 2 ALTERATION
 ACTION: DENIED
  
 1) LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. REVISE
 PLAN TO INCLUDE ALL GFI OUTLETS AS REQUIRED IN THE
 210.52(C)(1) WALL COUNTERTOP SPACES.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471,
 668.001-668.006
 FBC, WPB AMENDMENTS 107.2.1
  
 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, THE DWELLING UNIT SHALL BE EQUIPPED WITH
 SMOKE ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 REVISE PLANS TO ILLUSTRATE COMPLIANCE WITH THE FBC-R
 314 AND 315.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-14 Cont ID  
Sent By dhayes Date 2015-01-14 Time 14:38 Rev Time 0.00
Received By dhayes Date 2015-01-14 Time 13:56 Sent To  
Notes
2015-01-14 14:02:08SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-30 Cont ID  
Sent By rmcdouga Date 2014-12-30 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2014-12-17 Time 07:49 Sent To  
Notes
2014-12-18 07:48:41R05

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 10:35 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 10:20 Sent To  
Notes
***NONE***